Title Page
-
Site conducted
-
Conducted on
-
Prepared by
-
Location
-
Operative being assessed
Tools and equipment
-
Bag stop drilling machines/bases
-
Drilling base drills
-
Metallic vent stacks, flame traps and earthing straps
-
DI/CI pipe cutters & steel cutters
-
Continuity bond
-
Expanding pipe stoppers
-
Foam off kits (including spares)
-
Pressure gauges
General requirements
-
Prior to commencing any work ensure that the following documentation is available and
authorised where appropriate.
1. Job instructions
2. Routine / Non-Routine operation procedures
3. Permit to work
Foam plug preparatory work – General:
-
Confirm the mains pressure by drilling and tapping the main and installing a pressure point.
-
Inform the Operational Manger if the pressure is above 75mbar.
-
Confirm with the Operational Manger the direction of flow as detailed in the written procedures.
-
Confirm size of riders to be installed across the section to be cut out as detailed in the written<br>procedure.
-
Confirm with the Operational Manger that the main is one-way fed.
-
The upstream side of the operation is the where the gas has come from, whilst the downstream<br>side is where the gas is going.
-
Manufactures instructions on the storage of the foam kits must be adhered to.
Preparatory work – Mains preparation work
-
A position on the main must be selected where there is no large corrosion defects or hard <br>encrustations and the main cleaned by scraping and wire brushing. If necessary, wash the main <br>with clean water to ensure secure seal at machine saddle. For ductile mains ensure that the<br>plastic wrapping is removed. Ensure that the plastic coating is removed when encountered on <br>steel mains.
-
The underside of the main must be excavated at points for access to the drilling machines and <br>where the cut is going to be undertaken. Ensure the underside of the main is supported<br>throughout the operation; wood blocks should be used to support it. Ensure sufficient room is <br>made to operate the cutters to achieve a full circumferential cut.<br>
-
A machine saddle and seal must be selected according to the main size, its condition checked, and <br>fitted to the machine or main as appropriate. The fixing chain nuts should be tightened evenly to<br>a moderate hand torque while ensuring that the machine is level.
-
The drill tap must be inspected and lubricated with oil or grease.
-
A parallel threaded drill tap must be fitted to the chuck and inserted in the machine.
-
An air test at a pressure of 350 mbar must be applied with the gate valve in the OPEN position and <br>the machine seal checked with an approved leak detection fluid solution. No leakage must be<br>visible during the test duration of 5 minutes.
-
If leakage is observed the machine must be inspected for the leakage path if the seal cannot be <br>achieved without tightening the fixing chains beyond a moderate hand torque the base must be <br>removed and the main cleaned further, or the equipment exchanged.
-
The pressure gauge used for this test must be left connected and monitored whilst the main is <br>being drilled. The pressure gauge used must be suitable to operate within the pressure regime of <br>the main.
-
Drill and tap the main in preparation for the installation of the foam bags using an approved under<br>pressure-drilling machine and the tapping hole sizes as detailed in Table 37, (SGN/WI/ML/2)
-
Drill the main using a hand ratchet or air motor. Preferably the main should be tapped using a<br>hand ratchet. If excessive force is needed this should be investigated. The drill tap should be <br>withdrawn and for single spindle machines, the valve closed. The coupon should be retained for <br>inspection.
-
This process must be repeated at each of the drillings to be made.
-
Complete all drillings.
-
Ensure an electrical continuity bond is installed across the full section of the main to be isolated <br>and cut out.
-
Note: (Minimum dimensions from foam plugs)
Dimension between foam plug 1 and bypass point V1 = 800mm
Dimension between foam plug 1 and vent point V3 = 300mm
Dimension between foam plug 2 and bypass point V8 = 800mm
Dimension between foam plug 2 and vent point V5 = 300mm
The distance of 800mm allows for an additional foam plug to be installed if the first one fails.
Equipment set-up
-
Metallic vent stacks with flame traps must be installed, all protruding above the top of the<br>excavation by a minimum of 2.5m. All valves must be in the closed position and the vent stacks <br>must be adequately supported.
-
The foam bag must be loaded into the foam bag injection standpipe, following manufacturer’s<br>instructions.
-
Once the foam bag has been inserted into the injection standpipe, the assembly must be inserted <br>in to main via the drilling machine base, ensuring that the non-return valve in the neck of the foam<br>bag prevents gas escaping through the injection tube.
-
Should gas start to pass through the injection tube the procedure must be stopped immediately,<br>the injection tube withdrawn, and the under-pressure valve closed off.
-
The faulty tube must be inspected for damage and replaced. The procedure from b. above must <br>then be repeated.
-
Fit cartridge to gun and attach to installed foam plug tube.
Assemble and Commission bypass:
-
The bypass must be protected from any risk from vandalism or mechanical damage and this must <br>include the burying or sleeving of PE materials, using a flexible steel bypass or using all welded <br>steel for constructing the bypass.
-
A PE bypass must not be left unattended overnight.
- Yes
- No
- N/A
-
The bypass should be fabricated with a minimum number of joints and maximum of six bends.
- Yes
- No
- N/A
-
Prior to installing around the main, the bypass must be pressure tested to 350mbar for 15 <br>minutes. No pressure loss is allowed. On successful completion of this test the bypass can now be <br>installed.
