Title Page
-
Date of Fire Risk Assessment
-
Fire Risk Assessor
-
Address
-
Responsible Person / Competent Person
-
Carried out in the company of
-
Signature:
-
Review of this fire risk assessment should be carried out in:
Section A: Premises Summary
-
Description of property:
-
Quantity of Staircases within Premises:
-
Quantity of Lift Shafts with Premises:
-
Taking into account the nature of the building and the occupants, as well as the fire protection and procedural arrangements observed at the time of this fire risk assessment, it is considered that the hazard from fire (probability of ignition) found within the areas assessed is:
-
The most likely cause of fire is likely to be generated from:
-
Taking into account the nature of the building and the occupants, as well as the fire protection and procedural arrangements observed at the time of this fire risk assessment, it is considered that the consequences for life safety in the event of fire would be:
- SLIGHT, i.e outbreak of fire is unlikely to result in serious injury or death of any occupant
- MAJOR, i.e outbreak of fire is likely to result in serious injuries or death of occupants
- SEVERE, i.e outbreak of fire is almost certain to result in serious injuries and death of occupants
-
This report was commissioned by:
-
Executive Summary:
-
The recommendations within this report have been put forward to assist the client
in complying with the requirements of the Regulatory Reform (Fire Safety) Order 2005 & The Fire Safety Act 2021. It is the decision of the responsible person(s) as to whether or not the guidance offered in this report is acted upon. Note that, although the purpose of this summary is to place the fire risk in context, the adopted approach to fire risk assessment is subjective and for guidance only. All hazards and deficiencies identified in this report should be addressed by implementing all recommendations identified below. The risk assessment should be reviewed periodically so that it is up to date; particularly if there is reason to suspect that it is no longer valid. The Regulatory Reform (Fire Safety) Order 2005 & The Fire Safety Act 2021 imposes requirements on the ‘Responsible Person’ to take such general fire precautions as will ensure, so far as is reasonably practicable the safety from fire of any of their employees or other relevant persons. A relevant person is any person (including the responsible person) who is or may be lawfully on the premises, including any person in the immediate vicinity of the premises who may be at risk from a fire on the premises. It is recommended that a review is carried out at least once per year or if/where significant changes or material alterations have been made. -
The recommendations within this report are based on my interpretation of the obligation brought by the Regulatory Reform (Fire Safety) Order 2005 & The Fire Safety Act 2021 on to the responsible person(s) of the client and may on occasion differ from that of the responsible person(s) and the enforcing authorities. Differences in opinion arise because the perception of risk interpreted by an individual risk assessor and those of the responsible person(s) and/or authorities will, on occasion, vary due to the subjectivity of any assessment. The ultimate responsibility for the adequacy of the fire risk assessment rests with the duty-holder, namely the person defined by legislation as responsible for ensuring that the fire risk assessment is carried out and that the fire precautions are adequate. The responsible person is advised that should they deem any points made within this report inadequate, unreasonable and/or impracticable, they should first raise any issues with the fire risk assessor.
-
The type of assessment being carried out is known as a "Type 1". A Type 1 fire risk assessment is the basic fire risk assessment required for the purpose of satisfying the Regulatory Reform (Fire Safety) Order 2005 & The Fire Safety Act 2021. The inspection of the building is non-destructive. But, as well as considering the arrangements for means of escape and so forth, the fire risk assessment includes examination of any separating construction between compartments and occupancies without any opening up of construction. However, in this Type of fire risk assessment, entry to other premises beyond the area of the assessed premise is not involved. Where there are demountable false ceilings it may be appropriate to lift a sample of readily accessible false ceiling tiles. In addition, it will normally be appropriate to open a sample of service risers, provided access is practicable at the time of inspection.
Unless there is reason to expect serious deficiencies in structural fire protection – such as inadequate compartmentation, or poor fire stopping – a Type 1 inspection will normally be sufficient for most commercial premises and blocks of flats. Where doubt exists in relation to these matters, the action plan of a Type 1 fire risk assessment may recommend that one of the other types of fire risk assessment be carried out, or that further investigation be carried out by specialists. However, this
should not be a generic recommendation of all Type 1 fire risk assessments; the recommendation should be based on identification of issues that justify reason for doubt.) -
Are any areas excluded from this report?
