Information
-
Document No.
-
Location Name:
-
Business Unit Number:
-
Location
-
Telephone Number:
-
Fax Number:
-
General Manager:
-
Operations Manager:
-
Local Safety Officer:
-
Conducted on
-
Prepared by
-
Personnel
Facility Function:
-
Describe Site Use:
-
Is this facility shared with another company?
-
If shared, what is the name if the business?
-
What is the nature of this their business?
-
Does EMSC own or lease this facility?
-
How long has AMR been on site?
-
If leased, is a copy of the lease documented on site?
-
Lease renewal date?
Uninterrupted Power Supply / Generators
-
Does this site have a UPS?
-
Back-up battery system?<br>(If yes, see battery tab)
-
Does this site have a back up generator?
-
Generator fuel type:
-
Does generator require any local license or certificate?
Site Walk and General Housekeeping
-
1. Is the maintenance shop clean and tidy?
-
2. Are spills cleaned up promptly?
-
3. Is there an adequate supply of clean absorbent?
-
4. Is the Environmental policy posted on the wall in a general access area?
-
5. Are there any hazardous, regulated, or banned wastes in the garbage?
-
6. Is the facility fenced?
-
7. Are there scrap vehicle parts, tanks, drums, etc dumped on property?
-
8. Is litter controlled on property?
-
9. Are there any drains emptying into ditches surrounding the property?
-
10. Are the drains clear of rubbish and debris?
-
11. Are there signs of oil or petroleum discharge around drains?
-
12. Is there evidence of any of the following on site?
-
12.1 Oil Staining?
-
12.2 Stressed Vegetation?
-
12.3 Strong Odors?
-
13. Is the site under snow cover at time of site walk?
-
14. Are dumpsters closed or covered?
-
Action Required:
Underground Storage Tanks
-
Are underground storage tanks used at this site?
-
Tank 1:
-
Material of construction:
-
Tank is:
-
Capacity in Gallons:
-
Tank contents:
-
The tank contents are:
-
Does tank have Cathodic Protection?
-
Has Cathodic protection been tested in past 3 years?
-
Does tank have interstitial monitoring?<br>(Double wall only)
-
Is there a monitoring well? (Some states require ground well sensors)
-
Is there is a well, is there monitoring data?
-
Does tank have spill containment?
-
Does tank have overfill protection?
-
Pipe is:
-
Pipe construction material:
-
Pipe wall is:
-
Does pressurized pipe have leak detection?
-
Are daily inventory records okay?
-
Are monthly reconciliation okay?
-
Does tank have Auto Gauging?
-
Is dipstick in good condition?
-
Date tank was last tested:
-
Is tank tight? (Should be every year, required by law at least every 3 years)
-
Is a permit required for tank?
-
If yes, is tank permitted?
-
Is permit posted near tank?
-
Is tank in compliance?
-
Action Required:
-
Tank 2:
-
Material of construction:
-
Tank is:
-
Capacity in Gallons:
-
Tank contents:
-
The tank contents are:
-
Does tank have Cathodic Protection?
-
Has Cathodic protection been tested in past 3 years?
-
Does tank have interstitial monitoring?<br>(Double wall only)
-
Is there a monitoring well? (Some states require ground well sensors)
-
Is there is a well, is there monitoring data?
-
Does tank have spill containment?
-
Does tank have overfill protection?
-
Pipe is:
-
Pipe construction material:
-
Pipe wall is:
-
Does pressurized pipe have leak detection?
-
Are daily inventory records okay?
-
Are monthly reconciliation okay?
-
Does tank have Auto Gauging?
-
Is dipstick in good condition?
-
Date tank was last tested:
-
Is tank tight? (Should be every year, required by law at least every 3 years)
-
Is a permit required for tank?
-
If yes, is tank permitted?
-
Is permit posted near tank?
-
Is tank in compliance?
-
Is permit posted near tank?
