Power wires to L1, L2 and L3 for 3 phase and L1 and L2 for single phase
-
Motor leads to T1, T2 and T3
-
Relay between DI1 and DCM.
-
Analog out from Ao and ACM 0-10 Vdc only<br>
-
Analog in to AI and ACM 4-20 ma
Parameters Motor Setup
-
P0.00. Motor voltage.
-
P0.01. Motor ampers
-
P0.02. Motor frequency Default 60
-
P0.04 maximum frequency. Default 1750
Ramp parameters
-
P1.00 stop method. Default 00 ramp
-
00 - Ramp to stop
01 - Coast to stop -
P1.01 acceleration time. Default 10 sec.
-
P1.02. Deceleration time. Default 30 sec.
Volts/hertz settings
-
P2.00 volts/hertz a settings. Set to 02
-
00 - general purpose.
01 - high starting torque.
02 - fans and pumps.
03 - custom
Digital parameters
-
P3.00. Source of operation command. Set to 01
-
00 - keypad.
01 - external contacts keypad stop is enabled.
02 - external contacts keypad stop is disabled.
03 - comm interface keypad stop is enabled.
04 - comm interface keypad stop is disabled. -
P3.01-P3.10 multifunction terminals. <br>P3.02 external reset. Input to DI3 set to 02
-
P3.11. Output terminal #1. Set to 01 for fault
-
P3.12. Output terminal #2
-
00 - drive running 01 - Fault 02 - At speed 03 - Zero sped 07 - Over torque 08 - Above current 09 - Below current
Analog parameters
-
P4.00. Source of frequency command. Use 03 for 4-20ma input
-
01- frequency from keypad
02 - frequency from 0-10 Vdc input
03 - frequency from 4-20 ma input
04 - frequency from 0-20 ma input
05 - frequency from comm interface
06 - frequency from -10 to + 10 Vdc -
P4.11 analog output. set to 01 for current.
-
00 - frequency.
01 - current.
02 - process variable -
P4,12 analog output gain. Default 100%
Protection parameters
-
P6.00. Overload relay. Use 01 for standard motors
-
00 - frequency drive rated motors.
01 - standard motors.
02 - inactive -
P6.01. Auto restart. Set to at least 5
-
P6.02. Momentary power loss. Set to 02 to continue running
-
00 - stop.
01 - continent running speed search from speed reference.
02 - continues running speed search from zero speed -
P6.03. Reverse operation. Disable 01
-
00 - enable.
01 - disable. -
P6.11 Over current stall prevention. Default 150%. Reduces motor speed when overloaded set to 100% of motor current<br><br>
-
P6.12 maximum power loss time. Set to .3 sec.
-
P6.13. Base block time. Set to 5.0 sec.
-
P6.30. Line lock out. Set to 01. Disable
-
00 - enable line lock out.
01 - disable line lock out.