-
Ensure that the pressure gauges or recorders P1 and P4 are working and fitted correctly, showing<br>current pressure in the main
-
Ensure all valves on the bypass and vents are closed.
-
Open the vent valve V6 and valve V7 on the downstream side of the bypass.
-
Slowly open the valve V1 on the upstream side of the bypass and allow gas to vent out of the <br>bypass at the downstream vent position V6.
-
Confirm Two consecutive reading of greater than 90% G.I.A. from the vent and close the<br>downstream vent valve V6 and valve V7.
-
Close the upstream bypass valve, V1, open the downstream bypass vent, V8 and open the <br>upstream vent valve V4 and valve V2.
-
Confirm Two consecutive readings of greater than 90% G.I.A. from the vent and close the <br>upstream vent valve V4 and valve V2.
-
Re-open the upstream rider valve, V1.
-
The bypass is now commissioned.
Foam plug main
-
Mix the resin and hardener according to the manufacturer’s instructions and pour the contents<br>into the cartridge gun and dispense the foam into the bag number 1.
-
Mains pressures at P1 and P4 must be monitored to ensure that there is no drop-in pressure.
-
Repeat the process for bag position number 2.
-
The surplus foam left within the mixing container must be monitored to confirm the foam in the <br>bag has cured.
-
Once the foam has cured the vent stack valves V3 & V4 on the upstream and V5 & V6 on the <br>downstream can be opened to ensure an adequate seal. This can be confirmed by attaching a <br>pressure gauge P2 & P3 onto the vent stacks below the vent valve position, closing the vent valves<br>V4 & V6 and checking for let by through the foam bag.
-
Should a foam bag fail to seal a second stopping off operation using an additional foam bag via an <br>additional tapping must be carried out before continuing with the operation.
-
<br>
Cutting operation
-
Verify that there is no back feed into the section to be abandoned or consumers still connected to <br>the main by first closing off the downstream valve, V8 on the bypass. Pressure gauge, P4 on the <br>main to be abandoned must be observed and checked for signs that the pressure within the main <br>is falling.<br>
-
Should the pressure within the main to be abandoned start to fall the bypass must be re-opened<br>and the Operational Manager informed before the cause of the pressure drop is investigated.
-
Should the pressure remain constant the pressure in the main to be abandoned must be reduced<br>by 5mbar by venting the gas through the vent valves V9 and V10. The pressure in the main must <br>be allowed to stabilise and the pressure gauge on the main to be abandoned observed for a rise in <br>pressure.
-
Should the pressure start to rise the Operational Manager must be informed immediately and the<br>cause of the back feed investigated.
-
Only once the Operational Manager is satisfied that the abandonment is safe to continue the<br>operative can proceed as below.
-
Ensure that the section of main to be cut is accurately marked.
-
The method of cutting will be determined by the material and diameter of the main and detailed <br>in the work documentation.
-
Ensure the underside of the main is supported throughout the operation; wood blocks should be <br>used to support it. Ensure sufficient room is available to operate the cutters to achieve a full<br>circumferential cut.
-
Whilst cutting the main avoid unnecessary vibration that may cause the foam bags to pass.
-
Additional cuts should be made to ensure that the section of pipe is removed with the minimum<br>of effort.
-
The open ends of the pipe must be fitted with expanding stoppers if the main is not to be capped<br>immediately after cutting.
-
If an expanding stopper has been installed, remove the stopper and install the cap onto the end of <br>the main.
-
Anchorage of the cap must be carried out as per (SGN/PR/DIS/4.2.2)
Test end caps
-
The end caps must now be tested for gas tightness as detailed below:<br>Using the vent arrangement as shown, allow gas to pass to the other side of the foam bag and cap <br>ends, by opening valves V2 & V3 on the upstream side and valves V5 & V7 on the downstream<br>side ensuring that valves V4 & V6 are closed, so that live gas is now acting against the newly<br>installed cap ends
-
Test the cap ends for soundness with leak detection fluid
-
Should the cap(s) show leakage, Valve V2 and/or V7 must be closed, the section between the cap<br>and foam bag vented by opening valve V4 and/or V6, and the cap re-tightened.
-
Close valves V4 and/or V6 and open valves V2 and/or V7 and retest the cap end(s) for soundness <br>with leak detection fluid.
-
Remove the foam injection tubes and test with leak detection fluid.
-
Once caps and plugs have been deemed satisfactory close valves V2 and V7 and open valves V4<br>and V6 to vent between the cap ends. Close valves V3 and V5.
Removal of equipment
-
Close bypass valves V1 and V8.
-
Vent the bypass to zero pressure by opening valves V2 & V7 Disconnect V2 and attach an air <br>supply and direct purge the bypass with air at no more than 1/3<br>rd. of the main operating pressure.
-
Dismantle the bypass and using the drilling machine plug off under no gas conditions the<br>connection points for the bypass and vents.
-
Remove the pressure gauges as per c. above and check the plugged off holes with leak detection<br>solution.
-
Remove the continuity bond.
-
The applicator, foam cartridge and containers must be disposed of according to the manufacturer’<br>instructions, COSHH and as per Risk Assessment.
-
To ensure that the plugs screwed into the foam bag injection points are not leaking, leak detection<br>fluid must be applied to them at least 24 hours after the foam off operation.
-
Should the plugs show leakage the plugs must be tightened and tested with leak detection fluid.
Sign off
-
Name of assessor
-
Pass or refer for further training