Title Page

  • Site Name

  • Conducted on

  • Prepared by

  • Position

  • Current Conditions

  • Forecast Conditions

SDMO V220 Generator Load Checks

No Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

No Load

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

20% Load

20% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

20% Load (40 kW @ 56A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

40% Load

40% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

40% Load (80 kW @ 11.24A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

60% Load

60% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

60% Load (120 kW @ 166.86A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

80% Load

80% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

80% Load (160 kW @ 220A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

60% Load

60% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

60% Load (120 kW @ 166.86A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

40% Load

40% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

40% Load (80 kW @ 11.24A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

20% Load

20% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

20% Load (40 kW @ 56A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

No Load

No Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

No Load

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

SDMO J88k Generator Load Checks

No Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

No Load

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

20% Load

20% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

20% Load (15.91 kW @ 22A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

40% Load

40% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

40% Load (31.82 kW @ 44A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

60% Load

60% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

60% Load (47.73 kW @ 66A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

80% Load

80% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

80% Load (63.64 kW @ 88A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

60% Load

60% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

60% Load (47.73 kW @ 66A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

40% Load

40% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

40% Load (31.82 kW @ 44A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

20% Load

20% Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

20% Load (15.91 kW @ 22A)

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

No Load

No Load (Condition)

  • Voltage 1-2 (Fundamental RMS)

  • Voltage 2-3 (Fundamental RMS)

  • Voltage 1-3 (Fundamental RMS)

  • Average Phase to Phase Voltage

  • Voltage Imbalance Phases to Phase

  • Derating (%), Phase to Phase

  • Voltage 1-2 (CF)

  • Voltage 2-3 (CF)

  • Voltage 1-3 (CF)

No Load

  • Voltage 1-2 (THD)

  • Voltage 2-3 (THD)

  • Voltage 1-3 (THD)

  • Harmonic Voltage Factor

  • Derating (%), HVF

  • Voltage 1 (Fundamental RMS)

  • Voltage 2 (Fundamental RMS)

  • Voltage 3 (Fundamental RMS)

Notes

  • Enter any notes below:ret

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.