Title Page

  • Report number

  • Report type

  • Location
  • Conducted on

  • Prepared by

  • HOLLAND BROS PLUMBING (NSW) PTY LTD

  • 2/14 Chicago Ave, Blacktown NSW 2148

  • Phone: 9764 2790 Mobile: 0414 244 635

  • ABN: 51 003 968 616 LIC NO: 223351C

  • Email: martin@hollandbrosplumbing.com.au

  • Website: www.hollandbrosplumbing.com.au

6 Monthly maintenance

Water supply stop valves and System controls

  • Control valve assembly. CHECK that control valve assembly area is unobstructed and free of any condition that may adversely affect the operation or access.

  • Control valve photo

  • System pressure gauge

  • RECORD reading from pressure gauge.

  • System pressure gauge photo

  • Test and drain valve opperation

  • Open test and drain valve to insure water supply is present

  • Close test and drain valve and record time for pressure recovery

  • Verify that the time for pressure recovery aligns with previously recorded value. NOTE: Where the building exceeds four storeys in height, care should be taken to censure that the static head of the installation does not excessively elevate the residual pressure reading.

  • Sprinkler spares, sprinklers and sprinkler spanner. CHECK that there are spare sprinklers of appropriate quantity and type including a matching sprinkler spanner for each type of sprinkler fitted, available.

  • Sprinkler spares photo

  • All isolation valves strapped and locked with 003 locks

Signage

  • CHECK for legibility and appropriate location

  • System control valve clearly labeled

  • Photo of system control valve

  • Test and drain valve clearly labeled

  • Photo of Test and drain valve

Yearly test

  • Complete all six-monthly service activities, as listed above

Survey—Pipes and hangers

  • CHECK (A) pipework check that exposed water distribution system, including pipework, pipe support and valves, appear free from corrosion and damage, not subject to external loads and pipework is properly supported

  • PHOTOS

Survey— Sprinkler condition

  • CHECK sprinklers for any condition, including physical damage, contamination, and paint on operating elements or cover plates, likely to adversely affect their function. NOTE: Sprinkler frames may be painted as part of the manufacturing process; however, the heat response elements should not be painted as this will delay or prevent operation and paint accumulated at the seat of the sprinkler may affect operation. Minor spatter on the fusible elements may be acceptable but operation should be checked if doubt exists.

  • Number of sprinklers on site

  • Photos

Survey— Sprinkler obstructions

  • CHECK for obstructions likely to impede sprinkler discharge and for adequate clear space below sprinklers.

  • Photos

  • Mullions and glazing bars less than 40mm projection present

  • Provide photos of Mullions and glazing bars

  • Mullions and glazing bars greater than 40mm projection present

  • Measurements of Mullions and glazing bars

  • Provide photos of Mullions and glazing bars

Survey— Unprotected areas

  • CHECK for presence of unprotected areas

  • CHECK for sprinkler spacing and location relative to wall, bulkhead and partition alterations and the introduction of fixtures and fittings shielding sprinkler discharge.

  • CHECK for the need to install sprinkler guards

Survey— Occupancy

  • (A) Occupancy- CHECK that design remains applicable for current building arrangement or use.

  • (B) Site documentation- CHECK emergency instructions and pressure schedules contain the details required in accordance with relevant design standards

  • PHOTOS

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.