SAFETY CHECKS
-
No flammables are present (Consider electronic gas detector for confined spaces)
-
Area clean and free of combustible materials within a 15 m radius
-
All drains within 15 m are covered with a wet fireproof blanket
-
A fire hose run out to job site and checked for supply & pressure
-
All sparks from work more than 2 meters above ground are contained by a suitable enclosure e.g., fire resistant canvas
-
Welding machines/gas cylinders are located not within 8 meters of any drain e.g., risk of flammable vapors accumulating in drain
-
Welding machine earthed directly to equipment being welded as close to welding point as possible e.g., to avoid arching & excessive sparks
-
Power leads are not draped across pipelines or access ways.
-
Coatings stripped for a distance of not less than 150mm (to minimize catching fire)
-
Any surface coatings checked for possibility of releasing toxic vapors when heated
-
Appropriate fire extinguishers ready to use and personnel trained to use emergency equipment
-
Person assigned to fire watch during and for at least 30 minutes after hot work ceases
-
The need for any extra ventilation is assessed
-
Fire resistant shields are covering combustibles
-
Fire alarm points identified prior to commencement and all personnel understand emergency plan for site.
-
Completion Signature
Hot Work Zone Set Up Checklist.<br><br>This is to be used for the establishment of permanent or long-term hot work zones. <br><br>All works conducted in this zone is exempt from completing a permit to work and hot work checklist.
AREA
-
Non-combustible, fire-resistant construction
-
Free of combustibles and flammables, including no cardboard boxes, cloths, paper or fuel. If storage required install metal cupboards
-
Designated working surfaces are non-combustible
-
Not within 8m of drains, to prevent build-up of flammable vapors.
-
Area is segregated and restricted access/ use to authorized persons. This may be the use of barriers/ welding curtains.
-
Suitable fire extinguisher/s within the zone and unobstructed.
-
No smoke detector, use heat detector instead
-
Equipment mechanical ventilation for work zone/ task location/s.<br><br>Tested to be sufficient for expected work tasks.
-
Signposted restricted access/use,
-
Allocated location for welding gases to be secured at all times.
-
Area free from becoming damp or wet.
-
no combustibles or flammables to be stored with 15m.
-
Evacuation route kept clear.
Procedures
-
Competency training and only authorized persons to conduct hot work
-
Prestart check of area daily to ensure clear of any dust, flammables, or combustibles, also check of equipment e.g., hoses for any punctures or weakness.