The following quality control checklist is to be completed everyday to ensure compliance with the relevant standard AS5100.8
-
Add location
-
Specify product manufacturer, product name and batch no.
-
-
Select date
-
Surface Moisture Content less than 10%
-
Dew Point Temperature > Ambient Temperature + 3 Degrees Celsius
-
Relative Humidity Less than 85%
Surface Preparation
-
Surface free of the following: Dust, oil, grease, loose particles, remnants of curing compound, waxes, coatings, organics contaminants and weak concrete layers
How has the surface been prepped? Specify:
-
Dry abrasive blasting, wet abrasive blasting, steam cleaning, angle grinder, high pressure water blast
-
Amplitude of surface profile to be between 0.5-1mm (60 grit sand paper)
-
Minimum corner radius of 25mm
Treatment of cracks
-
Cracks greater than 0.2mm repaired using resin injection
-
Cracks less than 0.2mm coated with bridging layer of epoxy putty (Masterbrace 4000 Adhesive)
-
Provide photographic evidence of surface preparation Pro
-
Add media
Environmental Conditions
-
The FRP strengthening system can only be installed when all of the following conditions are met
-
Ambient temperature between 5-30 degrees Celsius
-
Concrete surface temperature between 8-35 degrees Celsius
-
Relative humidity below 85%
-
No rain or run off, including leaks and seepage through bridge decks that may affect adhesion
-
Surface temperature of substrate is 3 degrees higher than dew point temperature
-
Moisture content of substrate below 8%
Inspection Criteria
-
The following components of the FRP system shall be routinely inspected over the course of the installation
-
Changes in colour of FRP strengthening system
-
Debonding
-
Peeling
-
Blistering
-
Cracking and crazing
-
Excessive deflections
-
Provide photographic of Installation of FRP system
-
Add media
Pull of Adhesion Testing
-
Mean adhesion pull of strength of 1.5MPa with no individual result less than 1.35MPa
-
Minimum concrete compressive strength required for FRP strengthening is 17Mpa
-
Adhesion testing conducted at the following intervals: 1 per 75 lin.m of or repair or 1 sample per 10m^2