System and Pack Control Switches and Controllers, Controls.
-
Using a calibrated gauge, check suction and discharge pressure transducers are reading correctly, Calibrate or replace as required.
Electrical Panels and Switch Gear, Control Panels.
-
Check that electrical panel door isolator/interlock is functional and repair if necessary.
-
Check and replace missing panel keys
-
Check for signs of overheating or arcing on all internal panel components. Repair/replace components as required
-
Ensure panel fans are operational and clean internal panel filter
Display Cases.
-
Where fitted, check the operation of the defrost heaters. Repair/replace as required
-
Check that the control set points match the manufacturer's instructions. Correct as necessary
-
Check all joints between cabinets where multiplexed and check all end walls are sealed to the cabinet. Repair as required
-
Check all drain pumps for leaks or blockages inside and underneath the cabinet. Repair/replace as required
-
Ensure all earth bonding and straps are in place and secure. Repair as required
-
Ensure that all fixtures are visible and available on the store and remote networks
-
Condition of electrical control box and components, including all cable management, conduit, trunking and tray work. Repair as required, terminations to be tightened with an appropriate torque tool
-
Check correct operation off Doors Swing/Hinged, ensure integrity of hinges, hinge plates, retainers/fixings and handles, slow-close mechanism and frames conform to manufacturers specification. Repair or adjust as required
-
Check correct operation off Door Sliding, ensure integrity of tracks retainers/fixings, rollers, air-strings, slow-close mechanism and frames conform to manufacturers' specification. Repair or adjust as required
Cold Stores
-
Where fitted, check the operation of the drain pan defrost heaters. Replace if required
-
Where fitted, check the operation of the defrost heaters. Replace if required
-
Electrical System Integrity Checks, Ensure all earth bondings and straps are in place and secure. Repair as required
-
Ensure that all fixtures are visible and available on the store and remote networks.
-
Condition of electrical control box and components, including all cable management, conduit, trunkings and tray work. Repair as required
-
Check that the control set points match the manufacturer's instructions. Correct as required
-
Check Fabric, walls and ceiling panels for signs of delamination. Report any defects to the Customer
-
Check walls and ceiling panels and floors or any signs of wear or damage. Report any defects to the Customer
-
Check the evaporator fins for any signs of damage or deformation of the distributor, ensure inspection end plate is correctly fitted and replace if missing
-
Ensure that all entrapment and Asphyxiant protection alarms are functional. Repair/replace any defective items
Ice Makers, Water System
-
Clean Ice maker internal water system using Nickel Safe Ice machine cleaner
HVAC A/C Equipment.
-
Indoor unit Air Filter - Check, clean or replace as and when required
-
Condensate Tray - Check pipe connections, mountings. Tighten as necessary
-
Check the condensate away system for blockage and dirt. Clean as necessary
-
Check pump activation Switch condensate tray. Replace if necessary
-
Indoor unit Heat exchanger and refrigeration connections, Check for contamination. Clean as necessary (disinfect as required). Check defrost in cooling mode operates correctly, repair a necessary
-
Check operation in all modes, investigate and fix any faults. Replace as necessary
-
Outdoor Unit Compressor Running Noise. Check for Abnormal Noise. Repair/Replace as necessary
-
Outdoor/Indoor unit Fan & Motor. Running Noise, check for abnormal noise. Clean Fan. Replace Motor as required
-
Outdoor Unit heat exchanger and refrigeration connections. Check operation, investigate and fix any faults system. Check defrost activation in heating mode and repair as required
-
Outdoor Unit - check for oil quality/contamination. Clean or replace as necessary
-
Lubricate with suitable lubricant all panel locks and hinges
-
Check tightness of Electrical terminals. Tighten as necessary. Check correct operation of all switches and interlocks. Repair/replace as required
-
Outdoor/Indoor Unit - Measure Winding Resistance/Insulation integrity of fans/compressors
-
Measure and record the operating currents of all components
-
Measure and record the operating currents of all components
System
-
System ID
-
Component
component
-
Component
-
Amps