Title Page
-
Document No.
-
Audit Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
Process - Disconnecting service mains at Distribution
-
Test all equipment and PPE.
-
WHRA completed and signed.
-
Safety Observer in Place.
-
Independent earth installed.
-
Insulating matts installed as required and correct.
-
Test from independent earth to all distribution conductors, identify suspect neutral and active conductors.
-
Disconnect and remove independent earth.
-
Test from suspect neutral and other conductors to confirm neutral.
-
Confirm isolation at switchboard.
-
Check for load on service mains prior to disconnection.
-
Disconnect actives first and neutral conductor last.
-
Lower each conductor to the ground safely.
Process - Connecting service mains at Distribution
-
Test all equipment and PPE.
-
Safety Observer in Place.
-
Independent earth installed.
-
Insulating matts installed as required and correct.
-
Install approved fixing for Service mains on pole.
-
Raise Service mains with approved lifting device.
-
Install Service mains and tension.
-
Use approved tool to clean Distribution mains prior to connection.
-
Test from independent earth to all distribution conductors, identify suspect neutral and active conductors.
-
Disconnect and remove independent earth.
-
Install neutral service main to distribution main.
-
Install service actives to distribution mains.
-
Remove any insulating matts from distribution mains.
Completion.
-
Is AUP competent?
-
Notes.
Sign off.
-
AUP Assessed
-
Assessor