Roof

Roof

Valve Stations

  • Gauges in place and working reading correct pressure

  • Paint is not pealing and missing

  • Defrost pressure between 65-70 PSI

  • Valve stems clean and lubricated

  • Valve stems have been exercised regularly

  • Pipe plugs in place

  • Ammonia drains for isolated filter/strainers.

  • No evidence of leaks

  • Electrical conduit and junction boxes are properly supported and undamaged

Pipe and Insulation Condition

  • Crossovers in place and in good condition

  • Piping does not have any rust or corrosion

  • Proper pipe labels being used and in place

  • Insulation does not have any cracking, gaps, holes, or damage.

  • Pipe labels easily legible and not damaged or pealing

  • Pipe saddles in place at pipe stands

  • Pipe stands in place and properly supporting pipes

Safety Relief Vent Line

  • Vent line exhaust 7.25 feet above working surface and 20 feet from any opening to the building.

  • Vent line sensor installed.

  • Rain cover in place on relief line to prevent contamination

Condenser

  • Fan belts are adjusted to specification with no damage

  • Fan blades are clean with no scale buildup

  • Bearings are greased, no noise while running

  • Piping is painted and does not have any rust or corrosion

  • Paint on piping is not pealing or damaged

  • Tubes are clean - check for corrosion and scaling. Must include at least 4 photos of the tubes with the water turned off.

  • Nozzles have good water pressure and coverage over tubes, none plugged.

  • Drift eliminators, sun blockers and fill media in place, clean, and in good condition

  • Water sump clean and free of debris

  • Water pumps running as needed with no leaks

  • Structural steel completely painted with no corrosion or damage

  • Electrical conduit and junction boxes are supported with no sags and undamaged

  • Water treatment is effective.

  • Valves and Handles painted and accessible

  • Drift Eliminators and nozzles easily accessible

DHU

  • Does this facility have a Dehumidification Unit

  • Filters in place and not clogged

  • Sensors in place and working correctly

  • Valves in working condition

  • Belts adjusted to specification and not damaged

  • Desiccant wheel in working condition

  • Equipment operating as designed

Machine Room

Machine Room

Condenser Pumps and Water Treatment

  • Condenser pumps working operating with no leaks

  • Condenser water is tested and results recorded daily.

  • Condenser Water Usage is Tracked

  • Condenser side stream filter is running. Water is clean

  • Condenser water treatment chemical feed equipment is working properly.

Underfloor Warming

  • Is there an Underfloor Air Blower for floor freeze protection.

  • Is the Blower Running

  • Is the Blower Drive mechanism and duct work in good condition.

  • Is the Blower drive belt adjusted properly and in good condition

  • Is there air flow through every underfloor air outlet.

  • Is there a Glycol underfloor warming for floor freeze protection

  • Heat exchanger Warming glycol to temperature set point

  • Relief valves in place and in compliance

  • Glycol pump runs when called for, is painted and clean with no leaks

  • Glycol temperature between 40-50 degrees

  • Glycol flow is appropriate

  • Glycol liquid level is appropriate

  • Glycol valves and flow adjusted to a minimum of 5* gpm, clean and undamaged. *5 gpm at 42" centers on pipe

  • Glycol temperature probes working properly

Cross Connection Regulator

  • Cross connection regulator set to design specifications and working

Compressors - Screw

  • Name plate legible

  • Relief valves in place and in compliance

  • Gauges in place and in and reading pressure correctly

  • Economizer open and working as designed

  • Set points set for operating conditions

  • Guards in place

  • Filter pressure within acceptable limits

  • Operating limits are properly set for conditions

  • Anchors and grouting tightened properly and undamaged

  • Safety switches in place and cutout points set and verified

  • Oil quality and changing is based on oil sampling analysis

  • Sensors reading accurately

  • Equipment is clean

  • Paint is in is not pealing or damaged

  • No oil leaks are evident

  • Valves will isolate as needed

  • Equipment is operating as designed for conditions

  • Starters are working as designed

Compressor - Reciprocating

  • Does system have Reciprocating Compressors?

