CQU Transformer Assets - Inspection
-
Is this a CQU Kiosk-style HV/LV Transformer Asset?
Transformer Safety
-
Insulation material (SF6, oil) levels OK?
-
Transformer free of oil leaks?
-
Are all panels secure, with no damage, no bolts or screws loose?
-
Is the paintwork in good condition, with no surface rust or paint bubbles?
-
Thermal-image the transformer. Is there evidence of major heat spots?
-
Evidence of damage to the transformer?
Electrical Safety
-
HV ONLY - Main earth cables minimum 35mm in diamater?
-
LV ONLY - Main earth cables minimum 25mm in diamater?
-
HV Protection hardware in good condition - no visible damage? (Visual check)
-
LV Protection hardware in good condition - no visible damage? (Visual check)
-
No access available to live components of any voltage?
-
Are all metallic parts and guard of the transformer bonded to earth?
-
Transformer and earthing corrosion free, rust free?
-
Is there sufficient labelling warning of electrical risks? (i.e. "DANGER - 415 VOLTS AC")
General Safety
-
Is there a clear >600mm access zone around the transformer (including distance of any open panels)?
-
As per AS/NZS 2067, there are minimum safety requirementsto ensure a safe area is maintained for both electrical operation & electrical workers.
-
Look for adequate clearance to walls, vents. Are the cooling fins clean of dust, dirt, flora or fauna?
-
Is there adequate ventilation & airflow around the generator cooling fins?
-
Egress paths from all accessible sides of the transformer safe, unobstructed?
Misc
-
Are there any further issues with the board that need rectification (i.e. Lighting, ventilation, messy areas)?
-
Is this a CQU Switchroom-located HV/LV Transformer Asset?
Transformer Safety
-
Insulation material (SF6, oil) levels OK?
-
Transformer free of oil leaks?
-
Are all panels secure, with no damage, no bolts or screws loose?
-
Is the paintwork in good condition, with no surface rust or paint bubbles?
-
Thermal-image the transformer. Is there evidence of major heat spots?
-
Evidence of damage to the transformer?
Electrical Safety
-
HV ONLY - Main earth cables minimum 35mm in diamater?
-
LV ONLY - Main earth cables minimum 25mm in diamater?
-
HV Protection hardware in good condition - no visible damage? (Visual check)
-
LV Protection hardware in good condition - no visible damage? (Visual check)
-
No access available to live components of any voltage?
-
Are all metallic parts and guard of the transformer bonded to earth?
-
Transformer and earthing corrosion free, rust free?
-
Is there sufficient labelling warning of electrical risks? (i.e. "DANGER - 415 VOLTS AC")
General Safety
-
Is there a clear >600mm access zone around the transformer (including distance of any open panels)?
-
As per AS/NZS 2067, there are minimum safety requirementsto ensure a safe area is maintained for both electrical operation & electrical workers.
-
Is there adequate ventilation & airflow around the generator cooling fins?
-
Look for adequate clearance to walls, vents. Are the cooling fins clean of dust, dirt, flora or fauna?
-
Egress paths from all accessible sides of the transformer safe, unobstructed?
Misc
-
Are there any further issues with the board that need rectification (i.e. Lighting, ventilation, messy areas)?
Ergon Transformer Assets - Inspection
-
Is this an Ergon Switchroom-style HV/LV Transformer Asset?
Transformer Safety
-
Insulation material (SF6, oil) levels OK?
-
Are all panels secure, with no damage, no bolts or screws loose?
-
Is the paintwork in good condition, with no surface rust or paint bubbles?
-
Is the transformer name plate readable?
-
Thermal-image the transformer. Is there evidence of major heat spots?
-
Evidence of damage to the transformer?
Electrical Safety
-
HV ONLY - Main earth cables minimum 35mm in diamater?
-
LV ONLY - Main earth cables minimum 25mm in diamater?
-
HV Protection hardware in good condition - no visible damage? (Visual check)
-
LV Protection hardware in good condition - no visible damage? (Visual check)
-
No access available to live components of any voltage?
