Title Page
-
Site conducted
-
Conducted on
-
Completed by
-
PPM Task Number
-
• The temperature of blended (mixed) water outlets must be distributed between 39°C and 43°C.
• The temperature of cold water outlets must be distributed at or below 20°C.
• The temperature of hot water outlets must be distributed at or above 50°C .
For hot and blended outlets, run tap for 1 minute prior to recording temperature.
For cold outlets, run the tap for 2 minutes prior to recording temperature. -
Standard Checks – variation of these checks must have formal approval from the QHSE/Technical Manager.
• This task is to be carried out in accordance with the relevant Method Statement within Section 16 of the logbook.
• Remedial Actions Required refers only to physical inspection and measurements taken at time of visit.
• Remedial actions required due to out of specification sample results should be recorded and actioned as per Logbook Escalation Process.
C/D Ground
-
For hot and blended outlets, run tap for 1 minute prior to recording temperature.
For cold outlets, run the tap for 2 minutes prior to recording temperature.
College Cupboard - d1C0 9
-
Hot Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D0 11
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D0 12
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Toilet - d1D0 6
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Toilet - d1D0 7
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men's Disabled Toilet - d1D0-8
-
Mixed Temp °C
-
Remedial Actions Required
Ladies Disabled Toilet - d1D0-15
-
Mixed Temp °C
-
Remedial Actions Required
DG Floorplate Cupboard - d1D0 16
-
Hot Temp °C
Cold Temp °C
-
Remedial Actions Required
DG Selecta Cupboard - d1D0 10
-
Hot Temp °C
Cold Temp °C
-
Remedial Actions Required
C/D First Floor
-
For hot and blended outlets, run tap for 1 minute prior to recording temperature.
For cold outlets, run the tap for 2 minutes prior to recording temperature.
Men’s Toilet - d1D1 6
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Toilet - d1D1 7
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Toilet - d1D1 8
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Toilet - d1D1 5
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Disabled Toilet - d1D1 17
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D1 12
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D1 13
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D1 14
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D1 15
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Disabled Toilet - d1D1 10
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
D1 Selecta Cupboard - d1D1 11
-
Hot Temp °C
Cold Temp °C
-
Remedial Actions Required
D1 Floorplate Cupboard - d1D1 24
-
Note: Boiler has been removed
Cold Temp °C
-
Remedial Actions Required
C/D Second Floor
-
For hot and blended outlets, run tap for 1 minute prior to recording temperature.
For cold outlets, run the tap for 2 minutes prior to recording temperature.
Men’s Toilet - d1D2 5
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Toilet - d1D2 6
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Toilet - d1D2 7
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Toilet - d1D2 8
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Men’s Disabled Toilet - d1D2 17
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D2 12
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D2 13
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D2 14
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Toilet - d1D2 15
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Ladies Disabled Toilet - d1D2 9
-
Mixed Temp °C
Cold Temp °C
-
Remedial Actions Required
Cleaning Cupboard - d1D2 11
-
Hot Temp °C
Cold Temp °C
-
Remedial Actions Required
C2 Cleaning Cupboard - d1C2 06
-
Hot Temp °C
Cold Temp °C
-
Remedial Actions Required