MVHR

  • 1: Check all punch-louvre's have back locking nut and are adjustable

  • 2: Set MVHR to trickle and adjust speed setting and punca louvres to achieve air velocities required. Confirm these are achieved.

  • 3: Set MVHR to boost and adjust speed setting to meet required boost air volumes.

  • 4: Confirm boost switch activates for all bathrooms / en-suites when the light is turned on.

  • 5: Confirm boost turns off as soon as light is switched off.

  • 6: All materials to be returned to storage area and the plot left clean and tidy.

This inspection sheet confirms that the item or area detailed above is 100% completed in line with the current specification, drawings and pre agreed sample panels although still remaining Sub Contractors responsibility until practical completion has been achieved.

  • Inspected by sub-contractor.

  • Inspected by wates manager.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.