-
Are all metallic parts and guard of the transformer bonded to earth?
-
Transformer and earthing corrosion free, rust free?
-
Is there sufficient labelling warning of electrical risks? (i.e. "DANGER - 415 VOLTS AC")
General Safety
-
Is there a clear >600mm access zone around the transformer (including distance of any open panels)?
-
As per AS/NZS 2067, there are minimum safety requirementsto ensure a safe area is maintained for both electrical operation & electrical workers.
-
Is there adequate ventilation & airflow around the generator cooling fins?
-
Look for adequate clearance to walls, vents. Are the cooling fins clean of dust, dirt, flora or fauna?
-
Egress paths from all accessible sides of the transformer safe, unobstructed?
Misc
-
Are there any further issues with the board that need rectification (i.e. Lighting, ventilation, messy areas)?
-
Is this an Ergon Kiosk-style HV/LV Transformer Asset?
Transformer Safety
-
Insulation material (SF6, oil) levels OK?
-
Are all panels secure, with no damage, no bolts or screws loose?
-
Is the paintwork in good condition, with no surface rust or paint bubbles?
-
Evidence of damage to the transformer?
Electrical Safety
-
When was the last inspection by Ergon?
-
Enter the last inspection date:
-
No access available to live components of any voltage?
-
Are all metallic parts and guard of the transformer bonded to earth?
-
Transformer and earthing corrosion free, rust free?
-
Is there sufficient labelling warning of electrical risks? (i.e. "DANGER - 415 VOLTS AC")
General Safety
-
Is there a clear >600mm access zone around the transformer (including distance of any open panels)?
-
As per AS/NZS 2067, there are minimum safety requirementsto ensure a safe area is maintained for both electrical operation & electrical workers.
-
Is there adequate ventilation & airflow around the generator cooling fins?
-
Look for adequate clearance to walls, vents. Are the cooling fins clean of dust, dirt, flora or fauna?
-
Egress paths from all accessible sides of the transformer safe, unobstructed?
Misc
-
Are there any further issues with the board that need rectification (i.e. Lighting, ventilation, messy areas)?
Protection Details
HV Protection Details (if available)
-
HV Feed Description:
-
HV Protection Location:
-
HV Protection Type:
-
HV Protection Make & Model:
-
HV Protection Size:
-
Add other HV Protection parameters here:
LV Protection Details (if available)
-
LV Protection Location:
-
LV Protection Type:
-
LV Protection Make & Model:
-
LV Protection Size:
-
Add other LV Protection parameters here:
Transformer Performance
Transformer Information
-
Transformer Size (kVA):
-
Transformer Make & Model
-
Transformer Serial Number:
-
Transformer Tap:
-
Transformer Impedance (ohms):
-
Transformer Rated Primary Voltage:
-
Transformer Rated Secondary Voltage:
-
Transformer Rated Primary Current:
-
Transformer Rated Secondary Current:
-
Add any extra useful information here:
Electrical Parameters - HV (primary) Side
-
A Phase Voltage:
-
B Phase Voltage:
-
C Phase Voltage:
-
A Phase Amps:
-
B Phase Amps:
-
C Phase Amps:
-
Power Factor:
Electrical Parameters - LV (seconday) Side
-
A Phase Voltage:
-
B Phase Voltage:
-
C Phase Voltage:
-
A Phase Amps:
-
B Phase Amps:
-
C Phase Amps:
-
Power Factor:
Drawings
Drawing Set
-
Is there a set of drawings present in this location?
-
Are there red-line markups present?
-
Add photos of redline markups present.
-
Add a comment about the redline markups present
-
Do redlines in DFM and field match?
Finalise Audit
Finalise Audit
-
Are there any Danger, Isolation, Hazard or Information tags in the switchboard?
-
If yes, please ensure you take photos of each tag (both sides).
-
Are there any other issues that should be noted?
-
Ensure that this report is emailed to #######@cqu.edu.au for actioning of any outstanding items.
Sign off by auditor.
-
Transformer checked by:
-
Signature: