General organization of the Shop / Potential Trip Hazards / Housekeeping
-
Overhead loft(s) rated for load and posted; shelves not overloaded
-
Load limits posted on over head hoists and floor jacks
-
Flammable storage must be approved cabinet, vent plug in place
-
Gas cylinder storage - 20‘ apart and chained
-
Flashback arrestors (by torch end)
-
Arc Welder: No repairs 1st. 10‘ of stringer lead
-
Arc Welder: no visible damage to insulation on the rest of leads
-
Arc Welder: no exposed lugs where lead attaches
-
Electrical: 3’ clearance in front of circuit breaker boxes, disconnects, and panel(s)
-
Electrical: Properly labeled (power source, use, voltage, arc flash hazard)
-
Electrical: no open, uncovered slots in breaker boxes or panels
-
Electrical: All outlets have covers and are GFCI protected
-
Electrical: is romax wiring exposed to contact that could cause a short
-
Electrical: Cords - no tape repairs, plug end has ground pin
-
Bench Grinder: work rest - max 1/8” gap at bottom, tongue guard - max 1/4” gap at top of grinding wheel, side guards on each wheel spindle, eye shield secured
-
Drill Press - Secured, drill bit guard in place & clamp
-
PPE: Eye & Face Protection - face shield, welding mask, apron & gloves, googles for cutting / grinding
-
Welding Fumes ventilated by exhaust fan
-
Welding Curtain(s) - needed, used properly and good condition
-
Fire Extinguisher(s) - present, hung up, unobstructed and inspected
-
Exits: Posted and access to exit has clear runway (28”min)
MCC
-
“Danger: Authorized Personal Only” signage posted
-
MCC Room clean with no stored material not specific to the room
-
3’ Clearance in front of circuit breaker boxes and disconnects
-
Condition of boxes
-
All panels and covers closed and sealed completely
-
Water and Dust tight - any condensation issues
-
1200 amp service or larger need panic doors that open outward
-
MCC Labeling: Disconnects and Breakers labeled for use
-
MCC Labeling: Arc / Shock / Blast signage on or near all electrical boxes
-
MCC Labeling: Power source and voltage identified
-
MCC Labeling: Main Disconnects labeled and clearly marked “ON and Off”
-
Metter is rated either Cat 111 or IV
-
MCC room pressurized
-
MCC : PPE - Double layer switching hood & FR 8 (min) clothing accessible
-
MCC: PPE - Electric gloves certified in past 6 months
-
MCC: PPE - review procedures on pre-use glove inspection with employee(s)
-
MCC: Dielectric mat present and in good condition
-
MCC: Voltage rated blanket present and inspected annually
-
MCC: Fire Extinguisher(s) - present, hung up, unobstructed and inspected
-
MCC Exits: Posted and access to exit clear (28”min)
DRYER
-
“Confined Space” signage on access doors / panels
-
Gas or propane supply line(s) marked properly and grounded
-
System’s gas or propane supply line protected from truck traffic - crash protection
-
System has automatic shutoff valve(s) in place
-
Disconnects and breakers labeled per general instructions
-
Dryer access ladder(s) and platforms compliant; both interior and exterior
-
Verify fall protection and fall protection signage is present on the roof
-
Verify pre-season inspection check has been completed
-
Complete gas leak check: smell or bubble test the gas line
MANLIFT
-
Electric Powered: Fire extinguisher present
-
Electrical Powered: Weight capacity posted
-
Manlift car lighting works
-
Alarm functions
-
Restricted access to manlift shaft - (interlocking doors preferred)
-
Rope Pulled: Rail / Chain installed on open side
-
Rope Pulled: Properly weighted, portable weights secured on car
-
Door on every floor is latched when manlift is not present
-
Manlift shaft has adequate lighting at all levels
-
Manlift(s) 3rd. Party inspection: Annually for electric / 5 year inspection for Rope Pull
TRUCK RECIEVING / LOADOUT
-
Area clean and organized
-
Tools are non-sparking, in good condition, and organized
-
Pit grating is level and secure, no bent bars, 2.5” spacing max between bar rungs
-
Openings to lower levels of receiving pit are guarded
-
Truck loadout platforms have proper access ladders with chained or self-closing gate
-
Adequate lighting at the receiving pit and loadout area
-
HK schedule includes underneath truck scales, scale probe functions properly
RAIL CAR LOADING / UNIT TRAINS
-
Fall Protection adequate for the facility for the number of cars
-
Fall protection posts are not leaning
-
Rail Car openers - adequate power, no assistance required
-
Tracks cleared of spilled grain
-
Gate Opener - condition
-
Is there a visible indicator at both ends of the fall protection system
-
Track condition - (Frogs, Switch Points, Track sized properly)
-
Fall Protection lifeline annual inspection
-
Locomotive - Trackmobile - right size for the operation, condition
BOOT PIT
-
Safe and easy access
-
Adequate lighting
-
House Keeping: Combustible dust, Fugitive grain, Water issues
-
Confined Space signage posted
BUCKET ELEVATOR
-
<br>Head Section: Access to Head Section
-
Condition of motor; maintained and properly rated
-
Gearbox in good condition and documented maintenance
-
Belt Alignment sensors present
-
Pressure relief venting for inside elevators
-
Side lagging present under the belt and on top of the Head Pulley
-
Bonnet: lagging inspection doors below the centerline of head pulley
-
Tail section: Belt alignment sensors present.
