Title Page

  • Site conducted

  • Date and Time

  • Task

  • Work Location

  • Conducted on

  • Prepared by

Exposure to Hazardous Substances

Access Control

  • 1. Is access to hazardous substance storage areas controlled?

  • 2. Are hazardous substances only stored in designated areas?

  • 3. Is the training of each person in the hazardous storage area up-to-date?<br>Note: Check the Competency Card is being carried by the individual and it is<br>valid.

Alarms Systems

  • 4. Do sensors display the date they were last calibrated?

  • 5. Is the testing and calibration date within the last year?

  • 6. Are sensors and alarms in good physical condition?

  • 7. Did the team perform a visual check of the sensors and alarms before<br>commencing work?

  • 8. Does the team know response procedures for possible alarms in their<br>work area?

Chemical PPE

  • 9. Have all hazardous substances involved with the task been clearly<br>identified and written on the Permit to Work?

  • 10. Do the team know the potential health effects of the chemicals they are<br>working with?

  • 11. Is the team using the correct hazardous substances PPE for this task?

  • 12. Was the Hazardous Substances PPE inspected prior to use and in good<br>condition?

  • 13. Is the Hazardous Substances PPE being worn correctly?

Handling Requirements

  • 14. Is the SDS for the hazardous substance(s) readily available and are the<br>requirements being followed?

  • 15. Are the handling tasks completed as per the written procedure?

  • 16. Does the team know what to do in an emergency when handling<br>hazardous substances?<br>

  • 17. Is piping and other process equipment labeled indicating the hazardous<br>contents?

Loading and Unloading Protection

  • 18. Are hazardous substance bulk loading and unloading facilities secured?

  • 19. Is the team following the procedure for safe loading and unloading of<br>bulk hazardous substances?

  • 20. Is the delivery driver familiar with the delivery and safe loading /<br>unloading procedure?

  • 21. Have the contents of the delivery truck been verified?

Mechanical Integrity of Storage and Distribution

  • 22. Are hazardous substances stored and segregated as per MSDS?

  • 23. Are there written procedures for the use, storage and disposal of<br>identified hazardous substances?

  • 24. Are hazardous substance containers correctly and clearly labelled?

  • 25. Are pipes or other distribution systems used for hazardous substances<br>clearly identified?

  • 26. Are structural beams, supports, pipes and vessels free from structural<br>damage and excessive corrosion/rust?

  • 27. Are all vessels, pipes, flanges and fittings free from visible leaks?

  • 28. Is the Hazardous Storage Area free from unnecessary combustibles and<br>incompatible substances?

PHA - Protection against exposure to Chlorine Gas © Rio Tinto

  • 29. Has a weekly inspection of containers been completed?

  • 30. Is the cylinder/ drum within inspection date? (within 5 yrs of date stamp)

  • 31. Have the drums/ cylinders been inspected and verified safe for use?<br>i.e there should be no visual physical damage or degradation of drum /<br>cylinder shell, valve cap, container<br>valve etc

  • 32. Is the gland packing on the valve spindle intact and at least hand tight?

  • 33. Have all piping, fittings, flexible hose, small chlorinator and injector<br>been inspected and verified safe for<br>use? i.e. There should be no visual physical damage, no blistering, kinks or<br>blockages and no chlorine leaks<br>suspected through visual or audio cues etc<br>

  • 34. Has a 52 week service been completed?

  • 35. Has a weekly inspection of the Vacuum Regulator Device (VRD),<br>including the drip leg heater and carbon canister, been completed?

  • 36. Has a visual check been conducted on the Vacuum Regulator Device?<br>i.e. inspected for signs of corrosion and dirt?

  • 37. Has the drip leg heater been checked that they are operational by<br>feeling for warmth?

  • 38. Has a 26 weeks service on the Vacuum Regulator Device and drip leg<br>heater been completed?

  • 39. Has a weekly inspection of the Chlorine Gas Detection, Alarm and<br>Shutdown System been completed?

  • 40. Has a function test been performed on the whole of the system?<br>This is to confirm the following:<br>- Alarm light up on Hydra Sentinel Panel,<br>- Display on on-line chlorine gas leak monitoring system,<br>- Activation of the audio alarm, and<br>- Operation of the ratchets<br>- Chlorine gas detection results alarmed to operations centre

  • 41. Have the gas detectors been inspected to ensure they are<br>unobstructed, clean and in safe working condition?

  • 42. Does the display panel show chlorine gas level at zero?

  • 43. Has the Shutdown device / ratchet arm been inspected to ensure that<br>there is no damage?<br>This includes no corrosion, or loose fittings, or an other abnormalities.

  • 44. Has the pneumatic lines been inspected to ensure that they are free<br>from damage or degradation?

  • 45. Is the 24 hour auto gas leak detector panel clear of any alarms?<br>Note: If the auto test has failed, there should be a trouble/ warning lamp<br>and an audible alarm

  • 46. Has a 4 weekly inspection of the Chlorine Gas Detection, Alarm and<br>Shutdown System been completed?<br>This should include:<br>- A check that the Pneumatic Panel air pressure greater than 600 kPa<br>- There is no low pressure or low battery alarm is present on the Check<br>Hydra Sentinel Panel<br>

  • 47. Is the Pneumatic Panel air pressure greater than 600 kPa?

  • 48. Is the Hydra Sentinel Panel clear of any low pressure or low battery<br>alarm? i.e. if no alarm is activated, tick yes

  • 49. Has a 24 weekly inspection of the Chlorine Gas Detection, Alarm and<br>Shutdown System been completed?

  • 50. Is the relevant SWP(s) available at the facility?<br>- RTIO-HSE-0164531 SWP 70kg Chlorine Cylinder Changeout<br>- RTIO-HSE-0165384 SWP 920kg Chlorine Drum Changeout

  • 51. Is the relevant SWP(s) current?<br>- RTIO-HSE-0164531 SWP 70kg Chlorine Cylinder Changeout<br>- RTIO-HSE-0165384 SWP 920kg Chlorine Drum Changeout

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.