Installation
-
Dip switch behind connectors set to 60 Hz
-
Incoming power to L1. L2 and L3
-
Motor leads hooked to U, V and W
-
Relay between 5 and 9
-
Analog in a between 3 and 4 for current or 1 and 2 for 0-10 vdc
-
Analog out from 12 and 13
-
Dip switch AIN1 and AIN2 set up for current or down for 0-10 Vdc
Parameters
-
Setup done
-
P0003 User access level set to 3
-
P0100 Europe/North America. Set to 1
Motor setup
-
P205 Inverter application. Set to 1
-
0 - Constant torque 1 - Variable torque
-
P0300. Motor type. Set to 1
-
P0304. Motor voltage. Set to 575
-
P0305. Motor current. Set to nameplate.
-
P0311 motor RPM. Set to nameplate
-
P335 - Motor cooling set to 0
-
P0640 motor overload. Set to 100%
-
P0700. Command source. Set to 2
-
0 - Factory default
1 - Keypad
2 - Terminal strip
4-6 - Comm link -
P0701 digital input #1. Set to 1<br>
-
0 - Off
1 - On/off
9 - Reset fault
16 - fixed set point and on -
P731 Digital output. Set to 52.3. Fault
-
52.2. Drive running
52.3. Drive fault
Analog input
-
P0756 Type of ADC. Set to 2
-
0 - 0-10 Vdc
1 - 0-10 Vdc with monitoring
2 - 0-20 ma
3 - 0-20 ma with monitoring
4 - -10--+10 Vdc -
P757 Value of x1 Set to 4
-
P0758 value of y1. Set to 0
-
P0759. Value of x2. Set to 20
-
P0760. Value of y2. Set to 100
Analog output
-
P0776. Type of DAC. Set to 0
-
0 - Current output
1 - Voltage output -
P0777 Value of x1. Set to 0
-
P0778. Value of y1. Set to 0 or 4 ma.
-
P0779. Value of x2. Set to 100
-
P0780 Value of y2. Set to 20 ma.
Set speed control
-
P1000. Frequency set point. Set to 2
-
1 - keypad
2 - analog in
3 - fixed frequency put into P1001 -
If keypad or MOP set P1031 to 1 to save set-point to memory in case of power failure
-
P1001. Fixed frequency #1. If used set to P0701 to 15 and enter frequency
-
P1080. Min. Frequency. Set to 30
-
P1082. Max. Frequency. Set to 60
-
P1120. Ramp up time. Set to 10
-
P1121. Ramp down time. Set to 30
Protection
-
P1210. Automatic restart. Set to 6
-
P1211. Number of restarts. Set to at least 5
-
P1300. Control mode. Set to 2 for fans and pumps
Used for first time setup
-
P1910. Select motor data identification. Set to 1
-
When this done you will get an error the next on cycle will check motor. You have to wait and the second motor cycle will reset error
-
P3900 End quick commissioning. Set to 3