Information
-
Document No.
-
Audit Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
Site Contact info
Site Contact info
-
Add additional contacts
-
Name
-
Title
-
Address
-
Work phone
-
Cell Phone
-
Email Address
-
Other details
Staffing Assessment
Staffing assessment
-
Is there currently in-house maintenance
-
Define staffing levels and skill sets
-
Is there Janitorial Staff
-
Define staffing levels and skill sets
-
Is there food service staff at this location
-
Define staffing levels and skill sets
-
Other Staff info
-
Define staffing levels and skill sets
Facilities Structure Info
Facilities Structural informantion
-
Structure Type
-
Number of Stories
-
Total Square Footage
-
Square Fottage of Office
-
Square Footage of Warehouse
-
Square Footage of Prodiction
-
Square footage of Other
-
Define the Square Footage
-
Total Arcers
-
Parking type
-
Total Number of Stalls
-
Storefront Type
-
Storefront Color (include color code and manufacture if possible)
-
Glazing Color (include color code and manufacture if possible)
-
Structural Color (include color code and manufacturer if possible)
-
Number of Exits
-
Number of Dock Door if applicable
Facilities Utilities Assessment
Facilities Utilities Assessment
-
Electrical Service
-
Provider info/ Contact
-
Main Utility Input to Facilities
-
MD Voltage/ Amperage/ Phase
-
Ground fault protection
-
Provide details about the system
-
Lighting protection
-
Provide details about the system
-
General Comments
-
Gas Utility
-
Service Provider / Contact
-
Main Pressure high or low
-
Main and meter protected from damage
-
Provide Reason for partial compliance
-
General Comments
-
Water Service
-
Service Provider / Contact
-
Main Size / Pressure
-
Cross connect Service Provider / Contact
-
Inspection up to date
-
Provide Reason for partial compliance
-
Are valves secured
-
Provide Reason for partial compliance
-
General Comments
-
Waste Removal
-
Provider / Contact
-
Type of removal (dumpster or compactor)
-
Estimated pulls or tons per month
-
Define Schedule of pick up's
-
General Comments
Standard Operating Procedures Manual Assessment
Standard Operating Procedures Manual
-
Approval page is signed/dated by Department Manager and Administration.
-
Provide Reason for partial compliance
-
There is a current department organization chart
-
Provide Reason for partial compliance
-
Copies of all policies and procedures are included in appropriate sections
-
Provide Reason for partial compliance
-
Maintenance Request System procedure is approved by Administration
-
Provide Reason for partial compliance
-
Job descriptions are included for all current positions
-
Provide Reason for partial compliance
-
All documentation, logs and maintenance records are retained for a minimum of 3 years
-
Provide Reason for partial compliance
-
General Comments
Emergency Contingency Plans Assessment
Emergency Contingency Plans include:
-
Up to date call roster for department personnel
-
Provide Reason for partial compliance
-
Vendor call list
-
Provide Reason for partial compliance
-
Procedure for air conditioning failure
-
Provide Reason for partial compliance
-
Procedure for boiler failure
-
Provide Reason for partial compliance
-
Procedure for plumbing failure
-
Provide Reason for partial compliance
-
Procedure for elevator failure
-
Provide Reason for partial compliance
-
Procedure for communications failure
-
Provide Reason for partial compliance
-
Procedure for natural gas failure
-
Provide Reason for partial compliance
-
Procedure for water system failure
-
Provide Reason for partial compliance
-
Procedure for commercial electrical failure
-
Provide Reason for partial compliance
-
Procedure for emergency generator failure
-
Provide Reason for partial compliance
-
Procedure for fire alarm system failure
-
Provide Reason for partial compliance
-
Procedure for fire sprinkler system failure
-
Provide Reason for partial compliance
-
Procedure for piped medical gases failure (hospital only)
-
Provide Reason for partial compliance
-
Procedure for piped vacuum system/compressed air failure
-
Provide Reason for partial compliance
-
Procedure for oxygen system failure (hospital only)
-
Provide Reason for partial compliance
-
Single line diagrams of all systems are available
-
Provide Reason for partial compliance
