Information
-
Document No.
-
Client / Site
-
Conducted on
-
Night /Day
- Night
- Day
-
Prepared by
-
Personnel present
-
Location
ITEM 1
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 2
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 3
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 4
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 5
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 6
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 7
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 8
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 9
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 10
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 11
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 12
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 13
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 14
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 15
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 16
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 17
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 18
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 19
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 20
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 21
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 22
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 23
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 24
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments
ITEM 25
-
Approximate co ordinates
-
Station and location of plant being inspected
-
Photo of plant being inspected
-
Are the luminaries functional at the time of the inspection
- yes they are functional
- no they are not functional
- they are intermittent
-
Type of pole being inspected
- 10m pole
- 8.5m pole
- 13m pole
- SBM POLE
- BPM POLE
- JU POLE
- JU MAST ARM
- BIG POLE
- single 3m O/R
- single 4.5m O/R
- double 3m O/R
- double 4.5m O/R
-
Physical arrangement
- behind guard rail/barrier
- on verge
-
Physical condition of pole
- deformation of pole greater than 20% of diameter
- cut in pole greater than 20% of the circumference
- pole contains terminal panel and isolator as per current standards
- pole contains suitable mounting straps
- the pole contains slip base pins
- the base contains slip base pins
- 3 pin plug
- fuses mounted on cable tray or similar
-
Does pole require modifications
-
Internal photos of pole and any external damage
-
Type and Physical condition of pit
- type 4 pit
- type 7 pit
- type 60 pit
- pit buried
- unable to locate pit
- pit lid needs replacing
- there is evidence of vermin activity
- conduits have required 600mm cover
- pit has more than 5%. deformity
- pit will not accommodate a large j bell
- pit is unworkable
-
Does the pit and conduits require flushing/clearing
-
It the earthing as per current standards
-
Photo of pit
-
Comments