Title Page

  • Document No.

  • Audit Title

  • Client / Site

  • Conducted on

  • Prepared by

  • Location
  • Personnel

AS/NZS 2067 Requirements

AS/NZS 2067-2008 Requirements

  • As per AS/NZS 2067, there are minimum safety requirements in a switchroom to ensure a safe area is maintained for both electrical operation & electrical workers.

Electrical

  • Thermal-image the switchboard. Is there evidence of major heat spots?

  • No access available to live components of any voltage?

  • Is there adequate ventilation for battery or UPS compartments?

Earthing

  • HV ONLY - Earth cables minimum 35mm in diamater?

  • LV ONLY - Earth cables minimum 25mm in diamater?

  • Earthing system has at least 2 connected earth stakes?

  • Are all metallic parts in the switchroom bonded to earth?

  • All metallic exposure guards earthed?

Housekeeping & Safety

  • Is there sufficient labelling warning of electrical risks? (i.e. "DANGER - HIGH VOLTAGE AUTHORISED PERSONS ONLY"

  • Evidence of water ingress to the room?

  • Is there evidence of oil spills, fires or smoke in the switchroom?

  • Is there evidence of any damage to doors, windows, walls or ceiling?

  • HV ONLY: Switchroom doors have crash bars fitted and operational?

  • Doors lock securely to prevent unauthorized access, open outwards?

  • Egress paths from the switchroom are safe, unobstructed?

  • Fire extinguisher is of type B(E) or AB(E) and is in date?

  • Has the 24-hour switchroom temperature average exceeded 35 Degrees Celsius?

  • Are fire-rated walls identified and labelled "FIRE RATED WALL DO NOT PENETRATE"?

  • Is there LVR rescue kit in the room, is it correctly sign-posted, and are components in date?

Misc

  • Are there any further issues in the switchroom that need rectification (i.e. Lighting, ventilation, messy areas)?

National Construction Code Requirements

National Construction Code Requirements

  • As stipulated in AS/NZS 2067 Section 5.5, electrical switchrooms shall comply with the requirements of the Building Council of Australia's National Construction Code (NCC). BCA Class 8 buildings are used as a guide.

  • Do all egress paths have battery-backed exit lighting?

  • Is there sufficient emergency lighting in the switchroom?

  • Is there an exit within 20m of all points in the room?

  • Is the external area to the escape door free from blockages (i.e. vehicles, gardens, etc) within 1 metre, either existing or potential?

AS/NZS 3000 Requirements

AS/NZS 3000 Requirements

  • As per AS/NZS 3000, there are minimum safety requirements in a switchroom to ensure a safe area is maintained for both electrical operation & electrical workers.

General Safety

  • Is there minimum 600mm clearance between the all electrical (open) panels and other obstructions (such as other panels, walls, fences, pits)?

  • Is there a secondary egress path for boards with capacity over 800A, length >3m or fault current of >15kA?

  • Is the board in a location where smoke or fire could impact egress from a building?

  • Are the seals around the switchboard suitable to contain smoke and fire in the event of a failure (minimum IP5X)?

  • Switchboard is not in a hazardous area?

  • Fire panel operational and fault-free?

Electrical

  • Is the MEN point correctly marked and secure?

  • Earths identified & correctly labelled?

  • Are all isolation points clearly marked?

  • Have all RCD circuit breakers tested within the last 12 months?

  • Are all gap fillers installed securely, with no outstanding gaps?

  • Are safety services (lifts, fire, etc) separated from general power distribution?

  • As per section 7.2, it is critical that safety services are not at risk of isolation due to fault in another part of the electrical system.

  • Are dual feeds correctly labelled?

  • Have all instances of nuisance tripping (since last audit) been investigated and rectified (where necessary)?

  • Is there suitable segregation between circuits in cable tray/conduit?

  • Are cable trays secure, no rust/degradation and earthed at all non-bolted joints?

General Power

  • Are all GPO's protected by an RCD?

  • Are GPO's clean and dry?

  • Are GPO's free from damage (no cracking, switches operational)?

General Lighting

  • Is lighting sufficient in the switchroom?

  • 160lux or greater is recommended for general electrical tasks.
    400lux or greater is recommended for electrical maintenance work, and can be achieved by task lighting.

  • Are all light fittings operational (i.e. no blown bulbs or elements)?

  • Are light fixtures secure from damage?

  • Is emergency lighting in the switchroom sufficient?

  • It is recommended that an emergency lighting level of >1lux is present. This can be achieved by using battery-backed fluoro or LED tubes, spitfires or similar fixtures.

  • Are lighting fixtures suitably earthed?

Electrical Parameters

  • Red-Earth Voltage:

  • Blue-Earth Voltage:

  • White-Earth Voltage:

  • Neutral-Earth Voltage:

  • Power Factor:

  • Blue Phase Current:

  • Red Phase Current:

  • White Phase Current:

  • Is the earth system in tact (no damage)?

  • Earth resistance?

Miscellaneous

  • Are there any other issues that need raising?

Drawings

Switchroom Drawing Set

  • Is there a folder of drawings present in the switchroom?

  • Are there red-line markups present in the switchroom drawing set?

  • Add photos of redline markups present.

  • Add a comment about the redline markups present

  • Are there red-line markups present in the DFM drawing set?

  • Add photos of redline markups present.

  • Add a comment about the redline markups present

  • Do redlines in DFM and field match?

Finalise Audit

Finalise Audit

  • Are there any Danger, Isolation, Hazard or Information tags in the switchroom?

  • If yes, please ensure you take photos of each tag (both sides).

  • Are there any other issues in the Switchroom that should be noted?

  • Ensure that this report is emailed to #######@cqu.edu.au for actioning of any outstanding items.

Sign off by auditor.

  • Switchroom checked by:

  • Signature:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.