-
What areas are excluded?
-
What is the reason for exclusion?
- Not accessible
- H&S Risk (Asbestos, Electrical, Unsafe Access etc)
- Not quoted (additional building/area not made aware at quotation stage)
- Not covered under the RRFSO or FSA Legislation (e.g private dwelling)
Inspection
-
Indicate the risk level at the time of the assessment
-
Number of storeys including basement floors in the building
-
Number of storeys included in the risk assessment
-
Approximate total floor area in M2 of the floors surveyed
-
Approximate floor area in M2 of the footprint of the building
-
Number of additional tenants/occupiers in the building
Occupiers of the Building
-
Details of Occupants:
-
Approximate total numbers of persons employed in the whole premises
-
Approximate numbers of members of the public resorting to the premises
-
Premises used out of hours?
-
Are persons specifically at risk?
-
Approximate total numbers known to sleep in the premises
-
Are there occupants in remote areas?
-
Is there any recent history of fires in the building?
-
Has the premises got any licenses? (Gambling/Alcohol Etc)
-
Has the premises had a previous fire risk assessment?
-
Has the premises had any enforcement notices issued by local authority?
Section B: Fire Hazards and Ignition Sources
B1: Electrical Sources of Ignition
-
Is portable appliance testing undertaken?
-
Are electrical circuits and installations periodically tested and inspected?
-
Is there managerial control of personal electrical items?
-
Are any electrical adaptors or extension leads used safely?
-
Are electrical cables routed so as to avoid physical damage?
-
Is lightning protection provided for the building?
-
Indicate the appropriate risk level:
B2: Smoking
-
Is smoking permitted in any part of the building?
-
Is smoking managed in an appropriate and safe manner?
-
Indicate the appropriate risk level:
B3: Heating
-
Are mains gas supplies connected?
-
Are fixed heating installations, gas appliances and boilers subject to regular maintenance by competent contractors?
-
Are records of fixed heating installations, gas appliances and boiler maintenance kept on site?
-
Are portable heaters in use?
-
If yes, list the types
-
Are portable heaters kept away from any combustible storage or refuse?
-
Indicate the appropriate risk level:
B4: Cooking
-
Are catering facilities provided?
-
Is this on a commercial basis?
-
Does this involve the use of deep fat fryers, an oven, or cooking range?
-
Are emergency cut off switches/valves/cocks provided and accessible with their location and use indicated by signage?
-
Are grease filters and extraction ducting degreased and cleaned?
-
Are cleaning certificates provided?
-
Indicate the appropriate risk level:
B5: Arson
-
Is external refuse managed adequately?
-
Are suitable external security arrangements in place?
-
Are suitable internal security arrangements in place?
-
Is the building vulnerable to arson?
-
Indicate the appropriate risk level:
B6: Factory Processes
-
Do any potentially hazardous processes take place?
-
Indicate the appropriate risk level:
B7: Storage and Housekeeping
-
Are large/abnormal amounts of combustible storage kept in the premises?
-
Is there a large or excessive fire loading?
-
If so, are storage arrangements adequate?
-
Are highly flammable materials kept in the premises?
-
If so, are storage arrangements adequate?
-
Are other hazardous materials kept in the premises?
-
If so, are storage arrangements adequate?
-
Is general housekeeping satisfactory?
-
Is the upholstery of foam furniture in good condition?
-
Are significant ignition sources separated from combustible or highly flammable materials?
-
Is the use of highly flammable materials minimised?
-
Is there a roof space/basement used for storage?
-
Indicate the appropriate risk level:
B8: Building Work and Outside Contractors
-
At the time of the risk assessment, was there any building work being carried out?
-
If so, did this introduce any unusual hazards or ignition sources?
-
Is managerial control of contractors adequate and satisfactory?
-
Are any fire safety conditions imposed on contractors?
-
Is there a permit to work/hot work permit scheme?
-
Do contractors work out of hours?
-
Indicate the appropriate risk level:
Section C: Means of Escape in Case of Fire
C1: Alternative Means of Escape
-
Details:
-
Are there adequate numbers of final exit doors for the occupancy capacity?
-
Are all fire exits immediately open-able without the use of a key?
