Title Page
-
Site conducted
-
Operator Name
-
Date & Time
-
Shift
-
Need safety gear? ask your supervisor!
-
Take Photos of Leaks and Make Sure To Add In The Red Book
Boiler Room
Boiler #1
-
Alarms
-
Time of Alarm
-
Alarm Type
Supply Temperature Before Resetting Alarm
Return Temperature Before Resetting Alarm
-
Was Unit Able To Return Back To Normal
-
Did You Contact Mechanic / Controls
-
Boiler Status
Stack Temp
-
Hot Water Return Pressure
-
Control Switch / Front Panel
Boiler #2
-
Alarms
-
Time of Alarm
-
Alarm Type
Supply Temperature Before Resetting Alarm
Return Temperature Before Resetting Alarm
-
Was Unit Able To Return Back To Normal
-
Did You Contact Mechanic / Controls
-
Boiler Status
Stack Temp
-
Hot Water Return Pressure
-
Control Switch / Front Panel
Boiler #3
-
Alarms
-
Time of Alarm
-
Alarm Type
Supply Temperature Before Resetting Alarm
Return Temperature Before Resetting Alarm
-
Was Unit Able To Return Back To Normal
-
Did You Contact Mechanic / Controls
-
Boiler Status
Stack Temp
-
Hot Water Return Pressure
-
Control Switch / Front Panel
Boiler #4
-
Alarms
-
Time of Alarm
-
Alarm Type
Supply Temperature Before Resetting Alarm
Return Temperature Before Resetting Alarm
-
Was Unit Able To Return Back To Normal
-
Did You Contact Mechanic / Controls
-
Boiler Status
Stack Temp
-
Hot Water Return Pressure
-
Control Switch / Front Panel
-
---------------------------------------------------------------------------
LAB AIR
Equipment Info
-
The Air Compressors Serve Both the Labs And Exhaust
-
1 Compressor Must Be Available To Provided Air
-
If The Units Shut Off The Exhaust Fans 1-4 will need Reset
Lab Air Compressor - Quincy Status
-
YOU DO NOT NEED TO TOUCH ANY OF THE CONTROLS TO CHECK THE READINGS ON THE DRYER OR COMPRESSOR
AIR DRYER
-
Status
-
Temperture On Display
-
GREY TANK PSI
Air Compressor #1
-
Alarms
-
Status
-
Compressor Display PSI
Air Compressor #2
-
Alarms
-
Status
-
Compressor Display PSI
Hot Water Make Up Meter
-
LOOK UP - meter is over head
-
Meter Reading
CBH Heating Water Pumps
Hot Water Pump #1
-
Pump Status
-
Suction PSI
-
Discharge PSI
-
Discharge Temperature
Hot Water Pump #2
-
Pump Status
-
Suction PSI
-
Discharge PSI
-
Discharge Temperature
Hot Water Pump #3
-
Pump Status
-
Suction PSI
-
Discharge PSI
-
Discharge Temperature
Hot Water Pump #4
-
Pump Status
-
Suction PSI
-
Discharge PSI
-
Discharge Temperature
Heating Hot Water Pump - IREB
Heating Hot Water Pump #5
-
Status
-
Suction
-
Discharge
Heating Hot Water Pump #6
-
Status
-
Suction
-
Discharge
Heating Hot Water Pump #7
-
Status
-
Suction
-
Discharge
-
---------------------------------------------------------------------------
Vacuum Pumps
Equipment Info
-
Vacuum Running : Means motor is on and increasing vacuum to set point -24 to -28
-
Vacuum Not Needed : Equipment is at set point Vacuums don't need to be on
-
Vacuum Off: Vac is switched off or being called on but not running
Vacuum Pump Panel
-
Alarms
-
Vacuum Make Up Range is -24 through -28 mmHg
-
Vacuum Gauge mmHg
-
Pump #1 HOA Switch
-
Pump #2 HOA Switch
Vacuum Pump #1
-
Status
Vacuum Pump #2
-
Status
-
---------------------------------------------------------------------------
Chilled Water Make Up
-
LOCATED IN THE CAGE LOOK UP > METER IS OVER HEAD
-
Meter Reading
-
---------------------------------------------------------------------------
Domestic Water Pumps
Domestic Water Pump #1
-
Status
-
Hours
Domestic Water Pump #2
-
Status
-
Hours
Domestic Water Pump #3
-
Status
-
Hours
-
---------------------------------------------------------------------------
Aerco Domestic Hot Water Heat Exchanger
-
Status
Set Point Temperature
Supply Temperature
Chiller Room
Condenser Water Pump
