Title Page
-
Document No.
-
Environment of Care - Maintenance
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Personnel
1.0 Previous Inspection
-
Has the last Inspection been reviewed?
-
No outstanding work orders?
2.0 fire Prevention
-
Alcohol Based Hand Rub (ABHR) containers in proper location? One inch to the right, left and below ignition source. NFPA 101:19.3.2.6.
-
Fire extinguisher signs six feet off floor?
-
Is fire extinguisher four inches off floor and 60 inches to top of extinguisher? NFPA (2010) 6.1.3.8
-
Are "K" extinguishers properly labeled? NFPA (2010) 5.5.5
-
A restraining device is correctly installed on caster equipped natural gas appliances? NFPA 54 (2012) 9.6.1.2/ANSI Z223.1
-
Exit doors open easily?
-
Miscellaneous
3.0 General Lighting
-
Lights working and in good condition?
-
Light lens cover in place and not damaged?
-
Egress lights working?
-
Exit lights working?
-
Miscellaneous
4.0 Building Maintenance
-
Base cove not loose,damaged or missing?
-
Hand rails not damaged or missing parts?
-
No visible wall damage?
-
Doors not damaged or missing parts?
-
Door locks and handles working correctly?
-
Doors not held open by devices other than those that release when the door is pushed or pulled? NFPA 101 (2012) 18.3.6.3.10
-
Signage not damaged or missing?
-
Room description and ID number present? (AutoCad Department)
-
No water leaks?
-
Faucets shut-off completely, no drips?
-
Toilet does not leak and is properly sealed?
-
Plastic laminate in good condition?
-
Counter tops properly caulked?
-
Ceiling grid in good condition and intact?
-
Ceiling tile in good condition, not stained and not missing?
-
Wall paper not torn or with loose seams?
-
Cabinet hinges and pulls in working condition?
-
Room conditions comfortable?
-
Eye wash in correct position? 33-45 inches off floor and 6 inches from nearest obstruction. ANSI Z358.1
-
Sharps box at correct height? 50-56 inches off floor to opening.
-
Exhaust grills secure and clean?
-
Thermostat/ sensor in good condition?
-
Supply and return grills in place?
-
Refrigerator / freezer seals and doors in good condition?
-
Is room air flow correct?
-
Room air flow correct.
-
Are exterior door air curtains working and clean?
-
Are ice machines clean and serviced on time?
-
Nurse call cord 4 inches off floor but not more than 6 inches off floor? Is call cord cleanable?
-
Miscellaneous
5.0 General Housekeeping
-
Mechanical, electrical and communication rooms clean?
-
Oily rags and combustibles in covered or closed metal containers?
-
Miscellaneous
6.0 Mechanical Rooms
-
Are machine guards in place?
-
Drip pans in place and no spills?
-
Is lighting adequate?
-
Noise levels controlled?
-
Air ducts in good repair?
-
Are compressed gas bottles secured?
-
Miscellaneous?
7.0 Electrical Safety
-
No open "J" boxes?
-
Breaker box legends complete?
-
Flexible cords not run through ceiling tiles or doorways? NFPA 70 (2011) 400.8
-
Portable equipment tested and tagged?
-
No broken plugs, sockets or switches?
-
GFIC and tamper resistant receptacles installed?
-
No extension cords in use?
-
No exposed wiring?
-
Line Isolation Monitor (LIM) cabinets unlocked?
-
Electrical panels locked in public areas? NFPA 99(2012) 6.3.2.2.1.3
-
Power strips not used in patient care area. Special Purpose Relocatable Power Taps (UL 1363A or UL 60601-1) or Relocatable Power Taps (UL 1363) in use.
-
36 inch clearance around electrical equipment and controls? NFPA 70 (2011) 110.26
-
Miscellaneous?
8.0 Ladders
-
Are ladders industrial strength? Non-household rated, check label.
-
Are ladders in good condition?
-
Are ladders properly secured?
9.0 Medical Gas
-
Medical gas alarms and zone valves labeled?
-
Do gauges have indicators with the normal pressure in the middle third of the range? NFPA 99 (2012) 5.1.8.1.3
-
Are gauges working?
-
Oxygen storage room with over 300 cubic feet has appropriate sign "Caution: Oxidizing Gas(es) Stored Within. No Smoking". NFPA 99 (2012) 11.3.4.2
-
Oxygen storage room with over 300 cubic feet has electrical fixtures five feet off the floor, a lockable door, one hour rated room, and cylinders secured from falling. NFPA 99 (2012) 5.1.3.3.2
-
Miscellaneous