-
Is tank in compliance?
-
Action Required:
-
Tank 3:
-
Material of construction:
-
Tank is:
-
Capacity in Gallons:
-
Tank contents:
-
The tank contents are:
-
Does tank have Cathodic Protection?
-
Has Cathodic protection been tested in past 3 years?
-
Does tank have interstitial monitoring?<br>(Double wall only)
-
Is there a monitoring well? (Some states require ground well sensors)
-
Is there is a well, is there monitoring data?
-
Does tank have spill containment?
-
Does tank have overfill protection?
-
Pipe is:
-
Pipe construction material:
-
Pipe wall is:
-
Does pressurized pipe have leak detection?
-
Are daily inventory records okay?
-
Are monthly reconciliation okay?
-
Does tank have Auto Gauging?
-
Is dipstick in good condition?
-
Date tank was last tested:
-
Is tank tight? (Should be every year, required by law at least every 3 years)
-
Is a permit required for tank?
-
If yes, is tank permitted?
-
Is permit posted near tank?
-
Is tank in compliance?
-
Is permit posted near tank?
-
Is tank in compliance?
-
Action Required:
-
Tank 4:
-
Material of construction:
-
Tank is:
-
Capacity in Gallons:
-
Tank contents:
-
The tank contents are:
-
Does tank have Cathodic Protection?
-
Has Cathodic protection been tested in past 3 years?
-
Does tank have interstitial monitoring?<br>(Double wall only)
-
Is there a monitoring well? (Some states require ground well sensors)
-
Is there is a well, is there monitoring data?
-
Does tank have spill containment?
-
Does tank have overfill protection?
-
Pipe is:
-
Pipe construction material:
-
Pipe wall is:
-
Does pressurized pipe have leak detection?
-
Are daily inventory records okay?
-
Are monthly reconciliation okay?
-
Does tank have Auto Gauging?
-
Is dipstick in good condition?
-
Date tank was last tested:
-
Is tank tight? (Should be every year, required by law at least every 3 years)
-
Is a permit required for tank?
-
If yes, is tank permitted?
-
Is permit posted near tank?
-
Is tank in compliance?
-
Is permit posted near tank?
-
Is tank in compliance?
-
Action Required:
-
Action Required:
Above Ground Storage Tanks:
-
Tank 1:
-
Tank capacity in gallons:
-
Tank contents:
-
Is tank labeled correctly?
-
Year of construction:
-
Location:
-
Tank configuration:
-
Cube:
-
Vertical
-
Horizontal
-
Drum:
-
Vertical
-
Horizontal
-
Is permit required for tank?
-
If yes, is tank permitted?
-
Is tank in compliance with local, state, and federal regulations as well as AMR Policy?
-
Is tank skid mounted?
-
Does tank have rain protection?
-
Is outdoor AST electrically grounded?
-
Does tank have automatic inventory controls?
-
Does tank have overfill protection at dispensing point?
-
Does tank have spill containment?
-
Is tank double wall construction?<br>(Is yes skip dike)
-
Is tank diked?
-
Dike floor construction:
-
Is dike drain closed?
-
Is dike empty?
-
Is there more than 1320 gallons of total Petro products stored in above ground tanks?<br>(If yes, need to comply with Sarah Tier II requirements)
-
If yes, is a spill Control & Countermeasure plan required? <br>(Only is petroleum exceeds 1320 gallons, and stored outdoors)
-
If SPCC plan required, is there a written plan in place?
-
Has plan been certified by management / signed by GM?
-
Certified by professional engineer?
-
Notification / Emergency contact list?
-
Inspection report on file?
-
Significant changes to SPCC plan?
-
Spill greater than 10 gallons within last year?
-
If plan has been implemented for more than 3 years, has the last review been done within the past 3 years?
-
Is the facility in compliance with the SPCC plan?
-
Action Required:
-
Tank 2:
-
Tank capacity in gallons:
-
Tank contents:
-
Is tank labeled correctly?
