Information
-
Audit No.
-
Customer
-
Project
-
Conducted on
-
Audited by
-
Location
Project Details
-
Insert Customer
-
Insert Project
-
Insert XT part number if applicable
-
Insert component/assembly if applicable
-
Insert component/assembly part number if applicable
Audit
-
Please answer N/A to any questions that are not applicable to the part being audited.
Notes or photos can be added to questions by pressing (…) and selecting 'Show Notes/Media'. -
Is the meter that is being used, listed as a suitable test instrument as per SPC-0010046?
-
Please record the meter serial number
-
Is the meter within calibration and fit for purpose?
-
Please record the meter calibration date
-
Has the meter been checked for internal resistance, and is the value being used as an offset when taking continuity readings?
-
Has paint/coating been removed from under the head/nut of bolted connections or grounding strap lugs?
-
Have all fasteners been torqued to the correct value, as per procedure or PRD-0000021662?
-
Have all fasteners been marked to indicate that they are fully torqued?
-
As per SWI60046855, has the correct wire size been used for all grounding straps?
-
Have all grounding straps been correctly crimped?
-
Have all grounding straps passed a pull test?
-
As per SWI60046855, has the correct make up of washers been used on all grounding straps?
-
Do continuity readings meet the acceptance criteria of <0.1Ω?
-
If applicable, have the meter details and average internal resistance values been recorded in the documentation?
-
Has the continuity been recored and signed off in the required documentation?
Audit Sign Off
-
Tick box to confirm all applicable questions have been answered.
-
Audited by