Title Page

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Building Location

Instructions

  • 1. Click "Add Door" below under "Fire Door Inspection" to add a new fire door to be inspected
    2. Fill in the relevant door information and answer whether door is Compliant
    3. If you answer "No" for Compliant, attach any supporting notes and photos
    4. When complete sign off

Fire Door Inspection

  • Add Door

  • Door
  • Enter door number

  • Select Fire-Rating

  • Enter door location

Door Frame

  • Is the frame in a good state of repair

  • Is the door frame securely attached to the wall?

  • Is the frame to door leaf gap consistently 3mm?

  • If a planted door stop is present, is it firmly attached?

Door Seals

  • Are intumescent seals in place?

  • Are the seals well attached inside the groove in the door leaf or frame?

  • Are brush or fin type seals free from damage?

  • Are the smoke seals continuous around the door leaf or door frame?

Door Hinges

  • Is there a minimum of 3 hinges with all the screws fitted?

  • Are all the screws the correct size?

  • Are the hinges free from non-combustible packaging?

Door Closers

  • Open the door to 75mm or 5 degrees. Does it close and engage with the latch?

  • Is the closer securely attached to the door and the frame?

  • Is the closer free from damage?

  • If unlatched/open does the closer hold the door in line with the frame and intumescent seal?

  • If hung in pairs, do they close in line if both are opened and released together?

Lock & Latch

  • Does the latch hold the door firmly in the frame without rattling

Glazing & Glass

  • Is the intumescent seal continuous and attached to the glass and bead?

  • Are the glazing beads well attached to the frame and free from damage?

  • Is the glass free from cracking or damage

  • If the glass has been replaced is it fire rated glass?

Threshold Gap

  • Is there a consistent gap under the door that allows it to swing without touching the floor covering?

  • Is the door to floor covering gap consistently 10mm (3mm if smoke seals are fitted) or less when the door is closed?

  • If the door leaf is fitted with a threshold seal, does the seal make contact with the floor covering when the door is closed?

Compliance

  • Compliant

Completion

  • Inspected by

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.