-
Year of construction:
-
Location:
-
Tank configuration:
-
Cube:
-
Vertical
-
Horizontal
-
Drum:
-
Vertical
-
Horizontal
-
Is permit required for tank?
-
If yes, is tank permitted?
-
Is tank in compliance with local, state, and federal regulations as well as AMR Policy?
-
Is tank skid mounted?
-
Does tank have rain protection?
-
Is outdoor AST electrically grounded?
-
Does tank have automatic inventory controls?
-
Does tank have overfill protection at dispensing point?
-
Does tank have spill containment?
-
Is tank double wall construction?<br>(Is yes skip dike)
-
Is tank diked?
-
Dike floor construction:
-
Is dike drain closed?
-
Is dike empty?
-
Is there more than 1320 gallons of total Petro products stored in above ground tanks?<br>(If yes, need to comply with Sarah Tier II requirements)
-
If yes, is a spill Control & Countermeasure plan required? <br>(Only is petroleum exceeds 1320 gallons, and stored outdoors)
-
If SPCC plan required, is there a written plan in place?
-
Has plan been certified by management / signed by GM?
-
Certified by professional engineer?
-
Notification / Emergency contact list?
-
Inspection report on file?
-
Significant changes to SPCC plan?
-
Spill greater than 10 gallons within last year?
-
If plan has been implemented for more than 3 years, has the last review been done within the past 3 years?
-
Is the facility in compliance with the SPCC plan?
-
Action Required:
-
Tank 3:
-
Tank capacity in gallons:
-
Tank contents:
-
Is tank labeled correctly?
-
Year of construction:
-
Location:
-
Tank configuration:
-
Cube:
-
Vertical
-
Horizontal
-
Drum:
-
Vertical
-
Horizontal
-
Is permit required for tank?
-
If yes, is tank permitted?
-
Is tank in compliance with local, state, and federal regulations as well as AMR Policy?
-
Is tank skid mounted?
-
Does tank have rain protection?
-
Is outdoor AST electrically grounded?
-
Does tank have automatic inventory controls?
-
Does tank have overfill protection at dispensing point?
-
Does tank have spill containment?
-
Is tank double wall construction?<br>(Is yes skip dike)
-
Is tank diked?
-
Dike floor construction:
-
Is dike drain closed?
-
Is dike empty?
-
Is there more than 1320 gallons of total Petro products stored in above ground tanks?<br>(If yes, need to comply with Sarah Tier II requirements)
-
If yes, is a spill Control & Countermeasure plan required? <br>(Only is petroleum exceeds 1320 gallons, and stored outdoors)
-
If SPCC plan required, is there a written plan in place?
-
Has plan been certified by management / signed by GM?
-
Certified by professional engineer?
-
Notification / Emergency contact list?
-
Inspection report on file?
-
Significant changes to SPCC plan?
-
Spill greater than 10 gallons within last year?
-
If plan has been implemented for more than 3 years, has the last review been done within the past 3 years?
-
Is the facility in compliance with the SPCC plan?
-
Action Required:
-
Tank 4:
-
Tank capacity in gallons:
-
Tank contents:
-
Is tank labeled correctly?
-
Year of construction:
-
Location:
-
Tank configuration:
-
Cube:
-
Vertical
-
Horizontal
-
Drum:
-
Vertical
-
Horizontal
-
Is permit required for tank?
-
If yes, is tank permitted?
-
Is tank in compliance with local, state, and federal regulations as well as AMR Policy?
-
Is tank skid mounted?
-
Does tank have rain protection?
-
Is outdoor AST electrically grounded?
-
Does tank have automatic inventory controls?
-
Does tank have overfill protection at dispensing point?
-
Does tank have spill containment?
-
Is tank double wall construction?<br>(Is yes skip dike)
-
Is tank diked?
-
Dike floor construction:
-
Is dike drain closed?
