Title Page

  • Takes place on 21/06/2023

  • Prepared by Pablo Moreno.

  • Siemens Energy Paulsternstr. 26 13629 Berlin

Factory Acceptance Test SG (8VM1)

a-Visual Inspection

  • 1-Surfaces undamaged

  • 2-Designation labels available and correct

  • 3-Rating plate available and executed correctly

  • 4-Earthing balls and earthing busbars available

  • 5-Cable compartment -XB1: Voltage indicator VDS available.

  • 6-Cable compartment -XB2: Voltage indicator VDS available.

  • 7-Cable compartment -XB3: Voltage indicator FPI available.

  • 8-Cable compartment -XB3: Voltage indicator VDS available.

  • 9-LV equipment acc. to circuit diagram.

  • 10-Current transformer rating acc. to circuit diagram

  • 11-All phase labels are available and correct

  • 12-Bottom plates including cable cleats in the -XB2 cable compartment included and according to specification (BayConf.)

  • 13-Bottom plates including cable cleats in the -XB3 cable compartment included and according to specification (BayConf.)

  • 14-SIPROTEC Mimic diagrams correct

  • 15-Tool box available and complete (If it will delivered separate a sample will show).

  • 16-Check of repair kit and desiccant bags.

  • 17-Check of Acceleration sensors-sample.

  • 18-Check of Short-Circuit plugs for VDS (toolbox)/ sample.

  • 19-Check frame bolts.

  • 20-Project specific labels are according specification.

  • 21-Deviations

b-Function Test: Interface In & Outputs to WTC

  • 1-Connection of Power Supply -230V AC

  • 2-Connection of Power Supply -110V DC

  • 3-Close/Interlock from WTC

  • 4-Local/Remote from WTC

  • 5-Local/Remote switch

  • 6-Circuit-breaker operations and commands

  • 7-3-position drives (manual & electrical) operations and commands

  • 8-Gas low

  • 9-Gas too low

  • 10-CB tripped

  • 11-110V DC supervision monitoring

  • 12-MCB trip swithgear

  • 13-Aux. voltage supervision AC 230V

  • 14-On-spring charged / motor runtime supervision

  • 15-Prot. Relay not tripped (7SR45)

  • 16-No int. relay failure (7SR45).

  • 17-Inten. Relay failure (7SJ85).

  • 18-Trip circuit supervision (7SJ85).

  • 19- Trip signal 1 (7SJ85).

  • 20- Trip signal 2 (7SJ85).

  • 21-Auto reclose/SST check

  • 22-External trip WTC.

  • 23-External trip transformer

  • 24- VDS failure.

  • 25- EF-Isolated Network.

  • 26-Deviations

c-Secundary Injection Test- 7SR45- Self-powered Relay

  • 1- Test #1 I>

  • 2- Test #2 I>

  • 3-Test #3 I>

  • 4-Test #1 I>>

  • 5-Test #1 Inrush Restraint.

  • 6-Test #2 Inrush Restraint.

  • 7-Test #3 Inrush Restraint.

  • 8-Test #4 Inrush Restraint.

  • 9-Test #5 Inrush Restraint (Imax).

  • 10-Test #6 Inrush Restraint (Imax).

  • 11- Test #1 IG>>

  • 12-Deviations:

c-Secundary Injection Test- 7SJ85- Multifunction Relay

  • 1- Test #1 I>

  • 2- Test #2 I>

  • 3-Test #3 I>

  • 4-Test #1 I>>

  • 5-Test #1 Inrush Restraint.

  • 6-Test #2 Inrush Restraint.

  • 7-Test #3 Inrush Restraint.

  • 8-Test #4 Inrush Restraint.

  • 9-Test #5 Inrush Restraint (Imax).

  • 10-Test #6 Inrush Restraint (Imax).

  • 11- Test #1 IG>>

  • 12-Deviations:

d-Primary Injection Test

  • 1- Test #1 7SJ85- Trip verification 120A.

  • 2-Test #1 7SR45- Trip verification 70A.

  • 3-Test #1 7SJ85 & 7SR45- connection check 50A.

  • 4-Test #1 7SJ85 & 7SR45- connection check 80A.

  • 5-Deviations:

e-Fault Passage Indicator (FPI).

  • 1-Test #1- verify labeling.

  • 2-Test #2- verify device status.

  • 3- Test #3 - verify power supply.

  • 4-Test #4- no IE>activation.

  • 5-Test #5- IE>activation.

  • 6-Test #6- No I>activation.

  • 7-Test #7 I>activation.

  • 8-Deviations:

  • undefined

f-Voltage Detection System (VDS).

  • 1- VDS broken lead detection.

  • 2-VDS self-test.

  • 3-VDS Primary injection of High Voltage.

  • 4-VDS Signal test.

  • 5-Deviations:

g-Interlocking ( acc. to drawings).

  • 1- Interlocking conditions CB Open.

  • 2-Interlocking conditions CB Close.

  • 3- Trafo Key (-QZ91).

  • 4-Interlocking conditions Disconnector & Earthing switch.

  • 5- Interlocking conditions local/remote switch.

  • 6-Interlocking cable compartment cover.

  • 7-Interlocking Auto-Reclose/SST.

  • 8-Deviations:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.