Arrival on Site & Customer Interaction

  • Did the installer arrive in the allocated time slot?

  • Was the van clean and free of damage?

  • Was the installer presentable with clean uniform and correct PPE?

  • Were you shown any ID?

  • Was the installer polite and professional?

  • Did the installer run through the job description/cable?

Visual Inspections

  • Main fuse/ Tails/ Meter etc satisfactory? (Correct size/ No damage)

  • Is the gas bonding present and within 600mm of gas meter?

  • Is the water bonding present and within 600mm of stop tap?

  • Is bonding required for anything else? (if applicable record in notes e.g. oil)

  • CT in correct location/position?

  • CT correctly terminated and secured? (sticker applied where applicable)

  • Sub main adequate for connection? (RCD/MCB/Cable)

MATTe/GARO Installation (if applicable)

  • Cable entry via manufacturer points only?

  • Earth not exported via chassis to SWA sheath? (intrusive only)

  • Connections adequate with ferrules as appropriate (intrusive only)

Installation of Chargepoint

  • If it's a tethered unit, does the cable reach the vehicle's parked location without putting mechanical strain on the cable?

  • Does the chargepoint location qualify with the OZEV requirements regarding private parking?

  • Is the chargepoint installed within the height limitations of the Code of Practice: Electric Vehicle Charging?

  • Is the location of the chargepoint in the best possible place?

  • Is the chargepoint securely fixed?

  • Are the cable entries into the chargepoint protected from water entry and to the manufacturer spec?

  • Are the crimped ferrules tight and secure? (intrusive only)

  • Are the terminal blocks (60A) separate and securely screwed onto the ferrules? (intrusive only)

  • Are the connections made with ferrules where stranded cables are used?

  • Data cable/CT cable correctly terminated using ferrules where applicable? (intrusive only)

  • Are cables correctly identified/sleeved? (intrusive only)

Cable Installation

  • Is the route of the cable installed to BS7671 and cable size adequate for protective device and suitable for the chargepoint?

  • Is the cable routed in a way to avoid damage/external influences?

  • Is the cable route inside the customers property neat and tidy? (mini trunking, no damage etc...)

  • Has the PVC trunking been installed correctly? (if applicable)

  • Has the PVC trunking been permanently secured to the building/wall? (if applicable)

  • If using PVC T+E / Hi Tuff clipped direct- are the clips evenly spaced and secure along the cable route? (400mm between clips)

  • If using PVC T+E / Hi Tuff clipped direct- Is the entry point via a suitable sized cable gland and tightened to prevent movement? (25mm for 6mm T+E)

  • If using PVC T+E- is the CPC conductor sleeved correctly? (intrusive only)

  • If used (PVC T+E) Is an adaptable box securely fixed and IP rating maintained?

  • Junctions and connections via Red Wago where required? (intrusive only)

  • If using SWA, is the sheathing earthed adequately with banjo and fly lead? (intrusive only)

  • If using SWA, is the sheath insulated at the charger?

  • If using SWA, are the cable cores correctly identified (intrusive only)

Connecting at Consumer Unit

  • Has the EV circuit been clearly identified and labelled appropriately?

  • Have all additional consumer units been correctly labelled?

  • Has the correct rated and type of MCB been installed for the requirements of the chargepoint?

  • Has the chargepoint been protected by the correct type of RCD?

  • Does the make and model of MCB correlate with the existing MCB's in the consumer unit?

  • Are the connections tight and secure? (intrusive only)

  • Are the cable correctly identified? (intrusive only)

  • Rotary isolator installed where required?

  • Connections to sub main via approved methods

Quality of Work

  • Is the work installed to our professional standards, cable route neat and sympathetic to the property?

  • Are the cable terminations neat and equal?

  • Has care been taken during installation?

  • Could anything have been done to improve the quality of the work carried out?

Tests Carried Out

  • Ze

  • IPF

  • R1 + R2

  • Insulation Resistance

  • Polarity

  • Zs

  • RCD

  • Charger connected to WiFi/4G?

  • PC results match that of installers?

Customer Review

  • Was the customer happy with the installation?

  • Did the installer keep you updated throughout the installation?

  • Did the installer explain the use of the unit?

  • Did the installer remove all waste and clean the site before departing?

  • How long was the installer on site for?

  • How would you rate your installation out of 10?

  • How would you rate the process of getting to the installation?

  • How would you rate the product?

  • Any improvements from the installation?

  • Any improvements for the unit/web based app?

  • Would you recommend to others?

Outcome

  • Outcome?

  • QS Signature

  • Customer Signature

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.