  • Name plate legible

  • Relief valves in place and in compliance

  • Gauges in place and reading pressures correctly

  • Set points set up to operate at system pressure

  • Guards in place

  • Filter pressure within acceptable limits

  • Operating limits are set for conditions

  • Anchors tightened and grouting undamaged

  • Safety switches in place and will cut when activated

  • Oil quality and changing is based on oil sampling analysis

  • Sensors reading accurately

  • Equipment is clean

  • Equipment is operating as designed

  • No oil leaks are evident

  • Valves will isolate when closed

  • Starters are operating as designed

Vessels

  • Name plate / ASME stamp legible

  • Level controls will control level to set point

  • Linear Liquid Level Indicators protected (Glass Level Columns)

  • Bulls eyes visible and undamaged

  • Oil pots insulated with no damage or painted with not pealing paint

  • Oil Pot is properly rated for vessel temperature

  • Insulation in place with no damage

  • Feed valves control liquid feed at proper rate

  • All Safety float cut outs will cut out all compressors connected to vessell

  • Relief valves in place and in compliance

  • Piping shows no corrosion where visible

  • Equipment is clean

  • Valves are accessible, painted and in working condition

  • Electrical conduit and junction boxes are properly supported and undamaged

  • Equipment is operating properly

Ammonia Pumps

  • Pumps operating at correct pressures.

  • Gauges in place and and reading proper pressure

  • Equipment operation as designed

  • Does the system have Cornell pumps?

  • Oil cutout switch will stop pump on low oil

  • Rotary guard protecting pump from cavitation

  • Shaft seal in good condition - no seal leakes

  • Guards in place

Oil Recovery System

  • Oil recovery piping painted, no visible corrosion and supported properly

  • Vessel paint is not pealing and no visible corrosion

Floors, Walls and Room Cleanliness, and Door Signage.

  • Eyewash and Showers are located properly and Unobstructed

  • Doors are Self closing doors with panic hardware

  • The Room have two means of egress

  • Is the machine room restricted to authorized personal only?

  • Is There Proper Warning Signs on the Door?

  • No unauthorized storage in a machine room. Only refrigeration equipment and parts allowed

  • Ammonia cannot enter floor drains

  • Floors have no large cracks

  • Walls are clean and undamaged

  • Pipe penetrations in the walls are sealed

  • The machine room including tools and benches are clean?

Electrical / Panels

  • Electrical panels are clean, and doors closed

  • No unused penetrations are in panel, especially the top

  • Panel air filter is clean and fits opening correctly

Pipes and Insulation

  • Pipe hangers are adequate and adjusted to support pipe.

  • Manually operated valves that are inaccessible from floor must be operable from portable platforms, fixed platforms, ladders, or chain operated<br>

  • Pipes show no corrosion and are painted with no pealing paint

  • Insulation has no gaps or damage and pipe saddles are in place

  • Pipe and equipment labels are in place and meet IIAR standards

High Pressure Reciever

  • Ammonia level within acceptable range

  • High pressure receiver is painted, paint is undamaged and the vessel clean with no visible corrosion

  • Safety Relief valves in place and in compliance

Ammonia Dispersion Tank

  • Dispersion tank is in painted and clean with no visible corrosion and no leaks

  • Tank has proper water level

Transfer Hose

  • Transfer hose is suitable for ammonia and certification date has not expired

HVAC

  • Does the main refrigeration system provide cooling to the HVAC system?

  • Heat exchanger working to design specifications

  • Relief valves in place and in compliance

  • Pump in working condition

  • Temperature set to design specifications

  • Glycol flow is acceptable

  • Valves are accessible and working to isolate when needed

  • Temperature probes reading proper temperature

Purger

  • Equipment clean and bubbler easy to see through

  • Insulation in place and in good condition

  • Purger operation is removing Non-Condensables. No leaks.

