Title Page
-
Business Name
-
Location
-
Date of Inspection
-
Inspector
Plans / Drawings
-
Verify approved plans / drawings are on-site or are available to the contractor.
Visual Inspection
Wiring
-
Wiring location, size, and type matches the specifications on approved plans.
-
Wiring is properly secured and clear of sharp objects.
-
Wiring is properly supported (not tied to ceiling grid support).
-
Verify Class A wiring with 4 foot separation in loops.
-
Wiring is provided for all devices shown on drawings.
Main Panel and Annunciator Panels
-
Dedicated electrical circuit is identified and posted at the main panel.
-
Breaker serving the main panel is labeled, marked in red, and locked in the open position.
-
Verify battery sizes match approved plans.
-
Verify batteries are labeled with month / year installed.
-
Verify that the fire alarm panel is grounded.
-
Verify that resistors are not being improperly used to bypass fault detection.
-
Map / legend posted at fire alarm panel and annunciators.
-
Verify annunciators panels are installed per approved plans.
Power Supplies
-
Dedicated electrical circuit is identified and posted at the power supply.
-
Breaker serving power supplies are labeled, marked in red, and locked in the open.
-
Verify battery sizes match approved plans.
-
Verify batteries are labeled with month / year installed.
-
Ensure power supply panel is grounded.
Initiating Devices
-
Initiating devices located as per approved drawings (smoke; heat; pull stations; water flow switches; modules).
-
Verify pull stations are double action.
-
Duct detector remote test switch and LED is installed.
Notification Appliances
-
Notification appliances located as per approved drawings (speakers; horns; strobes).
-
Strobes are set to correct candela as per approved plans.
Operational Test
-
Verify general operation of main panel and annunciator panels.
-
Communication lines disconnected and trouble signal is reported to main panel.
-
Disconnect batteries at main panel and trouble signal is reported to main panel.
-
Turn off electrical breaker supplying main panel and trouble signal is reported to main panel.
-
Disconnect batteries at power supply and trouble signal is reported to main panel.
-
Turn off electrical breaker supplying power supply and trouble signal is reported to main panel.
-
Remove device from each NAC and a trouble is reported at main panel.
Inspection Status
-
Inspection Status
-
Next Inspection
-
Fire Alarm Contractor
-
Phone #
-
Email Address