Condenser Water Pump #1
-
Status
-
Suction PSI
-
Discharge PSI
-
VFD Frequency
Condenser Water Pump #2
-
Status
-
Suction
-
Discharge
-
VFD Frequency
Condenser Water Pump #3
-
Status
-
Suction
-
Discharge
-
VFD Frequency
Condenser Water Pump #4
-
Status
-
Suction
-
Discharge
-
VFD Frequency
Chilled Water Pump
Chilled Water Pump #1
-
Status
-
VFD Frequency
Chilled Water Pump #2
-
Status
-
VFD Frequency
Chilled Water Pump #3
-
Status
-
VFD Frequency
Chilled Water Pump #4
-
Status
-
VFD Frequency
Chillers
Chiller #1 - TRANE
Alarms
-
Alarms
-
What Was The Alarm Type
-
Was The Chiller Able To Be Returned To Normal Operation
-
Was Alarm Cleared / Reset
-
Did Another Chiller Turn On
-
Can You Start Another Unit
-
Did You follow The After Hours Incident Chart
Operation Status
-
Status
-
Outside Air Temperature
Compressor
-
Compressor Run Time
-
Compressor Starts
Oil Tank Temperature
-
Oil Pump Discharge Pressure
-
Oil Tank Pressure
-
Contact Foreman
Evaporator Page
-
Active Chilled Water Setpoint
Evaporator Leaving Water Temperature
Evaporator Entering Water Temperature
-
Evap Rfgt Pressure
-
Contact Foreman
Evaporator approach temperature
Condenser Page
-
Condenser Entering Water Temperature
Condenser Leaving Water Temperature
-
Condenser Refrigerant Pressure
-
Contact Foreman
Condenser approach temp
Motor Page
-
Active Current Limit Set Point
-
Contact Foreman
-
Average Motor Current Percent % RLA
Purge Page
-
Purge - Pump Out Life
Physical Gauge on Pipe
-
Chilled water Supply Pressure
-
Chilled water Return Pressure
-
Condenser Supply Pressure
-
Condenser Return Pressure
Side of Chiller Near Oil Filter
-
Oil Level
Chiller #2 - TRANE
Alarms
-
Alarms
-
What Was The Alarm Type
-
Was The Chiller Able To Be Returned To Normal Operation
-
Was Alarm Cleared / Reset
-
Did Another Chiller Turn On
-
Can You Start Another Unit
-
Did You follow The After Hours Incident Chart
Operation Status
-
Status
-
Outside Air Temperature
Compressor
-
Compressor Run Time
-
Compressor Starts
Oil Tank Temperature
-
Oil Pump Discharge Pressure
-
Oil Tank Pressure
-
Contact Foreman
Evaporator Page
-
Active Chilled Water Setpoint
Evaporator Leaving Water Temperature
Evaporator Entering Water Temperature
-
Evap Rfgt Pressure
-
Contact Foreman
Evaporator approach temperature
Condenser Page
-
Condenser Entering Water Temperature
Condenser Leaving Water Temperature
-
Condenser Refrigerant Pressure
-
Contact Foreman
Condenser approach temp
Motor Page
-
Active Current Limit Set Point
-
Contact Foreman
-
Average Motor Current Percent % RLA
Purge Page
-
Purge - Pump Out Life
Physical Gauge on Pipe
-
Chilled water Supply Pressure
-
Chilled water Return Pressure
-
Condenser Supply Pressure
-
Condenser Return Pressure
Side of Chiller Near Oil Filter
-
Oil Level
Chiller #3 - TRANE
Alarms
-
Alarms
-
What Was The Alarm Type
-
Was The Chiller Able To Be Returned To Normal Operation
-
Was Alarm Cleared / Reset
-
Did Another Chiller Turn On
-
Can You Start Another Unit
-
Did You follow The After Hours Incident Chart
Operation Status
-
Status
-
Outside Air Temperature
Compressor
-
Compressor Run Time
-
Compressor Starts
Oil Tank Temperature
-
Oil Pump Discharge Pressure
-
Oil Tank Pressure
-
Contact Foreman
Evaporator Page
-
Active Chilled Water Setpoint
Evaporator Leaving Water Temperature
Evaporator Entering Water Temperature
-
Evap Rfgt Pressure
-
Contact Foreman
Evaporator approach temperature
Condenser Page
-
Condenser Entering Water Temperature
Condenser Leaving Water Temperature
-
Condenser Refrigerant Pressure
-
Contact Foreman
Condenser approach temp
Motor Page
-
Active Current Limit Set Point
-
Contact Foreman
-
Average Motor Current Percent % RLA
Purge Page
-
Purge - Pump Out Life
