Motor 3.3 kV, 690v, 415v
-
The LCS and the FCI shall be one unit with two separate compartments, one for the power isolation section and one for the local control section. Each compartment shall have individual access doors.
IP 66
-
Minimum rating.
DOL / VSD
-
Which is fitted.
Thermistors
-
Are thermistors fitted?
Heater
-
Is heater fitted?
Cable Access
-
Small motors (<75kW), looped into a full pig-tail. Larger motors (75kW and above) require a slack full half-loop.
Motor Reversing
-
Phase reversing shall be performed at the motor terminal box by reversing RED and BLUE phases. Enough length needs to be left on cores to facilitate this action.
Earth Potential
-
Connected to the main earth bar via the equipotential earth backbone.
Labels
-
All equipment shall be identified by a label attached yo a non-detachable part.