Installation

  • Power wires to L1, L2 and L3 for 3 phase and L1 and L2 for single phase

  • Motor leads to T1, T2 and T3

  • Relay between DI1 and DCM.

  • Analog out from Ao and ACM 0-10 Vdc only<br>

  • Analog in to AI and ACM 4-20 ma

Parameters Motor Setup

  • P0.00. Motor voltage.

  • P0.01. Motor ampers

  • P0.02. Motor frequency Default 60

  • P0.04 maximum frequency. Default 1750

Ramp parameters

  • P1.00 stop method. Default 00 ramp

  • 00 - Ramp to stop
    01 - Coast to stop

  • P1.01 acceleration time. Default 10 sec.

  • P1.02. Deceleration time. Default 30 sec.

Volts/hertz settings

  • P2.00 volts/hertz a settings. Set to 02

  • 00 - general purpose.
    01 - high starting torque.
    02 - fans and pumps.
    03 - custom

Digital parameters

  • P3.00. Source of operation command. Set to 01

  • 00 - keypad.
    01 - external contacts keypad stop is enabled.
    02 - external contacts keypad stop is disabled.
    03 - comm interface keypad stop is enabled.
    04 - comm interface keypad stop is disabled.

  • P3.01-P3.10 multifunction terminals. <br>P3.02 external reset. Input to DI3 set to 02

  • P3.11. Output terminal #1. Set to 01 for fault

  • P3.12. Output terminal #2

  • 00 - drive running 01 - Fault 02 - At speed 03 - Zero sped 07 - Over torque 08 - Above current 09 - Below current

Analog parameters

  • P4.00. Source of frequency command. Use 03 for 4-20ma input

  • 01- frequency from keypad
    02 - frequency from 0-10 Vdc input
    03 - frequency from 4-20 ma input
    04 - frequency from 0-20 ma input
    05 - frequency from comm interface
    06 - frequency from -10 to + 10 Vdc

  • P4.11 analog output. set to 01 for current.

  • 00 - frequency.
    01 - current.
    02 - process variable

  • P4,12 analog output gain. Default 100%

Protection parameters

  • P6.00. Overload relay. Use 01 for standard motors

  • 00 - frequency drive rated motors.
    01 - standard motors.
    02 - inactive

  • P6.01. Auto restart. Set to at least 5

  • P6.02. Momentary power loss. Set to 02 to continue running

  • 00 - stop.
    01 - continent running speed search from speed reference.
    02 - continues running speed search from zero speed

  • P6.03. Reverse operation. Disable 01

  • 00 - enable.
    01 - disable.

  • P6.11 Over current stall prevention. Default 150%. Reduces motor speed when overloaded set to 100% of motor current<br><br>

  • P6.12 maximum power loss time. Set to .3 sec.

  • P6.13. Base block time. Set to 5.0 sec.

  • P6.30. Line lock out. Set to 01. Disable

  • 00 - enable line lock out.
    01 - disable line lock out.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.