-
Site plan showing all major utility shutoffs is available
-
Provide Reason for partial compliance
-
General Comments
Life Safety Testing and Inspection Assessment
Fire drills
-
Fire drills are documented in the Life Safety Manual
-
Provide Reason for partial compliance
-
Fire drills cover all personnel, one per shift, per quarter (once per year for stand-alone business occupancies)
-
Provide Reason for partial compliance
-
Fire drills are up to date for the last 12 months
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Fire extinguishers
-
There is an inventory of all fire extinguishers and are they scheduled for monthly inspections
-
Provide Reason for partial compliance
-
Fire extinguisher inspections are up to date for the last 12 months
-
Provide Reason for partial compliance
-
Inspections are recorded with dates and initials on tags and log
-
Provide Reason for partial compliance
-
Extinguishers and cabinets are numbered and clearly visible
-
Provide Reason for partial compliance
-
Extinguishers are maintained annually
-
Provide Reason for partial compliance
-
General Comments
Fire / Weather Alarm System Panel Assessment
Pull stations
-
There is an inventory of all pull stations
-
Provide Reason for partial compliance
-
All pull stations are numbered
-
Provide Reason for partial compliance
-
All pull stations are tested annually
-
Provide Reason for partial compliance
-
Pull station tests are up to date for the last 12 months
-
Provide Reason for partial compliance
-
General Comments
Horns, speakers and strobes
-
There is an inventory of all fire alarm horns, speakers and strobes
-
Provide Reason for partial compliance
-
All horns, speakers and strobes are tested annually
-
Provide Reason for partial compliance
-
Tests are up to date for the last 12 months
-
Provide Reason for partial compliance
-
All horns, speakers and strobes are numbered
-
Provide Reason for partial compliance
-
General Comments
Fire Alarm and Supervisory Signal Devices
-
Transmission of fire alarm signals to off-premises monitoring site is tested quarterly
-
Provide Reason for partial compliance or non-compliance
-
There is an inventory of all supervisory signal devices
-
Provide Reason for partial compliance
-
Devices are tested quarterly
-
Provide Reason for partial compliance
-
Tests are up to date for the last 12 months
-
Provide Reason for partial compliance
-
Monitoring Company / Contact
-
General Comments
Smoke, duct and heat detectors
-
There is an inventory of all Smoke, Heat and Duct Detectors
-
Provide Reason for partial compliance or non-compliance
-
All Smoke, Duct and Restoreable Heat Detectors are Tested Annually
-
Provide Reason for partial compliance
-
All non-restoreable heat detectors are tested mechanically and electrically annually<br>(2 per 100) every 15 years
-
Provide Reason for partial compliance
-
All detectors are numbered
-
Provide Reason for partial compliance
-
Detectors are tested annually and documented for the past 12 months
-
Provide Reason for partial compliance or non-compliance
-
Smoke Detector Information
Add Additional Smoke Detector Details
-
Manufacture
-
Current Service vendor / Contact
-
General Comments
-
Heat Detector Information
Add Additional Heat Detector Information
-
Manufacture
-
Current Service vendor / Contact
-
General Comments
-
Duct Detector Information
Add Additional Duct Detector Information
-
Manufacture
-
Current Service vendor / Contact
-
General Comments
Fire and smoke dampers
-
There is an inventory of all fire and smoke dampers
-
Provide Reason for partial compliance
-
All fire and smoke dampers are tested (with fusible links removed where applicable) every four years to verify they fully close
-
Provide Reason for partial compliance
-
General Comments
Smoke detection shutdown devices`
-
There is an inventory of all automatic smoke detection shutdown devices for air handling equipment
-
Provide Reason for partial compliance
-
Devices are tested annually
-
Provide Reason for partial compliance
-
Tests are up to date for the last 12 months
-
Provide Reason for partial compliance
-
General Comments
Sprinkler flow alarms
-
There is an inventory of all sprinkler flow alarm locations
-
Provide Reason for partial compliance
-
Alarms are scheduled for semiannual testing.
