  • Document number

  • Site conducted

  • Conducted on

  • Prepared by

  • Lot Number

  • GIS location data from device (Phone/Tablet etc)
  • PCU or Combiner Box number

  • PCU Trench Entry drawings

  • Inverter Foundation Entry drawings

  • DC Combiner Box drawings

  • Review the SOW, RFI register, drawing and drawing notes to ensuring the correct details have been read and understood

  • Check RFI004 [Rigid-PVC] and confirm correct conduit type is being used on the installation

  • RFI004 [Rigid-PVC] Result.png
  • Trench profile installed as per the drawing

  • Cable installed as per the applicable bend radius required

  • Earth cables, crimp connections installed as per specifications

  • Hardcover laid ensuring a minimum of 40mm overlap of each cable edge

  • Conduit bends installed as per requirement and hardcover overlaps the start of the conduit

  • Marker tape extended until the bend from the existing trench profile

  • UV stabilised paint installed on the flexible conduit or bend if its not already UV stabilised or exposed to direct sunlight*not required if conduits are behind covers etc

  • Conduit underground depth and surface exposure installed as per the specification

  • Conduits 200mm (Minimum) above the Finish Surface Levels as shown in Specification

  • 100mm Conduit centered between Combiner Box Piles, 50mm Conduit centered between 100mm Conduit and Combiner Box pile (as per drawing specification)

  • Are conduits fixed to the front side of the pile / conduit support

  • Conduit void filled, compacted and levelled off

  • Have all pile strikes been rectified (Straightened / replaced)

  • Suitable cable length left for the termination crew to perform termination after (1200mm minimum)

  • All cable ends are sealed with heatshrink end caps

  • Cable marking applied as required

  • Pictures of all cables and conduits installed and completed

Sign-off

  • PCU entry is installed as per SOW, IFC and UPrev drawing and RFIs specifications

  • Supervisor or QA technician sign off

  • Complete report, email to project email address (JLE_Stubbo@jlegroup.net.au), notify JLE Project QA team to log the report number in the application document register and file under each Lot, all NCR or defects added to the Defects Register as required

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.