Information

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

Previous Inspection

  • Have all outstanding actions/issues been completed from the previous audit?

Emergency Preparedness

  • Is the Emergency Manual available?

General Safety

  • GS 1: GENERAL AREA:<br>1. Temperature Comfortable?<br>2. Areas free from odors?<br>3. Noise levels is acceptable/adequately controlled?<br>4. Ventilation is adequate?<br>5. Stair treads and handrails present, safe & secured?

  • GS 2: No items stored under sinks that can absorb moisture?

  • GS 3: No broken/damaged/unused equipment or furniture stored on the patient care units?<br> Coverings are intact - no rips or repairs needed?

  • GS 4: Are all electrical appliances (coffee makers, microwaves, radios, etc.) properly wired (3 prong/UL) & appear to be in good working condition?

  • GS 5: Potential Safety Hazards: <br> 1. Housekeeping & Maintenance carts & buckets are attended and lock?

  • GS 6: LADDERS<br> 1. Are all ladders industrial strength (Non Household rated, check label)? <br> 2. Are ladders in good condition?<br> 3. Are ladders non conductive (Fiber glass)?<br> 4. Are ladders stored properly?<br>

  • GS 7: Are entry & walkways kept clear?

  • GS 8: Are docks, ramps & stairways in good repair and properly lighted?

  • GS 9: Are floor surfaces even & uncluttered, free of cracks, holes & tipping hazards?

  • GS 10: Is the floor clean & well maintained?

  • GS 11: Are non-slip surfaces adequate & in good repair?

  • GS 12: Is extension cord/power tab policy being enforced?

  • GS 13: Hazardous rooms are locked: EVS closets, supply closets, mechanical/electrical rooms & electrical panels?

  • GS 14: Are utility rooms in good order?

  • GS 15: Are sterile supplies & soiled equipment stored seperately?<br>

  • GS 16: Refrigerators: Contain only those items designed for the refrigerator (specimen, medications or patient/employee food)?

  • GS 17: Are blanket warmers set to maintain temperature of 130 degrees?

  • GS 18: Outer shipping carton boxes are empty & removed as soon as possible?

  • GS 19: Is equipment properly stored when not in use?

  • GS 20: Is staff able to locate the disaster, SDS and policy manuals?<br>*All manuals contain current information.

  • GS 21: Linen and Linen Carts are Covered and carts have solid bottoms.

  • GS 22: THERE ARE NO OTHER ABNORMALITIES OR INFRACTIONS?

HAZ

  • HAZ 1: Caution X-Ray signs are posted?

  • HAZ 2: Are pregnancy warning signs posted?

  • HAZ 3: Are all MRI Safety Zones posted?

  • HAZ 4: If required is PPE available?

  • HAZ 5: Is chemical signage appropriately displayed?

  • HAZ 6: Are hazardous chemicals and flammable agents labeled and stored properly?

  • HAZ 7: Are gas cylinders stored appropiately?

  • HAZ 8: Is the HMI (Hazardous Material Inventory) current Online?

  • HAZ 9: Can the staff locate the HMI?

  • HAZ 10: No hazardous chemicals /materials stored over shoulder high or where it can be knocked over?

  • HAZ 11: Are emergency eye washes & safety showers tested and inspection tags are present?

  • HAZ 12: Are eye washes & showers easily accessed?

  • HAZ 13: Are housekeeping carts locked in patient care areas?

  • HAZ 14: Are Hazardous Materials and drugs in proper waste stream?

  • HAZ 15: Are all compress gas cylinders securely mounted?

  • HAZ 16: Is there adequate spill containment for 30 & 55 gallon drums?

  • HAZ 17: Are all flammable liquids kept in approved containers?

  • HAZ 18: Does the volume stored meet the requirements for storage?

  • HAZ 19: Are oily rags and combustible refuse in covered metal containers (Shops)?

  • HAZ 20: Are needles, syringes, sharps & glass disposed of properly?

  • HAZ 21: Biohazard waste:<br> 1. Discard in Red Bags with a biohazard symbol<br> 2. Not overfilled<br> 3. Covered containers<br> 4. Contains only biohazards waste, no trash<br> 5. Stored in a secure area

  • HAZ 22: Soiled Linen: Properly stored in closed container and not overfilled.

  • HAZ 23: Sharps Waste:<br> 1. Placed in punctured resistant sharps container with lid.<br> 2. Disposed of when 3/4 full or "full" indicator.<br> 3. Mounted appropriately.<br> 4. Stored in secure location.

  • HAZ 24: THERE ARE NO OTHER ABNORMALITIES OR INFRACTIONS?

Life Safety/Fire Management

  • LS 1: Is the fire alarm system functioning (look for in-terminate lights) correctly?

  • LS 2: Nothing stored on top of flammable storage cabinets?

  • LS 3: Appropriate storage to maintained 18" clearance from ceiling?

  • LS 4: Oxygen or other combustible compressed gas cylinders are stored properly:<br> 1. Secured in floor stand, carrier or secured to the wall by a mount (not laying on the floor or against the wall).<br> 2. Labeled and separated, full from empty.