-
Provide Reason for partial compliance
-
Tests are up to date for the last 12 months
-
Provide Reason for partial compliance
-
General Comments
Sprinkler Systems Assessment
-
There is an inventory of all system risers
-
Provide Reason for partial compliance
-
Sprinklers, pipe and fittings, hangers and seismic braces, and spare sprinklers are inspection annually from floor level. Concealed spaces are exempted
-
Provide Reason for partial compliance
-
Antifreeze is tested annually if applicable
-
Provide Reason for partial compliance
-
Sprinklers and spray nozzles protecting cooking equipment and ventilating systems are replaced annually (except bulb-type with no buildup of grease or other
-
Provide Reason for partial compliance
-
Inspections are recorded with dates and initials on tags and log
-
Provide Reason for partial compliance
-
General Comments
Sprinkler control valves
-
There is an inventory of all sprinkler control valve locations
-
Provide Reason for partial compliance
-
Valves are scheduled for monthly inspection (weekly if not locked or supervised)
-
Provide Reason for partial compliance
-
Supervisory or tamper switches are tested semiannually
-
Provide Reason for partial compliance
-
Valves are operated annually
-
Provide Reason for partial compliance
-
Valves are maintained annually
-
Provide Reason for partial compliance
-
Tests are up to date for the last 12 months
-
Provide Reason for partial compliance
-
General Comments
Main drains
-
There is an inventory of all system risers with locations
-
Provide Reason for partial compliance
-
Main drain tests are conducted at least annually on all system risers
-
Provide Reason for partial compliance
-
General Comments
Dry pipe sprinkler systems
-
There is an inventory of all dry pipe sprinkler systems
-
Provide Reason for partial compliance
-
Gauges are inspected weekly (monthly with low-pressure alarm)
-
Provide Reason for partial compliance
-
Valves are inspected monthly
-
Provide Reason for partial compliance
-
Priming water level and low pressure alarms are checked quarterly
-
Provide Reason for partial compliance
-
Quick-opening devices are tested quarterly
-
Provide Reason for partial compliance
-
Valves are trip tested annually with partial flow
-
Provide Reason for partial compliance
-
Valves are trip tested every three years with full flow
-
Provide Reason for partial compliance
-
General Comments
Preaction or deluge systems
-
There is an Inventory of all Preaction Sprinkler Systems
-
Provide Reason for partial compliance
-
Systems are scheduled for test & inspection per NFPA requirements.
-
Provide Reason for partial compliance
-
Inspections are recorded for past 12 months
-
Provide Reason for partial compliance
-
General Comments
Stand pipe systems
-
There is an inventory of all stand pipe systems
-
Provide Reason for partial compliance
-
All stand pipe systems are scheduled for water flow and hydrostatic tests at least every five years
-
Provide Reason for partial compliance
-
Hose connections and valves are maintained annually
-
Provide Reason for partial compliance
-
General Comments
Fire hoses
-
There is an inventory of all occupant fire hoses
-
Provide Reason for partial compliance
-
Fire hoses are hydrostatically tested five years after installation and every three years thereafter
-
Provide Reason for partial compliance
-
Fire hose connections are inspected Quarterly
-
Provide Reason for partial compliance
-
Hoses are inspected Annually
-
Provide Reason for partial compliance
-
General Comments
Fire pumps
-
Fire pumps are tested weekly under no-flow condition
-
Provide Reason for partial compliance
-
Fire pumps are tested annually under flow condition.
-
Provide Reason for partial compliance
-
Inspections are recorded for past 12 months
-
Provide Reason for partial compliance
-
General Comments
Water storage tanks
-
Water level alarms are tested at least semiannually
-
Provide Reason for partial compliance
-
Low temperature alarms are tested monthly (cold weather only)
-
Provide Reason for partial compliance
-
Inspections are recorded for past 12 months
-
Provide Reason for partial compliance
-
General Comments
Fire department connections
-
There is an inventory of all fire department connections
-
Provide Reason for partial compliance
-
Fire department connections are inspected quarterly.
