Review Specification Section 230500- Basic Mechanical Requirements
-
Review the General Conditions and Contract Documents for compliance to the scope in this section
-
Review the Submittals associated with the work included in this scope of work and check all material for compliance.
-
Have all trades coordinated any clash or interference that may not be clear in the contract drawings?
-
Insert screenshot of coordinated drawings
-
Verify that all welded pipe is installed and true with right angles and joints are properly aligned.
-
Are all of the basic mechanical requirements found to be within the specification? If NO, please note all deficiencies and a plan of action to re-mediate.
Review Specification Section 230529- Mechanical Hangers and Supports
-
Verify that all pipe hangers and supports are in compliance with the specification for load capacities.
-
Verify that all fasteners are approved and installed as specified.
-
Verify that the maximum spacing for the CWP supports are not exceeded.
-
Verify that the proper size pipe supports allow for the required insulation thickness.
-
Insert photos
Review Specification Section- Mechanical insulation
-
Verify that sleeves are installed in thru-wall piping per the specification.
-
Insert photo's
Review Specification Section 232113- Hydronic Piping
-
Verify proper bevels were used in pipe to pipe and pipe to flange connections prior too root welds.
-
Visually inspect all welds for any cracking or slag inclusion.
-
Verify that all valves installed are approved as specified.
-
Has there been a full loop pressure test?
-
Insert photo documentation of pressure test.