  • Purger cycle counts recorded

Exhaust System

  • Ammonia detection Alarms at 25 ppm and shutdown is at 250 ppm

  • Exhaust system operates when ammonia is detected

  • Exhaust system meets IIAR2-2008 standards

  • Fan belts are adjusted to specification and show no damage

  • Fan blades in are clean and undamaged

  • Intake dampers are in proper location and working when called for

  • Exhaust fans can be started manually from outside the engine room

Evaporators

Evaporators

Freezer Evaporators / Penthouses

  • Unit defrosting cleanly with no ice bridges

  • Temperature set points set to quality control standards. See separate document provided by facility for standards.

  • Penthouse doors closing and sealing tightly

  • Electrical conduit and junction boxes in good condition

  • Fans are working properly

  • No excessive ice buildup

  • Coils clean

  • Unit clean

  • Heat trace in place and working

  • Drains in good condition and clear

  • Condensate drip pans are free of ice with no damage

  • Support hangers in place and properly adjusted

  • Guards in place

  • Equipment operating as designed

  • Sensors in place and working properly

  • Piping properly painted with no visible corrosion

  • Insulation in place with no cracks, holes, separation, or damage

  • Does the facility have an ice cream freezer system separate from the main refrigeration system

Ice Cream Freezer

  • Temperature set points set properly

  • Is discharge pressure in normal range

  • I suction pressure in normal range?

  • Is compressor motor amperage in normal range

  • Is evaporator super heat adjusted properly?

  • Does the system have a glycol cooled condenser?

  • Is the glycol in and out temperatures adjusted properly?

  • Unit defrosting properly

  • Electrical conduit and junction boxes in good condition

  • Fans clean and working properly

  • No excessive ice buildup

  • Unit clean

  • Heat trace in place and working

  • Drains in good condition and clear

  • Condensate drip pans in good condition

  • Support hangers in place and properly adjusted

  • Guards in place

  • Equipment operation good

  • Sensors in place and working properly

  • Piping in good condition

  • Insulation in place with no cracks. holes or damage

Cooler Evaporators / Penthouses

  • Unit defrosting properly

  • Temperature set points set properly

  • Doors closing and sealing properly

  • Electrical conduit and junction boxes in good condition

  • Fans in good condition and working properly

  • No excessive ice buildup

  • Coils clean

  • Unit clean

  • Heat trace in place and working

  • Drains clear and draining properly

  • Condensate drip pans are free of ice and show no damage

  • Support hangers in place and properly adjusted

  • Guards in place

  • Equipment operation good

  • Sensors in place and working properly

  • Piping properly painted with no visible evidence of corrosion

  • Insulation in place and in good condition

Dock Evaporators / Penthouses

  • Unit defrosting properly

  • Temperature set points set properly

  • Doors closing and sealing properly

  • Electrical conduit and junction boxes are properly supported and undamaged

  • Fans clean and working

  • No excessive ice buildup

  • Coils clean

  • Unit clean

  • Heat trace in place and working

  • Drains clear

  • Condensate drip pans free of ice and no damage

  • Support hangers in place and adjusted to support unit

  • Guards in place

  • Equipment operating as designed

  • Sensors in place and reading proper temperature and pressure

  • Piping properly painted with no evidence of corrosion

  • Insulation in place, no cracks holes or damage.

Controls / Electrical

Cleanliness of Control Cabinets

  • HOA Switches set correctly for current operation

  • Cabinets undamaged and clean inside and out

Electrical Panels

  • Panels undamaged and clean inside and out

  • No unused penetrations that are not plugged

Temperature and Pressure Sensors

  • Sensors set up and reading proper temperature and pressure

Ammonia Detectors and Operation

  • Ammonia detectors in designated locations and working

Labeling

  • Labeling of piping, equipment and door signs meets IIAR standards

Alarm Settings

  • Alarm settings are set properly and active

Paperwork / Safety Equipment

Paperwork / Safety Equipment

  • Proper P&ID displayed

  • Does emergency shutdown documentation exists

  • Emergency shutdown valves tagged

Alarms Audible and Visual

  • Alarms are both audible and visual at each Machine Room entrance door.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.