-
Provide Reason for partial compliance
-
Inspections are recorded for past 12 months
-
Provide Reason for partial compliance
-
General Comments
Kitchen Automatic Fire Extinguishing Systems
-
Kitchen hood systems are maintained at least semiannually
-
Provide Reason for partial compliance
-
Inspections are recorded for past 12 months
-
Provide Reason for partial compliance
-
General Comments
Kitchen Hood Cleaning
-
Kitchen hood systems are maintained at least semiannually with high volumes of frying, char broiling or Oriental cooking require more frequent cleaning
-
Provide Reason for partial compliance
-
Hood cleaning is up to date
-
Provide Reason for partial compliance
CO2/Halon/FM200 Systems
-
There is an inventory of all CO2, Halon, FM200 and other gaseous automatic fire extinguishing systems
-
Provide Reason for partial compliance
-
CO2 systems are tested at least annually (actual discharge is not required)
-
Provide Reason for partial compliance
-
Halon systems are tested at least semiannually (actual discharge is not required). (JCAHO annual)
-
Provide Reason for partial compliance
-
FM200 systems are tested at least semiannually (actual discharge is not required)
-
Provide Reason for partial compliance
-
Inspections are recorded with dates and initials on tags and log
-
Provide Reason for partial compliance
-
General Comments
Life Safety Policies Assessment
Combustible Decorations
-
There is a policy prohibiting combustible decorations, unless flame retardant
-
Provide Reason for partial compliance
-
The policy is implemented
-
Provide Reason for partial compliance
-
General Comments
Portable Space Heaters
-
There is a policy prohibiting portable space heaters in patient care areas
-
Provide Reason for partial compliance
-
The policy is implemented
-
Provide Reason for partial compliance
-
General Comments
Building Maintenance Program Assessment
Building Maintenance Program
1-hr and 1½-hr fire doors
-
There is an inventory of all 1-hr and 1½-hr fire doors
-
Provide Reason for partial compliance or non-compliance
-
Doors are tested quarterly for:
-
Properly functioning positive latching devices<br>
-
Provide Reason for partial compliance or non-compliance
-
Properly functioning self- or automatic-closing devices </=1/8 in gaps between meeting edges of door pairs<br></=3/4 in. undercuts
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Linen/trash chute inlet and outlet doors
-
There is an inventory of all linen/trash chute inlet and outlet doors
-
Provide Reason for partial compliance or non-compliance
-
Doors are tested quarterly for:<br>Positive latching devices<br>Self- or automatic-closing devices
-
Provide Reason for partial compliance or non-compliance
-
Inspections are recorded with dates and initials on tags and log
-
Provide Reason for partial compliance or non-compliance
Doors in smoke barriers
-
There is an inventory of all smoke barrier doors
-
Provide Reason for partial compliance or non-compliance
-
Doors are tested quarterly for:
-
Properly functioning self- or automatic-closing devices
-
Provide Reason for partial compliance or non-compliance
-
Maintained to resist the passage of smoke
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Corridor doors
-
Doors are inspected semiannually for:
-
Properly functioning latching devices<br>
-
Provide Reason for partial compliance or non-compliance
-
Maintained to resist the passage of smoke <1 in. undercuts (average)
-
Provide Reason for partial compliance or non-compliance
-
Inspections are recorded with dates and initials on tags and log
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Smoke barrier wall penetrations
-
Walls are inspected annually for penetrations
-
Provide Reason for partial compliance or non-compliance
-
Penetrations are sealed
-
Provide Reason for partial compliance or non-compliance
-
Inspections are recorded with dates and initials on tags and log
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Corridor wall penetrations (N/A above suspended ceiling if fully sprinklered)
-
Walls are inspected annually for penetrations
-
Provide Reason for partial compliance or non-compliance
-
Penetrations are sealed
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Means of egress illumination devices and exit signs
-
Devices are inspected quarterly
-
Provide Reason for partial compliance or non-compliance
-
Inspections are recorded with dates and initials on tags and log
-
Provide Reason for partial compliance or non-compliance
-
All detectors are numbered
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Filter Log
Filter Log
-
There is an inventory of all filters, including location, size, quantity, efficiency, and criteria for changing
-
Provide Reason for partial compliance or non-compliance
-
Filters are inspected for torn media or bypass in filter frames following each filter replacement
-
Provide Reason for partial compliance or non-compliance
-
Filter changes are up to date for the past 12 months
-
Provide Reason for partial compliance or non-compliance
-
Manufacturer's literature/specifications for all filters is included in the Filter Log Manual
-
Provide Reason for partial compliance or non-compliance
-
General Comment
Vendor Control Log
Vendor Control Log
-
A Vendor Control Log is being utilized
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Daily Journal/Pass Down Log
Daily Journal/Pass Down Log
-
The journal is used daily for all shifts