-
Are electronic security locks fitted to exit doors on escape routes?
-
If so, are the appropriately and safely fitted and maintained?
-
Do fire exits open in the direction of escape?
-
Are sliding or revolving doors relied on for means of escape?
-
Is adequate artificial illumination provided where necessary?
-
Are the alternative exit route(s) provided with appropriate fire exit signage?
-
Are any inner room situations involved?
-
Are vision panels fitted or automatic fire detection provided in access rooms to inner rooms?
-
Were any unsatisfactory fire exit or escape routes noted?
-
Alternative means of escape acceptable?
C2: Protection of Internal Escape Routes and Structural Integrity
-
Are any dead end exit routes adequately protected?
-
Are floor surfaces, stairs and handrails etc. safe?
-
Are exit routes adequately clear of storage and obstructions?
-
Are staircases kept clear of storage and obstructions?
-
Are existing fire doors installed to conform to relevant British Standards?
-
Are fire doors held open by irregular means?
-
Are fire doors maintained to current standards at the the required frequency or more by a competent contractor in accordance with BS9999/The Fire Safety (England)<br>Regulations 2022?
-
Are door holding devices fitted to fire doors?
-
If so, are the appropriately and safely fitted, signed and maintained?
-
Are any fire doors or fire resisting partitions damaged?
-
Are existing fire resisting partitions installed to comply with relevant British Standards as far as could be ascertained?
-
Is there reasonable limitation of linings which might promote fire spread?
-
Are service shafts between floors adequately fire stopped?
-
Are doors to service riser shafts to a suitable fire resisting standard?
-
Is compartmentation considered to be of a reasonable standard?
-
Does the premises have external cladding, curtain wall glazing or vertically stacked balconies?
-
Does the premises have any aluminum composite panels (ACM), metal composite panels (MCM) or high pressure laminate panels (HPL)?
-
Is the building over 18M (six storeys) in height?
-
Are disabled refuges provided?
-
If so, are they adequate and provided with appropriate communications?
-
Have active fire precautionary arrangements been introduced to replace passive measures? i.e. automatic fire detection to replace fire resisting lobbies on a single staircase etc.
-
If so, are they considered safe and adequate?
-
Is the protection of internal escape routes and structural integrity satisfactory?
C3: External exit routes
-
Do external exit routes lead to a place of final safety?
-
Are external exit routes even, illuminated and without obstructions or trip hazards?
-
Are external staircases, balconies and gangways examined by a competent person at not less than three yearly intervals?
-
Are external staircases, balconies and gangways properly and adequately protected from fire in the parent or adjacent occupancy?
-
Are external exit routes clear of obstructions, storage and refuse?
-
Are external exit routes considered satisfactory?
-
Alternative means of escape acceptable?
-
Indicate the appropriate risk level:
Section D: Emergency Escape Lighting
D: Emergency Escape Lighting
-
Does the premises have an emergency lighting system?
-
Maintained by:
-
Serviced to comply with the current British Standard 5266:
-
Tested to comply with the current British Standard 5266:
-
Date of last service:
-
Records up to date?
-
Is the emergency lighting system in good physical condition?
-
If no emergency lighting is provided or required, indicate this justification:
-
Are occupants at risk from emergency lighting deficiencies?
-
Indicate the appropriate risk level:
Section E: Signs and Notices
E: Signs & Notices
-
Existing signs and notices provided, comply with the Health and Safety (Safety Signs and Signals) Regulations 1996 and/or British Standard 5499 part 4-2000
- Existing signs and notices provided, appear to comply with the Health and Safety (Safety Signs and Signals) Regulations 1996 and/or British Standard 5499 part 4-2000.
- Existing signs and notices provided, do not appear to comply with the Health & Safety (Safety Signs & Signal) Regulations 1996 and/or British Standard 5499 part 4-2000.
- No signage provided.
-
Additional signs required?
-
Are occupants at risk from signage deficiencies?
-
Indicate the appropriate risk level:
Section F: Fire Alarm and Fire Warning Arrangements
F: Fire Alarm & Fire Warning Arrangements
-
Does this premises have a fire alarm system?
-
Does the premises have automatic fire detection?