-
Is dike empty?
-
Is there more than 1320 gallons of total Petro products stored in above ground tanks?<br>(If yes, need to comply with Sarah Tier II requirements)
-
If yes, is a spill Control & Countermeasure plan required? <br>(Only is petroleum exceeds 1320 gallons, and stored outdoors)
-
If SPCC plan required, is there a written plan in place?
-
Has plan been certified by management / signed by GM?
-
Certified by professional engineer?
-
Notification / Emergency contact list?
-
Inspection report on file?
-
Significant changes to SPCC plan?
-
Spill greater than 10 gallons within last year?
-
If plan has been implemented for more than 3 years, has the last review been done within the past 3 years?
-
Is the facility in compliance with the SPCC plan?
-
Action Required:
-
Tank 5:
-
Tank capacity in gallons:
-
Tank contents:
-
Is tank labeled correctly?
-
Year of construction:
-
Location:
-
Tank configuration:
-
Cube:
-
Vertical
-
Horizontal
-
Drum:
-
Vertical
-
Horizontal
-
Is permit required for tank?
-
If yes, is tank permitted?
-
Is tank in compliance with local, state, and federal regulations as well as AMR Policy?
-
Is tank skid mounted?
-
Does tank have rain protection?
-
Is outdoor AST electrically grounded?
-
Does tank have automatic inventory controls?
-
Does tank have overfill protection at dispensing point?
-
Does tank have spill containment?
-
Is tank double wall construction?<br>(Is yes skip dike)
-
Is tank diked?
-
Dike floor construction:
-
Is dike drain closed?
-
Is dike empty?
-
Is there more than 1320 gallons of total Petro products stored in above ground tanks?<br>(If yes, need to comply with Sarah Tier II requirements)
-
If yes, is a spill Control & Countermeasure plan required? <br>(Only is petroleum exceeds 1320 gallons, and stored outdoors)
-
If SPCC plan required, is there a written plan in place?
-
Has plan been certified by management / signed by GM?
-
Certified by professional engineer?
-
Notification / Emergency contact list?
-
Inspection report on file?
-
Significant changes to SPCC plan?
-
Spill greater than 10 gallons within last year?
-
If plan has been implemented for more than 3 years, has the last review been done within the past 3 years?
-
Is the facility in compliance with the SPCC plan?
-
Action Required:
-
Tank 6:
-
Tank capacity in gallons:
-
Tank contents:
-
Is tank labeled correctly?
-
Year of construction:
-
Location:
-
Tank configuration:
-
Cube:
-
Vertical
-
Horizontal
-
Drum:
-
Vertical
-
Horizontal
-
Is permit required for tank?
-
If yes, is tank permitted?
-
Is tank in compliance with local, state, and federal regulations as well as AMR Policy?
-
Is tank skid mounted?
-
Does tank have rain protection?
-
Is outdoor AST electrically grounded?
-
Does tank have automatic inventory controls?
-
Does tank have overfill protection at dispensing point?
-
Does tank have spill containment?
-
Is tank double wall construction?<br>(Is yes skip dike)
-
Is tank diked?
-
Dike floor construction:
-
Is dike drain closed?
-
Is dike empty?
-
Is there more than 1320 gallons of total Petro products stored in above ground tanks?<br>(If yes, need to comply with Sarah Tier II requirements)
-
If yes, is a spill Control & Countermeasure plan required? <br>(Only is petroleum exceeds 1320 gallons, and stored outdoors)
-
If SPCC plan required, is there a written plan in place?
-
Has plan been certified by management / signed by GM?
-
Certified by professional engineer?
-
Notification / Emergency contact list?
-
Inspection report on file?
-
Significant changes to SPCC plan?
-
Spill greater than 10 gallons within last year?
-
If plan has been implemented for more than 3 years, has the last review been done within the past 3 years?
-
Is the facility in compliance with the SPCC plan?
-
Action Required: