Information
-
AHU/FCU's IN VERY HIGH RISK AREAS - MONTHLY MAINTENANCE
-
Location
-
Conducted on
-
Campus
-
-
Completed By
-
-
Document No.
-
- John Cade
- Materials Handling
- 1B
- Main Block
- Outpatients
- CMR
- Clinical Sciences Bldg
- 1A
- Allied Health
- Infill/Centre Block
-
- B
- G
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- 12
- Roof
-
AHU/FCU Description (eg AHU 3W)
-
Plant Room Asset Number (if AHU)
-
Room Number (if AHU)
-
AHU/FCU Asset Number
Plantroom
-
Plantroom free from rubbish and safe to enter
-
Send to WOMS
Outdoor air intakes and exhaust air outlets
-
Undertaken inspection and cleaning as required
-
Send to WOMS
Heating and cooling coils
-
Undertaken inspection and cleaning as required
-
Send to WOMS
Drip trays, drains and drain traps
-
Inspect and prime with water as required
-
Send to WOMS
Fan Belts
-
Belt tension, wear to be checked. Adjust or replace as required
-
Send to WOMS
Pulleys
-
Damage, wear to be checked. Record and replace as required.
-
Send to WOMS
Drive and drive shaft guard
-
Ensure firmly in place. Adjust as required.
-
Send to WOMS
Fan
-
Ensure fan operates and is free of vibration, bearing noise and overheating. Record and replace as required
-
Send to WOMS
Fan Hold Down Bolts
-
Check mounts and hold down bolts for security
-
Send to WOMS
Motor bearings
-
Inspect motor bearings for noise and temperature
-
Send to WOMS
Filters
-
Inspect filters. Determine if maintenance required.
-
Send to WOMS
Mechanical Boards
-
Check board is free from faults and perform lamp test to check all lights working
-
Send to WOMS
Electrical Connections
-
Check all electrical connections and associated wiring
-
Send to WOMS
Lubrication
-
Lubricate motor bearings where required
-
Send to WOMS
Filter Air Leakage
-
Check to ensure no air leakage around filter media
-
Send to WOMS
Flexible Connections
-
Check condition of any flexible connections and report
-
Send to WOMS
AHU doors
-
Check AHU doors and fastenings
-
Send to WOMS
Insulation
-
Ensure insulation is secure
-
Send to WOMS
Lights
-
Replace defective lights
-
Send to WOMS
Dampers
-
Check all damper linkages and operation
-
Send to WOMS
Electric Motor Amps
-
Check electric motor maximum duty amps against nameplate
-
Send to WOMS
Automatic bearing lubricators
-
Check automatic bearing lubricators and report
-
Send to WOMS
Excess Lubricant
-
Remove and clean ant excess lubricants / greases from bearings
-
Send to WOMS
BAS Alarms and Faults
-
BAS alarms and reported faults ok?
-
Send to WOMS
Manual Overrides
-
Check that manual overrides are set in automatic
-
Send to WOMS
Time Schedules
-
Check time schedules are current and adjust if necessary
-
Send to WOMS
Temperatures
-
Check temperatures on floors, in rooms or in any areas requiring special conditions
-
Send to WOMS
Pressure Controls
-
Check pressure controls where applicable on floors, in rooms or in any areas requiring special conditions
-
Send to WOMS
Actuators
-
Check actuators and controls for physical damage
-
Send to WOMS
Lubrication
-
Lubricate spindles and linkages where required
-
Send to WOMS
Correct Operation
-
Check all controls for correct operation
-
Send to WOMS
-
Items to follow up? Write details.
-
Add signature