FIre Alarm Checklist:
-
Are all cable insulation and continuity resistance measurements are logged and recorded (38.2)
-
Mains supply is dedicated, non switched, double pole isolated, correctly fused and labelled (25.2)
-
Mains supply is correctly identified at all distribution boards (25.2)
-
All batteries are clearly marked and labelled with date of installation (25.4)
-
Select date
-
Field wiring is labelled and correctly terminated in all control and ancillary equipment (26.2)
-
All detection, MCPs, warning, ancillary devices have been tested for correct operation and the results have been recorded (39.2)
-
Line isolators are fitted as appropriate, operate correctly and are marked on the drawings (13.2.3) (12.2.1)
-
Are there too many devices between any isolators e.g Apollo loop sounders max 10 (MFG Guide)
-
Are there any areas that are not covered by short circuit isolators (12.2.2)
-
There are a minimum of two sounder circuits installed (12.2.2)
-
Sound pressure levels have been checked and recorded on drawing or on the appendix to this checklist (39.2)
-
Remote signalling has been checked for correct operation to ARC (39.2)
-
Zone charts have been fitted in all appropriate locations (adjacent to control and repeaters) (13.2.4)
-
As fitted drawings are complete and have been updated where required, routing including including cable size
-
The premises have been left in a tidy condition and all materials and equipment removed from site (42.2)
-
Are there any callpoints missing from any exit of the building or floor level (39.2.10)
-
Are any callpoints wrongly positioned (39.2.10)
-
Are there any areas that lack detectors (39.2.11-16)
-
Are any detectors not suitable for there location or near air inlets / fans (32.2.11-16)
-
Are any detectors less than 500mm from walls / downstands (32.2.11-16)
-
Are any detectors spaced incorrectly - 7.5m Smoke / 5.3m Heat (39.2.11-16)
-
Are any detectors too far from the ceiling - 600mm Smoke / 150mm Heat (39.2.11-16)
-
Are any detectors near lights / obstructions (Must be more than 1.5 x depth of obstruction) (39.2.11-16)
-
Is there a mix of sounders and bells - Are sounders all the same tone (16.2.1c)
-
Are any locked stores not covered by LED's
-
Are there any trigger / sounder zones or auxillary outputs where the current loading is near or exceeds the limit (39.2)
-
Are there any devices at risk of false alarms? If so list below
-
List all special cause and effect, zone switching or interfacing and test for correct operation
-
Fire alarm zones - Please list below
Equipment and operational data required for:
-
Panel access code / key no
-
Number of zones
-
Number of spare zones
-
Power supply for repeater
-
Cores to repeater
-
Standby period
-
Battery size (calculation - Q x standby time + A x 1.25)
-
Quiescent current
-
Alarm current
-
Charger voltage
-
Communicator - Chip No
Addressable systems only:
-
Panel firmware details
-
Repeater firmware details
-
Software version at program
Commissioning Engineer:
-
Have all devices on the system been tested for correct operation (39.2)
-
Have all sounders been tested for correct operation
-
Have all cause and effect, relays, and PSU's on the sytem been tested for correct operation (39.2)
-
Does the system as commissioned comply with the fire category as designed? If not, record variations below (39.2)
I certify that the above checks and functional tests have been completed in accordance with manufacturers recommendations and / or applicable codes of practice:
-