Physical Gauge on Pipe
-
Chilled water Supply Pressure
-
Chilled water Return Pressure
-
Condenser Supply Pressure
-
Condenser Return Pressure
Side of Chiller Near Oil Filter
-
Oil Level
Chiller #4 SMARDT
-
Alarms
-
What Was The Alarm Type
-
Was The Chiller Able To Be Returned To Normal Operation
-
Was Alarm Cleared / Reset
-
Did Another Chiller Turn On
-
Can You Start Another Unit
-
Did You follow The After Hours Incident Chart
Outside Air Temperature
-
Status
Main Page
-
Must be in "External Start"
Common Loop Chilled Water Temperature
-
Entering Chilled Water
Leaving Chilled Water
Chilled Water Set Point
-
Percent System Demand
-
Total Input KWs
-
Percent Full Load AMPs
-
Common Loop Condenser Water Temperature
Entering Condenser Water Temperature
Leaving Condenser Water Temperature
Compressor #1
-
Status
-
Alarms
-
Active Fault
-
Demand %
-
Interlock
-
Speed (RPM)
-
IGV % Open
-
Suction Press
Suction Temperature
-
Discharge Press
Discharge Temperature
-
Power Input
-
Desired Power
-
3 ph Amps
-
Pressure Ratio
-
Surge RPM
-
Choke RPM
Compressor #2
-
Status
-
Alarms
-
Active Fault
-
Demand %
-
Interlock
-
Speed (RPM)
-
IGV % Open
-
Suction Press
Suction Temperature
-
Discharge Press
Discharge Temperature
-
Power Input
-
Desired Power
-
3 ph Amps
-
Pressure Ratio
-
Surge RPM
-
Choke RPM
Penthouse
Penthouse
RO Water
Water Sofener
-
Salt Tank
-
UNITY Water Sofener Pressure Gauge
RO - 1 Pump Control Board
-
Alarm
-
System Start Selector
-
Run Time Counter
-
Place Hold for Cole When This Section Was Added Hr * 0039276
-
Tank Level
-
Are Any Lights On
- RO Pump
- Flushing
- Pretreatment
- Low Pressure
- High Pressure
- No Lights ON
RO Membrane Board
-
PPM - Parts Per Million
-
READ SITE GLASS FROM THE TOP OF THE METAL FLOAT
-
RO - GPM
-
Reject Rate
-
Recirculate
-
Membrane feed
-
Reject From Membrane
-
Pump Discharge
-
BLUE FILTER UNDER SIGHT GLASS
-
THERE SHOULD NOT BE A DELTA OF MORE THAN 5 PSI BETWEEN IN AND OUT
-
PSI Blue Filter Canister IN
-
PSI Blue Filter Canister Out
DI Water Station
-
Circulating Pump #7
-
Circulating Pump #8
-
Return DI Water Sight Glass (West Wall)
-
Return DI Water GPM
RO - DI - RO Humidifier Control Board
-
-
Located next to rooftop doors
DI Pump Selection
-
Only 1 DI Pump Needs to be ON
-
DI Pump #7
-
DI Pump #8
RO Pump Selection
-
Only 1 RO Pump Needs to be ON For Humidification
-
RO Pump B-1 Humidifier RO
-
RO Pump B-2 Humidifier RO
-
MYRON L COMPANY - SERIES 750 TESTER
-
Press & Hold The ( SET Point Check) Button for 3 seconds and Release
-
DI Water Millisiemens / CM
-
Did A Set Point Light Turn ON
Aerco Domestic Hot Water Heat Exchanger
-
Status
Set Point Temperature
Supply Temperature
Rooftop
Rooftop
Exhaust Fans
Exhaust fan #15
-
Status
Exhaust Fan #16
-
Status
Exhaust fan #6 - Bathroom Fan
-
Status
Roof Exhaust Fan #1
-
Status
Roof Exhaust Fan #2
-
Status
Roof Exhaust Fan #3
-
Status
Roof Exhaust Fan #4
-
Status
Exhaust Fan 17
-
Status
Air Handler
AHU - Air Handling Unit #1
-
Status
-
Alarm
-
Time of Alarm
-
Cause of Alarm
-
Was Unit Able to Be Returend to Normal Operation
-
Call Controls or Foreman
AHU - Air Handling Unit #2
-
Status
-
Alarm
-
Time of Alarm
-
Cause of Alarm
-
Was Unit Able to Be Returend to Normal Operation
-
Call Controls or Foreman
AHU - Air Handling Unit #3
-
Status
-
Alarm
-
Time of Alarm
-
Cause of Alarm
-
Was Unit Able to Be Returend to Normal Operation
-
Call Controls or Foreman
AHU - Air Handling Unit #4
-
Status
-
Alarm
-
Time of Alarm
-
Cause of Alarm
-
Was Unit Able to Be Returend to Normal Operation
-
Call Controls or Foreman
Heat Recovery Room
Heat Recovery Pump
-
HR Glycol Tank Level
-
Pump #1 Status
Temperature
-
HOA Switch
-
Pump #2 Status
Temperature
-
HOA Switch