Prepared by Ted Saunders, CFPS Patriot Fire & Life Safety Consulting
-
Location: 5525 Research Park Drive
-
Wayne Keehner, Building Manager
Building Information
-
Number of floors: 5 Including occupied basement level
-
Occupancy type: Business
Exit Components
-
Number of exits at level of exit discharge.
-
Number of exits on other floors: 2
-
All means of egress clear, unobstructed, and unlocked.
-
Doors, panic bars, and other hardware in good condition and functioning properly.
-
Stairwells are clear of storage and properly marked
-
Stairwell doors function properly
-
Openings and penetrations in stairwells are properly sealed or protected.
-
Exit signs are code compliant.
-
Stairwell floor designation signs installed per code.
-
Emergency lights tested and functioning properly.
-
Emergency light placement is code compliant.
-
Fire service phones operating properly
Emergency Procedures
-
Written emergency plan up to date and on file.
-
Evacuation drill conducted within the past 12 months.
-
Emergency evacuation floor plans provided.
-
Employees trained in emergency procedures.
-
Employees trained in proper use of fire extinguishers.
Fire Alarm - Central System
-
Control panel indicates system is powered.
-
Control panel is clear of trouble or supervisory signals.
-
Annunciator panel is functional and accessible
-
Batteries are in good condition.
-
Pull stations are visible and unobstructed.
-
Audio/visual device placement appears adequate.
-
Detection devices are in good condition and functional.
-
Enter date of last service.
-
Tap to enter information
-
Vendor test/maintenance report reviewed.
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
Automatic Sprinkler System - General Areas
-
Valves and gauges in good condition and functional.
-
System pressures appear to be adequate.
-
Sprinkler heads in good condition and properly located.
-
Spare sprinkler heads and wrench provided.
-
Date of last service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not reviewed
Standpipe System
-
System Class: Class I (Fire Department use only)
-
System Type: Wet
-
Pipes, valves, hose connections are in good condition.
-
Caps are in place at each connection.
-
System pressures appear to be adequate.
-
System appears to be operational.
-
Fire department connection is accessible, in good condition and properly marked.
Emergency Power Supply Systems
-
Building is equipped with three (3) emergency power generators located as follows:
-
Unit #1: Basement level of main building.
-
Units #2 & 3: Building 2
-
Building is equipped with two (2) UPS rooms as follows:
-
One in basement (Erickson) and one on 1st floor (Allegis)
-
Emergency generator room ventilation and exhaust systems are well maintained.
-
UPS rooms are well maintained.
-
Battery systems are well maintained.
-
Exterior fuel tanks are protected from damage and free of leaks.
-
Interior day tank is free of leaks and well maintained.
-
Date of last load test.
-
Tap to enter information
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report .
-
Yes
-
No
-
Not Reviewed
Allegis Data Center
-
The following information is for systems located in the 1st floor data center, UPS room and vacant space.
-
Clean agent systems are charged and operational.
-
Detection and discharge devices appear operational.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
-
Sprinkler pre-action system is operational.
-
Valves and gauges in good condition.
-
System pressures appear adequate.
-
Sprinkler heads in good condition and properly placed.
-
Spare sprinkler heads and wrench provided.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
-
VESDA systems (3) are powered and functional.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
-
Fire alarm control panel indicates system is powered.
-
Control panel is clear of trouble or supervisory signals.
-
Batteries appear to be in good condition.
-
Pull stations are visible and accessible.
-
Audio/visual device placement appears adequate.
-
Detection devices are in good condition and appear functional.
-
Date of last service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not reviewed
Erickson Data Center
-
The following information is for systems located in the Erickson data center and UPS room.
-
Clean agent systems are charged and operational.
-
Detection and discharge devices appear operational.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
-
Sprinkler pre-action system is operational.
-
Valves and gauges in good condition.
-
System pressures appear adequate.
-
Sprinkler heads in good condition and properly placed.
-
Spare sprinkler heads and wrench provided.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
-
VESDA system is powered and functional.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
RLTV Data Center
-
The following information is for systems located in the RLTV data center and mechanical room.
-
Clean agent systems are charged and operational.
-
Detection and discharge devices appear operational.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
-
Sprinkler pre-action system is operational.
-
Valves and gauges are in good condition.
-
System pressures appear adequate.
-
Sprinkler heads in good condition and properly placed.
-
Spare sprinkler heads and wrench provided.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
-
VESDA systems (2) are powered and functional.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not Reviewed
Building # 2
-
The following information is for systems located in Building #2
-
Dry-pipe sprinkler system is operational.
-
Valves and gauges are in good condition.
-
System pressures appear adequate.
-
Sprinkler heads are in good condition and properly placed.
-
Spare sprinkler heads and wrench provided.
-
Date of last vendor service.
-
Tap to enter information
-
Deficiencies noted vendor report.
-
Yes
-
No
-
Not Reviewed
-
Fire alarm control panel indicates system is powered.
-
Control panel is clear of trouble or supervisory signals.
-
Batteries appear to be in good condition.
-
Pull stations are visible and unobstructed.
-
Audio/visual device placement appears adequate.
-
Detection devices are in good condition and functional.
-
Date of last service
-
Tap to enter information
-
Deficiencies noted in vendor report.
-
Yes
-
No
-
Not reviewed
Delicatessen
-
Kitchen hood system is operational.
-
Discharge nozzles are in good condition.
-
Manual activation device is in good condition, visible and accessible.
-
Employees know procedure for manually activating system.
-
Date of last service.
-
Tap to enter information
-
Exits are clearly marked, unlocked and unobstructed.
-
Occupancy capacity card is displayed.
Portable Fire Extinguishers
-
Extinguishers are properly mounted, accessible and fully charged.
-
Distribution appears adequate.
-
Monthly inspections are recorded on tag.
-
Date of last service.
-
Tap to enter information
Elevators
-
Four elevators serving all floors.
-
Fire department control keys provided.
-
Emergency phones working properly.
-
State certification up to date.
General Fire Prevention
-
All areas are clear of excessive combustible storage.
-
Combustible/flammable liquids are properly stored.
-
Minimum 18 inches of clearance maintained from sprinkler heads.
-
"No smoking" regulations enforced.
-
Electrical appliances properly used and maintained.
-
General good housekeeping is maintained.
-
All electrical/mechanical rooms and miscellaneous areas of the building are code compliant.
-
Additional information.
-
Tap to enter information
-
Tap to enter information