Information
-
Document No.
-
Audit Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
1. Building Details
-
Add media
-
building Class
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
2. Previous Audit
-
Has there been a previous audit?
-
Has the last audit been reviewed?
-
Are there any outstanding actions?
Schedule 3.1 Structural Fire Protection and Compartmentation. BCA D2.20, D2.23, E2 AS1851
-
A rated fire door is installed across and opening in a fire wall to maintain the fire resistance rating of that fire wall. Smoke controls doors are designed to allow occupants a safe path of travel to an emergency exit in the event of fire by restricting the impact of smoke in that path of travel. A sign to alert persons that the operations of fire doors must not be impaired must be installed where it can be readily seen on or adjacent to, a required fire door providing direct access to a fire isolated exit on the side that faces a person seek egress.
-
Checking: check fire rated smoke controls doors for latching where hold hopes devices are installed press the test switch. Visually inspect fire walls and doors for fire stopping of penetrations.
-
item 1. Were the closing mechanisms for the fire / smoke doors free from damage and did they function correctly?
-
Recommendations for item 1
-
2. Are the Fire / smoke doors free from obstructions?
-
Recommendations for section 2.
-
3. Are the fire / smoke doors free from damage?
-
Recommendations for section 3.
-
4. If fitted, does the electro magnetic device function correctly?
-
Recommendations for section 4.
-
4. Is there approved signage affixed to the fire / smoke door? (fire / smoke door do not obstruct).
-
Recommendations for section 5.
-
5. Are the metal tags affixed to fire rated doors?
-
Recommendations for section 5.
-
6. Are the fire walls and floors free of penetrations?
-
Recommendations for section 6.
-
7. When was the last maintenance?
-
Recommendations for section 7.
Schedule 3.2 Means of Escape. BCA D2.21, D2.23
-
The means of escape and emergency egress routes, which will include fire stairs, must be clearly identified and provide a safe and uninstructed passage at all times.
-
Item 1. Are the emergency exit doors in the path of travel within a route of egress readily operable from the side from which egress is sought by a single hand and without the use of a key.
-
Recommendations for item 1
-
Item 2. Is the width of egress maintained at a minimum of one meter and is the path of travel clear of obstructions?
-
Item 3. Is the surface of the flooring in good condition?
-
Item 4. Paths of travel clear and well defined?
-
Item 5. Are the emergency exit stairs in good condition and free of obstructions?
-
Item 6. Are the external exit routes in good condition? Not slippery, no trip hazards.
-
Item 7. Are the terminal required emergency exit doors signposted internally and externally? "Fire safety door do not obstruct."
-
When was the last maintenance.
Schedule 3.3 Exit Signs BCA E4, E3.3, SAMF guidelines 006 & AS 2293.2/3
-
An exit sign must be clearly visible to persons approaching the exit. Warning against use of lifts in a fire. A warning sign must be displayed where it can be readily seen and near every call button for a passenger lift or group of lifts throughout the building.
-
Exit signs are designed to guide occupants and visitors of a facility to a designated exit.
-
Item 1. Are the exit signs free from damage and securely mounted?
-
Item 2. Are the exit signs clearly visible and do all directional. Signs indicate the direction of travel to the exit?
-
Item 3. Is the visual indicator glowing?
-
Item 4. Are illuminated signs serviceable? ( ie does it illuminate under battery power when the test button is depressed)
-
Item 5. Is there a maintenance record log book for illuminated exit signs and is it up to date? (6 monthly AS 2293.2 Sec 1.4.2) record date
-
Recommendation log book exit signs.
-
When was the last maintenance.
Schedule 3.4 Emergency Lighting. BCA E4 AS 2293.2/3 & OHS&R SA division 6
-
Emergency lighting must be installed in every fire isolated exit or stairway and every story of a class 5, 6, 7, 8 or 9 building where the storey has a floor area of more then 300m sq.
-
Item 1. Are illuminated lights serviceable? ( ie does it illuminate under battery power when the test button is depressed)
-
Item 2. Is the visual indicator glowing?
-
Item 3. Are the lights free from obstructions?
-
Item 4. Are the emergency lights free from damage and securely mounted?
-
Item 5. Is there a maintenance record log book for illuminated exit signs and is it up to date? (6 monthly AS 2293.2 Sec 1.4.2) record date.
-
Recommendation log book. (item 5).
-
When was the last maintenance?
Schedule 3.5 Fire fighting services and equipment
-
Fire extinguishers and fire hose reels must be installed to the degree necessary to allow occupants to safely undertake initial attach on a fire.
-
Item 1. Is there a block plan in the sprinkler control room?
-
Item 2. Is there a stop valve?
-
Item 3. Are sprinkler heads un painted.
-
Item 4. Is there a clear space under the deflector min 500mm?
-
Item 5. Is there a stock of sprinkler heads?
