Part 1 - To Be Completed By The Requester:
-
Description of circuit/equipment/job location:
-
Description of work to be done:
-
Justification of why the circuit/equipment cannot be de-energized. (Greater Hazard/Infeasible).
-
Requester and Title
-
Select date
Part II - To Be Completed By The Electrically Qualified Persons Doing The Work:
-
Detailed job description procedure to be used in performing the above detailed work:
-
Description of the safe work practices to be used:
-
SHOCK HAZARD ANALYSIS (for Alternate-Current Systems)
-
Approach Boundaries - What voltage range are you working with?
- <50 V
- 50V-300V
- 301V-750V
- 751V-15kV
- 15.1kV-36kV
- 36.1kV-46kV
- 46.1kV-72.5kV
- 72.6kV-121kV
- 138kV-145kV
- 161kV-169kV
- 230kV-242kV
- 345kV-362kV
- 345kV-362kV
- 500kV-550kV
- 765kV-800kV
-
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach - Not Specified
Restricted Approach - Not Specified
Restricted Approach - Not Specified -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary.
Limited Approach Boundary = 10 feet for movable conductor or 3' 6" for fixed circuit part
Restricted Approach Boundary = Avoid Contact
Prohibited Approach Boundary = Avoid Contact -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 10 feet for movable conductor or 3' 6" for fixed circuit part
Restricted Approach Boundary = 1'0"
Prohibited Approach Boundary = 0'1" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 10 feet for movable conductor or 5'0" for fixed circuit part
Restricted Approach Boundary = 2'2"
Prohibited Approach Boundary = 0'7" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 10 feet for movable conductor or 6'0" for fixed circuit part
Restricted Approach Boundary = 2'7"
Prohibited Approach Boundary = 0'10" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 10 feet for movable conductor or 8'0" for fixed circuit part
Restricted Approach Boundary = 2'9"
Prohibited Approach Boundary = 1'5" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 10 feet for movable conductor or 8'0" for fixed circuit part
Restricted Approach Boundary = 3'3"
Prohibited Approach Boundary = 2'2" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 10'8" for movable conductor or 8'0" for fixed circuit part
Restricted Approach Boundary = 3'4"
Prohibited Approach Boundary = 2'9" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 11'0" for movable conductor or 10'0" for fixed circuit part
Restricted Approach Boundary = 3'10"
Prohibited Approach Boundary = 3'4" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 11'8" for movable conductor or 11'8" for fixed circuit part
Restricted Approach Boundary = 4'3"
Prohibited Approach Boundary = 3'9" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 13'0" for movable conductor or 13'0" for fixed circuit part
Restricted Approach Boundary = 5'8"
Prohibited Approach Boundary = 5'2" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 15'4" for movable conductor or 15'4" for fixed circuit part
Restricted Approach Boundary = 9'2"
Prohibited Approach Boundary = 8'8" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 19'0"for movable conductor or 19'0" for fixed circuit part
Restricted Approach Boundary = 11' 10"
Prohibited Approach Boundary = 11' 4" -
Where one or more unqualified persons are working at or close to the Limited Approach Boundary, the designated person in charge of the work space where the electrical hazard exists shall advise the unqualified person(s) of the electrical hazard and warn him or her to stay outside of the Limited Approach Boundary
Limited Approach Boundary = 23'9" for movable conductor or 23'9" for fixed circuit part
Restricted Approach Boundary = 15'11"
Prohibited Approach Boundary = 15"5" -
HAZARD/RISK CLASSIFICATION
-
Tasks Performed on Energized Equipment