Part A – MINOR STORAGE (incl. Packaged Store) <br><br>Definition of Minor Mixed Gas Storage per table 2.1 AS 4332 – The Storage & Handling of Gases in Cylinders
KEY REQUIREMENTS per AS 4332 – Storage & Handling of Gases in Cylinders
-
Cylinders kept away from heat sources e.g. boilers, steam pipes
-
All cylinders kept at least 3m clear of combustible materials
-
Adequate ventilation in all storage areas
-
Gas cylinder stores to be outside & separated from buildings & boundaries by > 3m if any 2.3 poisonous gases or if > 500L 2.1 flammable gases or > 1,000L 2.2/5.1 oxidizing gases
-
Fire protection equipment available e.g. if: <br><1000L stored – water hose connection e.g. garden hose <br>1000-2000L – one fire hose reel or at least one 9L Dry Powder fire extinguisher
-
All cylinders stored in an upright position and secured against falling e.g., chained
-
All relief devices positioned away from barriers or other cylinders
-
Full and empty cylinders stored separately & labelled e.g. “Empty” or “Full”
-
Cylinders regularly checked for faults, leaks and stock rotated
-
All cylinder contents are clearly identified and have applicable Class 2 diamonds e.g., 2.1 Flammable Gas
-
Storage floor in good condition and non-combustible
-
Suitable cylinder trolley available to move cylinders about in an upright manner
-
Appropriate Personal Protective Equipment (PPE) available, as required by MSDS
-
Smoking prohibited in gas storage area e.g. “NO SMOKING” signage posted
-
Oil and grease kept away from cylinder valves
-
No ignition sources if flammable gases present, including flame proof electrics e.g. AS 2430
-
Cylinders are stored at ground level and whenever possible outdoors
-
Training provided to persons handling and using Class 2 gases
-
Class 2 gases are separated from other dangerous goods stores by >3m and >1m from any door, window, duct or air vent in outdoor storage
-
Indoor minor stores of gases are separated from other minor gas stores or other dangerous goods by a minimum of >5m & < minor quantity indoors / 200m2
-
Class 2.1 Flam. gases segregated from Class 2.2, subsidiary risk 5.1 9e.g. oxygen) by >3m
-
Class 2.3 Toxic gases segregated from all other gases by >3m
COMMON REQUIRMENTS e.g. Minor Storage & Packaging Areas
-
Reg: 413 - Unauthorized access prevented e.g., site or departmental access controls
-
421 - DG storage protected from impact e.g. barriers if vehicular traffic
-
438 – MSDS’s readily accessible for all DG’s e.g. in vicinity of use
-
442 - Register of DG’s maintained & up to date
-
COP 39.3 - Quantity of DG’s kept to minimum required e.g. Limited to one day’s supply in immediate work area
-
- Cylinders labelled e.g. comply with AS 4332
-
- Any recent incidents involving DG’s? If so, please specify