-
Provide Reason for partial compliance or non-compliance
-
The journal is bound with numbered pages
-
Provide Reason for partial compliance or non-compliance
-
All entries are made in ink
-
Provide Reason for partial compliance or non-compliance
-
All entries include the time of occurrence
-
Provide Reason for partial compliance or non-compliance
-
All watchstanders read and initial log before start of watch
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Maintenance Logs
Maintenance Log
-
Log is used for rounds daily, all shifts, and includes DHW temperature
-
Provide Reason for partial compliance or non-compliance
-
All mechanical equipment spaces are included in the log
-
Provide Reason for partial compliance or non-compliance
-
Logs are maintained and available for previous three years
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Blueprint Index
Blueprint Index
-
Blueprint Index for all buildings is in place and readily available
-
Provide Reason for partial compliance or non-compliance
-
Blueprints are neatly filed in a central location
-
Provide Reason for partial compliance or non-compliance
-
Blueprints are filed electronically
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Schematic diagrams are available for the following equipment:
-
Electrical Distribution
-
Provide Reason for partial compliance or non-compliance
-
Heating Hot Water
-
Provide Reason for partial compliance or non-compliance
-
Chilled Water
-
Provide Reason for partial compliance or non-compliance
-
Domestic Hot/Cold Water
-
Provide Reason for partial compliance or non-compliance
-
Medical Gases (hospital only)
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Manufacturers' Index
Manufacturers' Index
-
Manufacturers' Index is in place and readily available
-
Provide Reason for partial compliance or non-compliance
-
Manufacturers' literature is neatly filed in a central location
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Contracts Manual
Contracts Manual
-
Contracts pertaining to maintenance area of responsibility are included in the manual, and contracts are current
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Regulatory Agencies Manual
Regulatory Agencies Manual Assessment
-
Elevator permits are included
-
Provide Reason for partial compliance or non-compliance
-
Backflow preventer tests are included
-
Provide Reason for partial compliance or non-compliance
-
Fire marshal reports are included
-
Provide Reason for partial compliance or non-compliance
-
Fire retardant certificates are included
-
Provide Reason for partial compliance or non-compliance
-
Boiler inspections are included
-
Provide Reason for partial compliance or non-compliance
-
Health Department inspections are included
-
Provide Reason for partial compliance or non-compliance
-
Prior JCAHO Accreditation Decision is included (hospital only)
-
Provide Reason for partial compliance or non-compliance
-
Current Statement of Conditions is included
-
Provide Reason for partial compliance or non-compliance
-
Current Plan for Improvement (PFI) is included
-
Provide Reason for partial compliance or non-compliance
-
Pressure vessel inspections/permits are included
-
Provide Reason for partial compliance or non-compliance
-
Personnel licenses are included
-
Provide Reason for partial compliance or non-compliance
-
Generator & boiler emissions permits are included
-
Provide Reason for partial compliance or non-compliance
-
Sewer discharge permits are included
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Emergency Generator Manual
Emergency Generator Manual
-
Generator tests are conducted under load for 30 minutes at least monthly<br>(Local jurisdictions may require more stringent testing; e.g., California requires testing every 7 days)
-
Provide Reason for partial compliance or non-compliance
-
A written record of inspection, performance, exercising and repairs shall be maintained and available
-
Provide Reason for partial compliance or non-compliance
-
All automatic transfer switches are tested monthly
-
Provide Reason for partial compliance or non-compliance
-
Power failures are recorded in the manual
-
Provide Reason for partial compliance or non-compliance
-
30% load, EGT or annual load bank in place
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Electric Bed Manual (hospital)
Electric Bed Manual (hospital only)
-
There is an inventory of all electric beds
-
Provide Reason for partial compliance or non-compliance
-
They are scheduled for at least annual testing in critical care areas They are tested before being put into service for the first time and after repair or modifications (all other areas)
-
Provide Reason for partial compliance or non-compliance
-
Inspections are up to date for the last 12 months
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Receptacle Manual (hospital)
Receptacle Manual (hospital)
-
There is an inventory of patient care areas for receptacle tests
-
Provide Reason for partial compliance or non-compliance
-
Receptacles in critical care/electrically sensitive areas are scheduled for at least annual testing (California requirement)
-
Provide Reason for partial compliance or non-compliance
-
Receptacles in other patient care areas are scheduled for at least annual testing, except hospital grade receptacle testing frequencies can be based on experience (Local jurisdictions may have more stringent requirements.)