-
Slow-down sensors present
-
Bearing temperature sensors present
-
Magnets on inlet side of all shipping and receiving legs
-
Bucket elevator general casing condition
-
Bucket elevator load rating on lifting beams at the top
-
Bucket elevator emergency stop at the motor
ENCLOSED CONVEYORS
-
Condition of chain
-
Condition of Gearbox
-
Overall sound while running
-
Overall condition of conveyor
-
Expanded metal inspection holes at tail and head in front of all loaders
-
HTD drives on all inside drives
-
Removable slide lagging
-
None sparking splice ad splice protectors
BELT CONVEYORS
-
Motor
-
Gearbox in good condition with documented maintenance
-
Speed detection equipment
-
Bearing temperature equipment
-
Alignment sensing equipment
-
HTD drives n all inside drives
GRAIN STORAGE & SPOUTING
CONCRETE SILOS
-
Concrete integrity
-
Spalding
-
Foundation
-
Paint
STEEL BINS
-
Is there a sweep auger in each bin
-
Roof - free from leaks
-
Roof Fans - adequate number, overall condition
-
Roof rated for load
-
Side wall sheets - any missing or sheared bolts
-
Foundation
-
Floor fans - adequate CFM, overall condition
-
Condition of reclaim conveyor, covers / lids in place, any noise or vibration
-
Reclaim tunnel - clean and well lite, sumps access closed
Spouting
-
Ceramic or AR lined when replaced
-
Square Spouts and transitions have removable lids
-
Wet grain designed at 45 degrees
-
Dry grain designed at 40 degrees
PROCESS SAFETY
-
All electrical systems intrinsically safe ( class II, group E, F, & G Division 1
-
All Bearing sensors scanning at least every 20 seconds max
-
Bearing sensors: initial max setting of 140 degrees F
-
Bearing sensors: no sensor have an absolute max greater than 190 degrees F for outside bearings and 180 degrees F for inside bearings
-
Bearing Temperature sensors display the actual temp
-
Alignment sensors monitor misalignment on both sides of equipment
-
Alignment sensors display the actual temperature
-
Speed monitors: First alarm is to set alarm at 90% of operating speed
-
Speed monitors: Second alarm is set to shut the equipment down at 80% of operating speed
-
Speed monitors: start up delays set between 5 and 10 seconds
-
Speed monitors: exposed rotating sensor areProperly guarded
-
Speed monitors: verify there are no bypass switches
-
Speed monitors must indicate running RPM or percent ( percent is preferred)
AIR COMPRESSOR
-
Air nozzle with 30 psi max
-
Properly crimped connections, no hose clamps or open ends
-
Air lines labeled or color coded, no pvc material
-
All moving parts guarded
-
Pop off valve functioning properly, checked annually
-
No oil leaks, tank fitted with auto drain system
-
Monthly inspection documented
MOBILE EQUIPMENT
-
Forklift: Fire extinguisher present
-
Forklift: Daily inspection documented for past 30 days
-
Forklift: seat belt / safety devices present
-
Forklift: Back up lights / horn functioning properly
-
Forklift: basket has kill switch, locking attachment, and place designed to attach lanyard
-
Skid Loader: Hour Meter functions
-
Skid Loader: Seat Belt - Seat bar - Control Interlocks functions properly
-
Skid Loader: Front Horn / Backup Alarm function
-
Skid loader: Loader lift arms, lift links and cylinders, steering cylinder all function properly.
