RAMS

  • Risk assessment completed

  • Method statement completed

  • PPE

  • Engineer Initials

SFG 20 Procedure

Unit Filters

  • Check manometer reading and renew filter media as indicated.

Condensate Drains

  • Check for condensate carry-over and that drains are clear

  • Check condition of condensate tray and repaint as necessary, close condensate trap and fill tray to maximum with clean fresh water.

  • Examine and ensure that all drain points and pipework are clear and free from obstruction, clean/disinfect and report drip tray condition.

  • Removed any loose debris using wet and dry vacuum cleaner

  • Ensure that adequate air-break exists between condensate trap and drain to prevent siphoning.

General

  • Visually examine entire unit and check for correct operation. Ensure all brackets, supports, mountings and fixings are in position and secure.

  • Examine for any undue noise, vibration or overheating and report accordingly

  • Ensure all access panels are correctly positioned and secure

  • Examine the unit for water or air leaks.

  • Check and ensure security and integrity of safety guards.

  • Examine AHU flexible connections and ensure security of retaining bands.

  • Where accessible, examine all manually operated valves. Ensure full and free travel and correct setting, checking for leakage.

  • Thoroughly cleaned the interior of the unit and checked for corrosion.

Motorized Dampers & Actuators

  • Check to see that louvers are clear and not obstructed, couplings are secure and that motor runs without excessive noise or vibration.

  • Remotely operate controls to check that actuator operates correctly and in sequence with other interconnected dampers.

  • Examine actuators, dampers and linkages for security and freedom of movement and lubricate as required.

  • Ensure full and free travel and check the integrity of all mechanical linkages.

  • Check condition of all wiring and wiring facilities, ensuring security of terminations.

Frost protection, boost thermostat and controls

  • Check operation.

Fans

  • Check operation of fans

Heating and cooling coils

  • Check condition and clean.

Controls and electrical connections

  • Check operation and condition.

Valves

  • Fully open and close and then reset at the original setting.

Motors

  • Checked all motors in accordance with Motors - Drive Elements (SFG 39-01).

Anti-vibration mountings and duct-work flexible connections

  • Check condition.

Additional Comments

  • Report of any faults

Safety checks

  • Inspection Completed

  • Area left safe

  • Area left clean

Polyteck Building Services, 143 Leman Street, London, E1 8EY

  • Engineer signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.