{1} Chemical Storage/Safety

  • {1.1} Shelving is equipped with restraints to prevent items from falling off. Racks/shelves are secured. (IFC 5404.3.3.5.2)

  • {1.2} NFPA Placard is present and up-to-date on room doors.

  • {1.3} When the chemical fume hood is unattended, the sash shall be closed. (NFPA 45-8.8.3.2)

  • {1.4} Compressed gas cylinders are standing up, and secured with a chain with a minimum thickness of .25", or similar restraint. (IFC 5303.5.3, CGA)

  • {1.5} Compressed gas cylinders not "in use" shall not be stored in the laboratory. (NFPA 45-11.1.6.4)

  • {1.6} All chemicals are properly labeled. (NFPA 45-9.2.3.4)

  • {1.7} Chemicals are dated when first opened. (NFPA 45-9.2.3.4)

  • {1.8} Chemicals are stored appropriate. (NFPA 45-9.2.3.2 & 9.2.3.3)

  • {1.9} Chemicals shall not be stored in fume hoods. (NFPA 45-9.2.3.7)

  • {1.10} Chemical inventories shall be maintained within the maximum allowable quantities as specified in the Code. (IFC table 2703.1.1(1))

{2} Egress/Corridors/Exiting

  • {2.1} Exits and corridors are not obstructed. (IFC 1003.6)

  • {2.2} Exit signage functions and is located properly. (IFC 1011.1, 1101.3, 1101.6.3)

{3} Electrical/Lighting

  • {3.1} Electrical rooms are free of clutter and storage. (IFC 315.3.3)

  • {3.2} Electrical panels require 36" clearance in front. (IFC 605.3)

  • {3.3} Electrical cords are in good condition. (IFC 605.1 & 605.5)

  • {3.4} Multiplug adapters shall be directly connected to a permanently installed receptacle. (IFC 605.4.2)

  • {3.5} Electrical extension cords shall not be used as a substitute for permanent wiring and shall only be used for portable appliances. (IFC 605.5)

  • {3.6} Electrical receptacles located near a water source shall be protected by GFCI. (IFC 605.1)

  • {3.7}Emergency lighting functions properly. (IFC 604.5)

{4} Elevator Machine Room

  • {4.1} Machine room is free of storage. (ASME A17.1)

  • {4.2} Machine room has a fire extinguisher with a minimum rating of 2A:10B:C (ASME A17.1)

{5} Fire Alarms/Detectors (ITM)

  • {5.1} Fire alarm test shall be conducted semi-annually (NFPA 72.14.3)

  • {5.2} Smoke detectors shall be installed in each sleeping room and interconnected in R-2 Occupancies. (IFC 907.2.11.2 & 907.2.11.3)

{6} Fire Sprinklers (ITM)

  • {6.1} Automatic Fire Sprinkler Systems shall be inspected and tested semi-annually. (NFPA 25.5)

  • {6.2} Automatic Fire Sprinklers shall be installed in all R-2 Occupancies. (IFC 903.2.8)

{7} Fire Resistance Rated Construction

  • {7.1} All walls, ceiling and rated partitions shall be maintained. Includes door props. (IFC 703.1)

  • {7.2} Fire doors shall not be blocked or obstructed. (IFC 703.2)

{8} Housekeeping

  • {8.1} Storage shall be maintained 2' or more below the ceiling in non-sprinklered areas of buildings. (IFC 315.3.1)

  • {8.2} Storage shall be maintained a minimum of 18" below fire sprinkler head deflectors. (IFC 315.3.1)

  • {8.3} Combustible material creating a fire hazard shall not be allowed to accumulate in buildings. (IFC 304.1)

  • {8.4} Storage shall be orderly and not subjected to heating appliances. (IFC 315.3)

{9} Kitchens

  • {9.1} Class K portable fire extinguisher shall be provided for commercial cooking equipment involving vegetable or animal oils and fats. (IFC 904.11.5)

  • {9.2} Fire extinguishing systems in commercial kitchen hoods shall be serviced at least semi-annually. (IFC 904.11.6.2)

  • {9.3} Inspections of hoods, fans, ducts and devices shall be conducted at intervals not to exceed 6 months and cleaned if necessary. (IFC 609.3.3.1)

{10} Occupant Loading

  • {10.1} Occupant load is exceeded. (IFC Table 1015.1)

{11} Portable Fire Extinguishers

  • {11.1} Extinguishers are not present or travel distance is more than 75 feet. (IFC 906.1, 906.3)

  • {11.2} Inspections/service is more than 1 year. (IFC 906.2, NFPA 10-7.3.4)

  • {11.3} Extinguisher is not mounted. (IFC 906.7, 906.9)

  • {11.4} Extinguisher is obstructed or obscured. (IFC 906.6)

{12} Other Violations Noted

  • {12.1} Other violation

  • {12.2} Other Violation

  • {12.3} Other Violation

  • {12.4} Other Violation

  • {12.5} Other Violation

  • {12.6} Other Violation

  • {12.7} Other Violation

  • {12.8} Other Violation

  • {12.9} Other Violation

  • {12.10} Other Violation

No Violations Noted

  • No fire code violations were at the time of this inspection.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.