-
Provide Reason for partial compliance or non-compliance
-
Inspections are up to date for the last 12 months
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Medical gases
Medical gases
-
There is an inventory of all medical gas alarms, and they are scheduled for monthly testing
-
Provide Reason for partial compliance or non-compliance
-
Inspections of medical gas alarms are up to date for the last 12 months
-
Provide Reason for partial compliance or non-compliance
-
Annual test of medical gas system components is performed
-
Provide Reason for partial compliance or non-compliance
-
There is an inventory of all line isolation monitors, and they are scheduled for monthly testing unless self-testing and self-calibrating
-
Provide Reason for partial compliance or non-compliance
-
Inspections of line isolation monitors are up to date for the last 12 months
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Roof Inspection
Roof Inspection
-
A complete roof inventory exists
-
Provide Reason for partial compliance or non-compliance
-
Inspections are scheduled quarterly and are up to date for the last 12 months
-
Provide Reason for partial compliance or non-compliance
-
Type(s) of roofs
-
Install date if known
-
Is there any warranty
-
Expiration Date
-
Manufacture
-
Holder of warranty
-
Contact infomation
-
General Comments
Underground Storage Tanks
Underground Storage Tanks Assessment
-
Automatic Tank Gauging system is operated in test mode monthly
-
Provide Reason for partial compliance or non-compliance
-
Weekly manual gauging is used for tanks <1,000 GAL
-
Provide Reason for partial compliance or non-compliance
-
The following records are available:
-
Monitoring results for the previous 12 months
-
Provide Reason for partial compliance or non-compliance
-
Performance claims by leak detection system manufacturer
-
Provide Reason for partial compliance or non-compliance
-
Records of corrosion protection system tests and inspections
-
Provide Reason for partial compliance or non-compliance
-
Records of repair or upgrade to tank
-
Provide Reason for partial compliance or non-compliance
-
Records of maintenance, repair and calibration of leak detection equipment
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Water Treatment
Water Treatment
-
Water treatment samples of boiler water and appropriate other samples (feed water, condensate), are taken in accordance with water treatment company recommendations
-
Provide Reason for partial compliance or non-compliance
-
Blowdown of boilers is performed on a regularly scheduled basis in accordance with water treatment company recommendations
-
Provide Reason for partial compliance or non-compliance
-
Boiler blowdowns are recorded, including time and duration, on test result sheet or journal
-
Provide Reason for partial compliance or non-compliance
-
Test samples of cooling tower water are taken and test results recorded in accordance with water treatment company recommendations
-
Provide Reason for partial compliance or non-compliance
-
Domestic potable water supply from an independent source is treated and subjected to quarterly bacteriological analysis
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Grounds
Grounds
-
Parking lots are free of debris and provide adequate lighting
-
Handicapped parking spaces are provided and properly marked
-
Paved areas are in good repair
-
Grounds are kept free of litter/debris
-
All landscaping is properly maintained
-
All trees are trimmed appropriately to avoid power lines and other hazards
-
There is a policy/procedure for snow removal
-
Access to Emergency Room is clearly marked (hospital only)
-
Recreational areas (tennis courts, swimming pools, etc.) are in good repair
-
General Comments
Mechanical Equipment / Physical Plant Inventory
Mechanical Equipment Equipment Spaces / Physical Plant
-
Doors to mechanical equipment rooms are locked
-
Doors to mechanical equipment rooms are labeled
-
Penetrations in equipment room floors and walls are sealed
-
Equipment room floors and walls are clean
-
Equipment is clean and free of leaks and rust
-
Equipment room floors are sealed or painted
-
Piping insulation is in good condition
-
Piping is labeled as to contents or color coded, and directional arrows are affixed
-
Valve charts are posted
-
Valves are numbered and tagged in accordance with valve charts
-
Permits and inspections listed in 12, Regulatory Agencies Manual, are posted if required by authority having jurisdiction
-
Operating instructions are posted for the following equipment:
-
Boilers
-
Deaerators
-
Chillers
-
Water Softeners
-
Fire pumps
-
Vacuum Pumps
-
Emergency Generators
-
Signs indicating "Warning - This equipment starts automatically" are posted where applicable
-
Equipment is tagged in accordance with CMMS tag numbering system
-
Air handling units, exhaust fans, supply fans, and emergency generator(s) are labeled for areas served
-
Electrical breakers and controls are marked for equipment served
-
Temperature and pressure gauges are in operable condition range, and equipment is operating within the range
-
Mechanical equipment rooms are equipped with fire extinguishers
-
Storage in mechanical equipment rooms limited to engineering related items
-
Operators' licenses (stationary engineer, etc.) are posted if required
-
Safety guards are on equipment, as needed