  • LS 5: Fire exits and hallways are cleared:<br> 1. Egress corridors must have 8' clearance.<br> 2. Equipment in corridors must be in use within 30 minutes to remain in corridor.

  • LS 6: Are fire hydrants, fire extinguishers, and standpipes accessible?

  • LS 7: Fire alarm pull stations, fire extinguishers, medical gas shutoff valves and electrical panels are not blocked?

  • LS 8: Have Fire extinguishers been inspected monthly? Annually?

  • LS 9: Are fire extinguishers proper size and type (Surgery,. MRI., Food Service, IT., etc.)?

  • LS 10: Maximum of 2-32 gallon trash cans in a 10x10 room (unless fire rated)?

  • LS 11: Are "EXIT" doors unlocked or equipped with "panic bars"?

  • LS 12: Are fire doors kept closed or magnetically held open?

  • LS 13: Fire doors are not blocked, wedged or propped and when closed is positive latching?

  • LS 14: Are fire doors free of damage and do they close properly?

  • LS 15: Is 20% rule being violated? No combustibles on fire rated doors and walls?

  • LS 16: Anything hung on the wall fire rated? Proof?

  • LS 17: Exit signs are illuminated and readily visible/undamaged?

  • LS 18: Are all sprinkler heads clean, in good shape and escutcheons tight/in place?

  • LS 19: Ceiling tiles are in place, no cracks, holes, misaligned or visible stains?

  • LS 20: Is space being utilized appropriately?

  • LS 21: Is staff lounge guidelines being followed?

  • LS 22: Are stairways free of storage?

  • LS 23: Floors, ceilings, walls and other surfaces intact and free from holes, damage and soiling?

  • LS 24: Laundry chute accesses are latched?

  • LS 25: Is corridor clearances being maintained according to occupancies?

  • LS 26: Is 36" clearance maintained around electrical panels?

  • LS 27: THERE ARE NO OTHER ABNORMALITIES OR INFRACTIONS?

Medical Equipment

  • ME 1: Are bio-medical equipment stickers on patient equipment current?

  • ME 2: Power tabs/hospital surge protectors used in patient care areas?

  • ME 3: THERE ARE NO OTHER ABNORMALITIES OR INFRACTIONS?

Security

  • SEC 1: Are valuables secured (purses, expensive equipment, etc.)?

  • SEC 2: Does the area appear to be secure?

  • SEC 3: Confidential Patient Information: Cannot be overhead or seen by unauthorized persons:<br> 1. Computer terminals signed off when not in use.<br> 2. Patient information is not discussed in public areas.<br> 3. No patient information visible to unauthorized persons.

  • SEC. 4: No clipboards displayed as sign-in sheets when multiple patient names on the list?

  • SEC 5: If fax machine is in a public area patient information is quickly removed?

  • SEC 6: THERE ARE NO OTHER ABNORMALITIES OR INFRACTIONS?

Utilities Management

  • UM 1: Are switch plates & outlets covered?

  • UM 2: Are all electrical cords, plugs and switches in good order?

  • UM 3: Are Medical Gas Valve accessible, labeled & clean?

  • UM 4: Can the staff locate the medical zone shutoff valves?

  • UM 5: Electrical Safety<br> 1. Use of hospital grade power strips, plugs & receptacles in good condition?<br> 2. Wires neat and controlled with no trip hazards?

  • UM 6: Is adequate ventilation provided?

  • UM 7: THERE ARE NO OTHER ABNORMALITIES OR INFRACTIONS?

Exteriors/Grounds

  • EX 1: No damage, uneven surfaces, surface quility?

  • EX 2: Surface differences more the 1/2" accross?

  • EX 3: Are cracks greater than 1/2" accross?

  • EX 4: Are manholes and vault covers secure?

  • EX 5: Is the vehicles barriers undamaged and properly placed?

  • EX 6: Are the walkways clear, unobstructed by bushes etc.?

  • EX 7: Are parking lots properly maintained to provide a safe driving & walking area?

  • EX 8: Is handicapped parking available?

  • EX 9: THERE ARE NO OTHER ABNORMALITIES OR INFRACTIONS?

Infection Prevention

  • IP 1: Food and drink in designated areas: no employee food of drinks in the public/patient areas, should be limited to private offices or break rooms.

  • IP 2: Boxes stored on shelves close to floor must have solid bottom and high enough to not incur water damage?

  • IP 3: General Cleanliness:<br> 1. Observe surfaces for high dust & residue, floors, stairwells, nutritional area, med prep areas, lobby, exam rooms, bathrooms, equipment, decorative items, curtains, blinds or drapes.<br> 2. No blood or bodily fluids.<br> 3. Staff using hospital approved cleaning products according to manufacturer's recommendations.

  • IP 4: Coverings are clean and intact on exam tables, phlebotomy chairs, chairs in waiting areas and exam rooms - no rips or repairs needed. Coverings can be cleaned/disinfected with hospital approved product.

  • IP 5: THERE ARE NO OTHER ABNORMALITIES OR INFRACTIONS?

Notes and Comments

  • Report conclusion including any other recommendations.

  • Certificates, license, etc.

Sign Off

  • Your signature or reply (email) acknowledgement when the recommended corrective actions are completed.

  • Auditors Signature

  • Select date

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.