Title Page
-
Business Name
-
Location
-
Date of Inspection
-
Inspector
Plans / Drawings
-
Verify approved plans / drawings are on-site or are available to the contractor.
-
Verify that the procedures for unlocking the doors are described in the emergency preparedness plan as required by Chapter 4.
-
Verify a permit application has been submitted for an automatic fire sprinkler system and/or a fire alarm system.
Visual Inspection
-
Occupants will pass through no more than one door equipped with a controlled egress / delayed egress locking system before entering an exit.
-
The door locking system is listed in accordance with UL 294.
-
Door swings in the direction of egress.
-
Emergency lighting is provided at the egress door.
-
“Push to Exit” button is installed, readily visible / accessible, and labeled.
Operational Test
-
Door releases upon fire sprinkler / fire alarm activation.
-
Door releases upon loss of power to the lock or locking mechanism.
-
Door releases upon pressing of “PUSH TO EXIT” button and remains unlocked for 30 seconds.
-
Door releases upon activation of motion sensor.
-
Door releases upon activating an override switch at the fire command center, nursing station, or other approved location.
Delayed Egress
-
Signage that states “PUSH UNTIL ALARM SOUNDS - DOOR CAN BE OPENED IN 15 SECONDS” is located above and within 12 inches of the door hardware.
-
An irreversible process after release device is pressed for 1 second and the door unlocks within 15 seconds.
-
An audible signal activates in the vicinity of the door once the release device is pressed.
-
The delayed egress system must be manually reset.
Inspection Status
-
Inspection Status
-
Next Inspection
-
Owner / Representative
-
Phone #
-
Email Address