-
Eyewash stations are available within 10 seconds travel time from areas in which caustic or toxic materials are used within the facility
-
Electrical rooms have 3 feet clearance in front of equipment
-
There is no storage on top of electrical gear or in transformer vaults
-
General Comments
Equipment at site
-
Add Additional Unitary Equipment Details
-
Unitary Equipment including but not limited to Heat Pumps, Roof Top Units, Make up Air units, Condensers, Furnaces and split systems
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Additional Chiller Details
-
Chillers
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Additional Cooling Tower Details
-
Cooling towers
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Hot Water Equipment Details
-
Hot Water Heaters
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Additional Boiler Details
-
Boilers
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Additional Refrigeration Equipment Details -
Refrigeration equipment
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Additional Kitchen Equipment Details
-
Kitchen Equipment
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add additional Generator / UPS Details
-
Back Up Generator / UPS and other back up systems
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Additional Fuel Storage Tank Details
-
Fuel Storage tanks
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Additional Pressure Vessels Details
-
Pressure Vessels<br>
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Additional Air Compressor Details
-
Air Compressors
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
Add Additional Building Controls Details
-
Building Controls
-
ID
-
Manufacture
-
Model #
-
Serial #
-
Size
-
Voltage
-
General Comments
General Safety Compliance Assessment
General Safety
-
Evacuations routes are posted throughout facility, and they include pull station and fire extinguisher locations
-
Provide Reason for partial compliance or non-compliance
-
Exit signs are in place and lighted
-
Provide Reason for partial compliance or non-compliance
-
Egresses are not blocked or narrowed
-
Provide Reason for partial compliance or non-compliance
-
A copy of the smoking policy is posted in the facility
-
Provide Reason for partial compliance or non-compliance
-
An inventory of all chemicals used in the department is available
-
Provide Reason for partial compliance or non-compliance
-
MSDS sheets are on file for all materials used within the department
-
Provide Reason for partial compliance or non-compliance
-
Lock out / Tag Out Program in Place
-
Provide Reason for partial compliance or non-compliance
-
All electrical panels latch and hospital locking policy is followed if appicable
-
Provide Reason for partial compliance or non-compliance
-
Potable water supply systems are protected by vacuum breakers or other protective devices approved by the authority having jurisdiction
-
Provide Reason for partial compliance or non-compliance
-
Domestic hot water temperature is maintained between 105°F and 120°F (or other range if required by AHJ)
-
Provide Reason for partial compliance or non-compliance
-
There is an inventory of all confined spaces
-
Provide Reason for partial compliance or non-compliance
-
There is a policy covering permit-required confined spaces
-
Provide Reason for partial compliance or non-compliance
-
The policy is in use
-
Provide Reason for partial compliance or non-compliance
-
Free-standing gas cylinders are securely chained/supported, and there is a clear distinction between empty and full cylinders
-
Provide Reason for partial compliance or non-compliance
-
Piped medical gas shut-off valves are labeled for type of service and area served
-
Provide Reason for partial compliance or non-compliance
-
Appropriate Personal Protective Equipment is available for use by Engineering personnel
-
Provide Reason for partial compliance or non-compliance
-
Electric tools are properly fitted with grounds or double insulated
-
Provide Reason for partial compliance or non-compliance
-
Meters used for testing equipment are calibrated biennially and calibration is documented
-
Provide Reason for partial compliance or non-compliance
-
Engineering Office is neat and organized
-
Provide Reason for partial compliance or non-compliance
-
Engineering Shop is clean and organized
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Hazardous Materials Assessment
Hazardous Materials
-
Secondary containment is in place for all hazardous material storage tanks
-
Provide Reason for partial compliance or non-compliance
-
Training of maintenance workers in safe handling and disposal of hazardous waste and spills is documented
-
Provide Reason for partial compliance or non-compliance
-
There is a closed-loop system for tracking hazardous/infectious waste manifests
-
Provide Reason for partial compliance or non-compliance
-
There are appropriate storage containers or spaces for hazardous/infectious waste
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Materials Management System Assessment
Materials Management System
-
The Following systems are in place and utilized
-
Warehouse inventory
-
Materials Handling Equipment Inventory
-
Supplier inventory
-
Tool inventory
-
General Comments
Infection Control Assessment
Infection Control (Hospitals only)
-