-
Skid Loader: General overall condition of cab and instrument panel, no oil leaks, no loose or broken parts, tires or track in good condition.
-
Skid Loader: Lights, brakes, and warning signals operate properly, mirror(s) good condition.
-
Payloader:
-
Payloader:
-
Payloader:
-
Payloader:
-
Payloader:
-
Payloader:
GENERAL SAFETY
-
Emergency Issues: Exit signs on or above exits
-
“No Smoking” signs posted for the facility
-
“ No Smoking” and ‘Emergency Shutdown” posted on propane tanks
-
At least 2 ladder exits from bin decks
-
Grain Storage: Structure labeled with identification name or number
-
Grain Storage: Grating is present for every floor opening
-
Grain Storage: Bottom grates capable of locked closed
-
Grain Storage: Sweep auger - cords and guards in good condition, kill switch functioning
-
Grain Storage: Lighting approved for class II, Division 1, Cords in good condition
-
House Keeping: HK Schedule documented
-
House Keeping: Priority Areas - no dust accumulation over 1/8“
-
House Keeping: Non-sparking tool used in bins, driveways, confined spaces
GUARDING, LADDERS, HANDRAIL and STAIRWAYS
-
Couplers, drive belts, horizontal shafts guarded
-
Exposed shaft ends do not to exceed 1/2 of its diameter
-
Sharp edges in work zone removed or guarded
-
Ladder Safety: offsets every 30’ of ladder reach
-
Ladder Safety: Ladder cage required at 20’ of length and beyond
-
Ladder Safety: Ladder has minimum of 7” back clearance for entire length
-
Ladder Safety: Rungs to be evenly spaced, not to exceed 12” spacing between rungs
-
Ladder Safety: Each rung to have minimum diameter of 3/4”
-
Ladder Safety: Ladder width to be minimum of 16” between side rails
-
Ladder Safety: Bottom rung of ladder not to be more than 12” from ground or platform
-
Ladder Safety: Ladder to extend 42” above platform or roof edge
-
Ladder Safety: Portable ladders to have feet in good condition
-
Ladder Safety: Ladder needs to be fiberglass if used around electrical
-
Ladder Safety: Pass thru ladder openings are offset 18” minimum, 24” maximun
-
Stairway Safety: Steps need to be uniform rise & run, not to exceed 50 degrees
-
All work platforms have handrail and self-closing gate or chains. (2 minimum)
-
General Electrical: No breaks in conduit
-
General Electrical: All boxes and door panel closed, covers on
-
General Electrical: Sump pumps located inside approved for class II locations
-
General Electrical: Sump pumps direct wired or wired with a “twist-lock”
-
General Electrical: Motors inside building; class II, Division 1, Group G rating
LOCK OUT - TAG OUT
-
Lock Out program has a written policy at location
-
Lock Out program has written procedures for the location
-
Location has adequate lock out devices for the facility
-
Lock Out permits have been documented and are on file
-
Annual Lock Out certification per individual has been completed and documented
PERMIT REQUIRED CONFINED SPACE - BIN ENTRY
-
Location has documented all confined space locations on the facility
-
Confined Space - Bin Entry permit(s) have been completed and are on file
-
Permit Required Confined Space signage is on all locations at the facility
-
4-Gas monitor is available, and calibrated according to manufacturer recommendations
-
Confined Space:
-
Confined Space:
-
Confined Space:
-
Bin Entry:
-
Bin Entry:
-
Bin Entry:
-
Bin Entry:
MISCELLANEOUS
-
Fuel Tanks: NFPA Signage
-
Fuel Tanks: Secondary containment closed - does not leak
-
Facility Emergency Action Plan: Shutdown and Evacuation procedures written and on file. Current Head Count locations and Emergency Telephone numbers posted.
-
Facility property: Overall visual aspects / condition of the property (Good Neighbor Policy) “Welcome Sign w/ Visitors Must Sign In” posted.
-
Hi-Vis FCE clothing worn by FT employee(s)