Title Page
-
Site conducted
-
Conducted on
-
Prepared by
-
Location
-
Asset Number
-
Manufacturer
-
Size and Type
-
COMPLETE all six-monthly service activities as listed in Part A1 - referred to as Fire Extinguisher Level 1 inspection. All
-
Comments
-
CHECK that the anti-tamper device is intact. All
-
Comments
-
CHECK that the threads on operating head o cap are not damaged, vent(s) is (are) not blocked, and any strainer or expansion device is unobstructed. For heas with no screw thread, determine that the security locking device is undamaged and operation. Water, foam, powder
-
Comments
-
DISCHARGE and CHECK that the extinsuisher functions in accordance with the operating instructions and that the discharge is satisfactory. Recharge in accordance with Item 2.8 Table 10.4.2. of AS1851-2012. a) Water with additive, foam. b) water with corrosion inhibitors or freezing point depressants to be discharged on a 3-yearly frequency
-
Comments
-
CHECK that the actuating device is free of corrosion, moves freely, and is undamaged; any cutting edge is shar; and all sealing gaskets are in good condition. Water, foam, powder.
-
Comments
-
CHECK that the internal discharge tube, strainer and anti-overfill tube (where fitted) provide clear passage and are securely attached, and the anti-overfill device is undamaged. Water, foam
-
Comments
-
CHECK that the internal discharge tube or gas inlet tube or ports, provide clear passage and are correctly installed, and that the powder is free flowing. Powder
-
Comments