All employees receive annual Infection control training and training is documented
-
Provide Reason for partial compliance or non-compliance
-
All new construction and remodels are reviewed by the infection control committee when deemed appropriate, and an ICRA prepared
-
Provide Reason for partial compliance or non-compliance
-
Employees are instructed on the proper wearing apparel in surgical suites
-
Provide Reason for partial compliance or non-compliance
-
Engineering personnel are trained in the procedures for entering and leaving isolation areas
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Work Order Statistics Assessment
Work Order Statistics
-
Work Order statistics are reported weekly
-
Provide Reason for partial compliance or non-compliance
-
Work Order statistics are reported monthly
-
Provide Reason for partial compliance or non-compliance
-
General Comment's
Training Assessment
Training
-
In-service training meetings are conducted on a monthly basis
-
Provide Reason for partial compliance or non-compliance
-
There is a 12-month Program Schedule outlining topics to be reviewed
-
Provide Reason for partial compliance or non-compliance
-
Lockout/tagout & construction safety
-
Provide Reason for partial compliance or non-compliance
-
Electrical, equipment and tool safety
-
Provide Reason for partial compliance or non-compliance
-
Hazardous communication/chemical safety
-
Provide Reason for partial compliance or non-compliance
-
Asbestos management (if applicable)
-
Provide Reason for partial compliance or non-compliance
-
Bloodborne pathogens
-
Provide Reason for partial compliance or non-compliance
-
Infection control
-
Provide Reason for partial compliance or non-compliance
-
Fire response/fire drills
-
Provide Reason for partial compliance or non-compliance
-
Personal protective equipment
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Aesthetics Assessment
Aesthetics
-
Periodic rounds are scheduled to assess facility aesthetics and signage
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Purchasing / Financial Policy Assessment
Purchasing Policies Assessment
-
There is a policy requiring that proposed acquisitions of bedding, carpeting, drapes, wallcoverings, furniture, etc. be reviewed for fire safety
-
Provide Reason for partial compliance or non-compliance
-
The policy is implemented
-
Provide Reason for partial compliance or non-compliance
-
A policy/procedure is in place outlining purchasing procedures for the department that clearly outlines who may purchase materials
-
Provide Reason for partial compliance or non-compliance
-
The policy is implemented and followed
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Financial Tracking Assessment
-
Actual dollar expenditures for entire department are within the facility's budget year-to-date
-
Provide Reason for partial compliance or non-compliance
-
All invoices pertaining to the department are approved by the Department Manager before payment
-
Provide Reason for partial compliance or non-compliance
-
Actual dollar expenditures for salaries/expenses are within the facility's budget year-to-date
-
Provide Reason for partial compliance or non-compliance
-
Actual dollar expenditures for supplies are within the facility's budget year-to-date
-
Provide Reason for partial compliance or non-compliance
-
Actual dollar expenditures for purchased services are within the facility's budget year-to-date
-
Provide Reason for partial compliance or non-compliance
-
Actual dollar expenditures for overtime are within the facility's actual dollar expenditures for overtime are within the facility's
-
Provide Reason for partial compliance or non-compliance
-
There is a five year capital plan
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Energy Management Assessment
Energy Management
-
A monthly record is kept of fuel oil consumption
-
Provide Reason for partial compliance or non-compliance
-
A monthly record is kept of Nature Gas consumption
-
Provide Reason for partial compliance or non-compliance
-
Actual dollar expenditures for fuel oil are within the facility's budget year-to-date
-
Provide Reason for partial compliance or non-compliance
-
A monthly record is kept of electrical consumption
-
Provide Reason for partial compliance or non-compliance
-
A monthly record is kept of water consumption
-
Provide Reason for partial compliance or non-compliance
-
Actual dollar expenditures for electricity are within the facility's
-
Provide Reason for partial compliance or non-compliance
-
Actual dollar expenditures for natural gas are within the facility's budget year-to-date
-
Provide Reason for partial compliance or non-compliance
-
Actual dollar expenditures for water are within the facility's budget year-to-date
-
Provide Reason for partial compliance or non-compliance
-
Actual dollar expenditures for combined utility consumption are within the facility's budget year-to-date
-
Provide Reason for partial compliance or non-compliance
-
Department Manager has provided the facility with a plan for energy conservation and plan is implemented
-
Provide Reason for partial compliance or non-compliance
-
General Comments
Close out Comments
Close out Comments
-
General Comment and notes
-
Additional Non-Specific Photos
-
Signature of Assessor
Add Additional Signatures
-
Signee Name
-
Company
-
Title