Chemical Storage/Safety
-
Shelving is equipped with restraints to prevent items from falling off. Racks/shelves are secured. (IFC 3404.3.3.5.2)
-
NFPA Placard is present and up-to-date on room doors.
-
When the chemical fume hood is unattended, the sash shall be closed. (NFPA 45-8.8.3.2)
-
Compressed gas cylinders are standing up, and secured with a chain with a minimum thickness of .25", or similar restraint. (IFC 3003.5.3, CGA)
-
Compressed gas cylinders not "in use" shall not be stored in the laboratory. (NFPA 45-11.1.6.4)
-
All chemicals are properly labeled. (NFPA 45-9.2.3.4)
-
Chemicals are dated when first opened. (NFPA 45-9.2.3.4)
-
Chemicals are stored appropriate. (NFPA 45-9.2.3.2 & 9.2.3.3)
-
Chemicals shall not be stored in fume hoods. (NFPA 45-9.2.3.7)
-
Chemical inventories shall be maintained within the maximum allowable quantities as specified in the Code. (IFC table 307.1(1))
Egress/Corridors/Exiting
-
Exits and corridors are not obstructed. (IFC 1003.6)
-
Exit signage functions and is located properly. (IFC 1011.1)
Electrical/Lighting
-
Electrical rooms are free of clutter and storage. (IFC 315.2)
-
Electrical panels require 36" clearance in front. (IFC 605.3)
-
Electrical cords are in good condition. (IFC 605.1 & 605.5)
-
Multiplug adapters shall be directly connected to a permanently installed receptacle. (IFC 605.4.2)
-
Electrical extension cords shall not be used as a substitute for permanent wiring and shall only be used for portable appliances. (IFC 605.5)
-
Electrical receptacles located near a water source shall be protected by GFCI. (IFC 605.1)
-
Emergency lighting functions properly. (IFC 1006.1)
Elevator Machine Room
-
Machine room is free of storage. (ASME A17.1)
-
Machine room has a fire extinguisher with a minimum rating of 2A:10B:C (ASME A17.1)
Fire Alarms/Detectors (ITM)
-
Fire alarm test shall be conducted semi-annually (NFPA 72.14.3)
-
Smoke detectors shall be installed in each sleeping room and interconnected in R-2 Occupancies. (IFC 907.2.11.2 & 907.2.11.3)
Fire Sprinklers (ITM)
-
Automatic Fire Sprinkler Systems shall be inspected and tested semi-annually. (NFPA 25.5)
-
Automatic Fire Sprinklers shall be installed in all R-2 Occupancies. (IFC 903.2.8)
Fire Resistance Rated Construction
-
All walls, ceiling and rated partitions shall be maintained. Includes door props. (IFC 703.1)
-
Fire doors shall not be blocked or obstructed. (IFC 703.2)
Housekeeping
-
Storage shall be maintained 2' or more below the ceiling in non-sprinklered areas of buildings. (IFC 315.2.1)
-
Storage shall be maintained a minimum of 18" below fire sprinkler head deflectors. (IFC 315.2.1)
-
Combustible material creating a fire hazard shall not be allowed to accumulate in buildings. (IFC 304.1)
-
Storage shall be orderly and not subjected to heating appliances. (IFC 315.2)
Kitchens
-
Class K portable fire extinguisher shall be provided for commercial cooking equipment involving vegetable or animal oils and fats. (IFC 904.11.5)
-
Fire extinguishing systems in commercial kitchen hoods shall be serviced at least semi-annually. (IFC 904.11.6.2)
-
Inspections of hoods, fans, ducts and devices shall be conducted at intervals not to exceed 6 months and cleaned if necessary. (IFC 609.3.3.1)
Occupant Loading
-
Occupant load is exceeded. (IFC Table 1015.1)
Portable Fire Extinguishers
-
Extinguishers are not present or travel distance is more than 75 feet. (IFC 906.1)
-
Inspections/service is more than 1 year. (IFC 906.2)
-
Extinguisher is not mounted. (IFC 906.7)
-
Extinguisher is obstructed or obscured. (IFC 906.6)