-
If partial, indicate areas protected by automatic fire detection:
-
Maintained by:
-
Serviced to comply with current British Standards 5839?
-
Does the system conform to current British Standards 5839?
- BS5839-1:2017 (Commercial)
- BS5839-6:2017 (Domestic/HMO)
- Does not comply to current standards
-
Tested to comply with British Standard 5839 Part 1?
- Tested to BS5839-1:2017 (Commercial) Standard
- Tested to BS5839-6:2017 (Domestic/HMO) Standard
- Not Currently Tested
-
Date of last service?
-
Records up to date?
-
Alarm connected to a remote monitoring centre?
-
History of false alarms?
-
Is phased evacuation or a staged alarm system used in the building?
-
Are visual or other non-audible signals used or necessary to augment the fire warning arrangements?
-
Is the fire alarm connected to any music system (DJ booth, PA system, Speaker System) to cut off the audio output automatically during a fire alarm activation?
-
Are occupants at risk from fire alarm deficiencies?
-
Indicate the appropriate risk level:
Section G: Fixed and Portable Fire Extinguishing Equipment
G1: The following types of fire extinguishers are provided on site:
-
Are portable fire extinguishers provided on the premises?
-
Types:
- CO2
- Water
- Foam
- Dry Powder
- Wet Chemical
-
Are fire extinguishers adequate for the current risk?
-
Are fire extinguishers correctly sited and correctly identified by signage?
-
Are fire extinguishers adequately secured in position and not obstructed?
-
Extinguishers serviced by:
-
Are fire extinguishers serviced in accordance with British Standard 5306?
-
Has there been a discharge test on the extinguishers and has this been recorded?
-
Records up to date?
-
Date of last service?
-
Are occupants at risk from fire extinguisher deficiencies?
-
Indicate the appropriate risk level:
G2: The following fixed fire fighting installation(s) is/are provided on site:
-
Are fixed fire fighting installations provided in the premises?
-
Type of equipment
-
Serviced by
-
Date of last service
-
Records up to date?
-
Are occupants or fire-fighters at risk from fixed installation deficiencies?
-
Indicate the appropriate risk level:
Section H: Management of Fire Safety
H1: Fire routine & Emergency Plan
-
Is there an established fire routine and emergency plan?
-
Are all necessary issues included in the plan?
-
Are all necessary issues included in the plan?
H2: Training & Drills
-
Does the premises have any on site staff/employees?
-
Are all staff given fire instruction on induction?
-
Are all staff given periodic refresher training at suitable intervals?
-
Are staff trained to recognise and use fire extinguishers?
-
Are fire wardens appointed and trained?
-
Are there adequate numbers of fire wardens?
-
Are staff, other than fire wardens, designated to assist where necessary?
-
Have people been trained in the assistance of evacuation of disabled occupants?
-
Have people been trained in the assistance of evacuation?
-
Evacuation drills held?
-
Date of last evacuation drill?
-
Has an assembly point been agreed and notified to occupants?
-
Have all occupants been made aware of the emergency plan?
-
Who is responsible for fire safety?
-
Who is responsible for checking fire alarm system?
-
Who is responsible for contacting the emergency services?
-
Is a suitable fire safety policy in place?
H3: Record Keeping
-
Is a dedicated fire log book maintained?
-
Are all appropriate records maintained?
-
Is there a system for monitoring fire safety in place?
-
Is there a system for auditing fire safety in place?
H4: Disabled Persons & Visitors
-
Are disabled persons employed?
-
Do disabled persons frequent premises?
-
Any special requirements or additional needs?
-
Is management of disabled procedures satisfactory?
-
Is the procedure part of the fire routine, emergency plan and staff training?
-
Do visitors frequent the premises?
-
Is the managerial procedure for visitors satisfactory?
-
Are any persons at risk from management deficiencies?
-
Indicate the appropriate risk level:
Section I: Access for Fire Fighting and Fire Fighter Safety
I: Access for Fire Fighting & Fire Fighter Safety
-
Is access for fire service vehicles satisfactory?
-
Is access for fire fighters on foot satisfactory?
-
Is access for fire fighting or means of escape clear and unobstructed?
-
Date of last fire service inspection, if known?
-
Have the fire and rescue service been advised of any changes to the building or occupancy?