-
Item 6. Are all fire extinguishers at their mounting point?
-
Item 7. Is signage designated to the fire extinguisher in place?
-
Item 8. Are the fire extinguisher brackets securely mounted?
-
Item 9. Do the fire extinguishers appear to be serviceable, ie tamper proof sells and pin in place?
-
Item 10. Is there a metal service tag?
-
Item 11. Are the hose reels clearly sign posted?
-
Item 12. Are the nozzles in the interlock?
-
Item 13. Is there a device tag?
-
Item 14. Are the hose reels neatly wound on the drum.
-
Recommendations for hose reels.
-
Item 16. Is access round the fire fighting equipment unobstructed?
-
Is there a maintenance record available and is it up to date?
-
When was the last maintenance?
Schedule 3.6 Air Handling Systems.
-
Item 1. Do all smoke baffles / curtains show any sing of damage or deterioration?
-
Item 2. Are kitchen exhaust grease filters clean and not showing signs of deterioration.
-
Item 3. Make up air provisions, are all louvers clear and unobstructed?
-
Recommendations for Air Handling Systems.
-
When was the last maintenance?
Schedule 3.7 Automatic Fire Detection and Alarm Systems.
-
The fire indicator panel shall be clearly visible and accessible within the designated building entry point or the fire control room.
-
Item 1. Is the Fire Indicator Panel secure and free from damage?
-
Item 2. Is there an external fire alarm bell visual indicator?
-
Item 3. Are all detectors free from damage and securely mounted?
-
Item 4. Are the Manual Call points clearly visible and unobstructed?
-
When was the last maintenance?
Schedule 3.8 Building Emergency Warning and Intercommunication Systems. aS 1851 AS 1670
-
Item 1. Is access to the EWIS un obstructed?
-
Item 2. Are the emergency instructions displayed adjacent to the Emergency Control Point? (ECP).
-
Item 3. Are the operating procedures displayed?
-
Item 4. Is there telephone access to the public network avaliable?
-
Item 5. Are the two legible block plans avaliable?
-
Recommendations for Building Emergency Warning and intercommunication Systems.
-
When was the last maintenance?
Schedule 3.9. Lifts. BCA E3.2 & E3.4
-
Item 1. Can the emergency lift accommodate a stretcher with a patient lying on it horizontally by providing a clear space not less than 600mm wide x 2000 mm long x 1400mm high above the floor level?
-
When was the last maintenance?
Schedule 3.10. Emergency Standby Power Systems. BCA3.4AS 1851.
-
Emergency power supplies in the form of diesel generators are fitted to some buildings. Six monthly testing to ensure that the aux power is operable.
-
Is the emergency generator located in a well ventilated area?
-
Is the area clear of fuel spills and combustible materials?
-
Are there operating instructions clearly displayed?
-
Are noise hazard warnings displayed?
-
Has a power simulation bee conducted in the last 6 months?
-
When was the last maintenance?
Schedule 3.11. Interconnections - Fire Safety Systems.
-
Was there any faults noted during the last annual test?
-
When was the last maintenance?
Schedule 3.12 Access for Fire Appliances. BCA 2.4
-
6 monthly inspection to ensure that there is unobstructed access to buildings and fire fighting facilities that serve that building.
-
Is there anything obstructing access to hydrants, boosters etc.
-
Is the rubbish stored away from the building?
-
When was the last maintenance?
Schedule 3.13 clearances for Large Isolated Buildings. BCA 2.3, 2.4
-
The definition of a large isolated building is a building ove 18,000 Sq M
-
Item 1. Will the emergency services have clear unobstructed access around the building?
-
When was the last maintenance?
Schedule 3.14 Occupancy hazard. BCA E1,E10,E15
-
Do the types and sizes of fire extinguishers appear adequate and appropriate for the hazard and environmental demand?
-
Do the extinguishers cover at least the electrical hazard?
-
Are the rubbish bins emptied on a regular basis?
-
When was the last maintenance?
Schedule 3.15. Emergency Procedures AS 3745 Emergency Evacuation Management Plan (EEMP).
-
Item 1. Is the facility in possession of an up to date (EEMP)?
-
Response for EEMP. Item 1.
-
Item 2. Has warden training been provided (6 monthly record date)
-
Response for training. Item 2.
-
Has there been a trial evacuation in the last 12 months?
-
Are there records of training available?
Evacuation Diagrams.
-
Item 1. Are evacuation diagrams displayed?
-
Item 2. Do they have a legend?
-
Item 3. Are they orientated with a you are here?
-
Item 4. Is all fire equipment marked appropriately?
-
Item 5. Is the assembly area adequate?
-
Item 6. Is there a review date no more than five years from initial issue? (record date).
-
Recommendations for Evacuation Diagrams.
Sign Off
-
On site representative
-
Auditor's signature
-
Next review date.