-
Are local water supplies/hydrants adequate and suitably near to the building?
-
Are the local fire service made aware of any hazardous materials or issues, which may be hazardous whilst fire fighting?
-
Is external signage provided to warn fire fighters of storage hazards?
-
Are suitable fire fighters switches provided?
-
Has the responsible person considered any issues which might significantly damage of effect the environment in case of fire?
-
Has the possibility of fire spread to or from adjoining or adjacent buildings been considered by the responsible person?
-
Are occupants, fire fighters or the environment at risk from access or managerial deficiencies?
-
Indicate the appropriate risk level:
Section J: Quality Statement
-
This report presents the significant findings of the fire risk assessment which took into account the occupancy profile, the fire hazards and risks present while evaluating the general fire precautions in the premises at the time. The measures highlighted in the following table of remedial actions are recommendations which it is considered should be put in place to achieve compliance with the Regulatory Reform (Fire Safety) Order 2005 and reduce the risk to people from fire in these premises to a level which may be considered as low as reasonably practicable.
The company and the fire risk assessor(s) cannot condone the continuance of contraventions which became evident as a result of this fire risk assessment. Therefore the significant findings and relevant actions recommended in this report should be remedied without delay to ensure compliance.
The risk ratings recorded in the remedial actions table are intended to give clients an indication of the severity of the associated risk and assist with prioritisation of work. They should not be taken to imply any specific time period for completion or legal immunity in any intervening period.
This form of quantification serves purely as a broad indication of the situation for the benefit of the “Responsible Person” to then determine how best to achieve and manage the actions to be taken/recommendations contained in this report.
Where appropriate remedial actions may still be required from the previous fire risk assessment (where this has been made available to the assessor) and still require action in accordance with the previous fire risk assessment. -
Assessor:
-
All reasonable skill and care has been taken in the preparation of this report.
-
Taking into account the fire prevention measures observed at the time of this risk assessment, it is considered that the hazard from fire (likelihood of fire) at these premises is:
-
In this context, a definition of the above terms is as follows:
Low: Unusually low likelihood of fire as a result of negligible potential sources of ignition.
Med: Normal fire hazards (e.g. potential ignition sources) for this type of occupancy, with fire hazards generally subject to appropriate controls (other than minor shortcomings).
High: Lack of adequate controls applied to one or more significant fire hazards, such as to result in significant increase in likelihood of fire. -
Having assessed the fire hazards present, the occupancy profile and having evaluated the general fire precautions in place at the time of this fire risk assessment, it is considered that the consequences for life safety in the event of fire would be:
-
In this context, a definition of the above terms is as follows:
Slight Harm: Outbreak of fire unlikely to result in serious injury or death of any occupant (other than an occupant sleeping in a room in which a fire occurs).
Moderate Harm: Outbreak of fire could foreseeably result in injury (including serious injury) of one or more occupants, but it is unlikely to involve multiple fatalities.
Extreme Harm: Significant potential for serious injury or death of one or more occupants. -
Accordingly, it is considered that the risk to life from fire at these premises is:
-
Tolerable: No major additional fire precautions required. However, there might be a need for reasonably practicable improvements that involve minor or limited cost.
Substantial: It is essential that efforts are made to reduce the risk. Risk reduction measures, which should take cost into account, should be implemented within a defined time period.
Where moderate risk is associated with consequences that constitute extreme harm, further assessment might be required to establish more precisely the likelihood of harm as a basis for determining the priority for improved control measures. Considerable resources might have to be allocated to reduce the risk. If the premises are unoccupied, it should not be occupied until the risk has been reduced. If the premises is occupied, urgent action should be taken.
Intolerable: Premises (or relevant area) should not be occupied until the risk is reduced. -
A suitable risk-based control plan should involve effort and urgency that is proportional to risk.
Note that, although the purpose of this section is to place the fire risk in context, the above approach to fire risk assessment is subjective and for guidance only.
All hazards and deficiencies identified in this report should be addressed by implementing the recommendations contained in the action plan.
Recommended Timescales for remedial actions.
High: Immediate action, every effort should be made to rectify the issues within 7 days
Medium: Action within 30 days preferably to resolve the issue within this period
Low: Action within 90 days