Title Page

  • Client

  • Site address

  • EICR Contractor

  • EICR Contractor Engineer

  • Date the works to be audited were completed

  • Works that were completed, to be audited

  • Audit Date

  • Audit conducted by

Remedial/Installation work and Certification accuracy.

  • Are details of the work carried out entered on the certification correctly? (EIC or MWC) To include the selection new, alteration or addition on any EIC.

  • Do the Supply Characteristics and Earthing Arrangements match what is recorded on the certification submitted? (incl. Distributors Facilty/Earth Electrode)

  • Does the main earth conductor size and main protective bonding conductor sizes match what is recorded on the certification submitted?

  • Does the main protective bonding conductor/s connection or continuity test reflect what is recorded on the certification produced? (note services applicable)

  • Was the main earthing conductor/main earthing conductor to the DB/Consumer Unit upgraded as part of remedial work - if so done correctly?

  • Where the main protective bonding conductor/s upgraded/installed as part of the work? If so have they been installed correctly and conductor continuity tests noted ? (list any issues, with photo)

  • Does the Ze and PFC and/or Zdb and Ipf (higher of PEFC or PSSC) match what is recorded on the certification submitted?

  • Maximum demand noted/calculated correctly?

  • Schedule of Inspections on any EIC submitted completed correctly relating to work carried out? (N/A for MWC)

  • Has any replacement Distribution Board or Consumer Unit been installed as per BS 7671:2018+A2:2022 including SPD and, if required, AFDD's? (Include photos)

  • Have any replacement OCPD's been selected and installed correctly?

  • If applicable, have any accessories been replaced correctly? (include photos)

  • If applicable, have any replacement downlights been selected and installed correctly? (i.e fire rated, enclosed connections etc. Include photos)

  • If applicable, Have any bathroom accessories been selected and installed correctly? (i.e Surface mounted IP rated lights. Include photos)

  • If applicable, has any new or replacement wiring been selected and installed correctly? (List circuits affected and details incl presence of fire rated cable supports where required. Include photos)

  • Has all the EICR C1/C2/FI identified required remedial works been completed to BS 7671:2018+A2:2022?

  • If applicable, has all the EICR C3 identified recommended remedial works been completed to BS 7671:2018+A2:2022?

  • Has any further defective parts of the installation been found that can be confirmed as missed from the initial EICR? (List details with photos)

  • On completion of the initial EICR, or after the Distribution Board/Consumer Unit has been replaced, has a BS 7671 compliant Periodic Inspection Test notice been placed at the origin of the installation or at teach DB/Consumer Unit and correctly completed? (Include photos as applicable)

Sample test results and circuit details accuracy. (Mark as N/A tests not part of this audit)

  • Does the Distribution Board or Consumer Unit circuit schedule match the details recorded on the certification submitted?

  • Do all OCPD devices and RCD's (incl RCBO's) have the correct BS EN details, rating and type noted correctly on the certification submitted?

  • Does the Type of Wiring code and Cable Installation Reference Methods match what is recorded on the certification submitted?

  • Do the number of points on a circuit/s match those recorded on the certification submitted? (note which circuit/s sampled)

  • Do the Lighting Circuit/s R1+R2 or R2 sample tests match those recorded on the certification submitted? (note which circuit/s checked, certificate test result and photos)

  • Does the Cooker and/or Hob circuit R1+R2 or R2 sample tests match those recorded on the certification submitted? (Include certificate test result and photo)

  • Do the Shower circuit R1+R2 or R2 sample tests match those recorded on the certification submitted? (if more than one electric shower note which circuit was checked, certificate test result and include photos)

  • Do the Immersion and/or Central Heating circuit R1+R2 or R2 sample tests match those recorded on the certification submitted? (note which circuit checked, certificate test result and photos)

  • Do the Fire detection circuit R1+R2 or R2 sample tests match those recorded on the certification submitted? (note certificate test result and photos)

  • Do the Ring Circuit/s 'end to end' conductor continuity sample tests match those recorded on the certification submitted? (note which circuit/s checked, certificate test result and photos)

  • Do the Ring Circuit/s R1+R2 sample tests match those recorded on the report submitted? (to reflect Figure of 8 test) (Note which circuit/s checked, certificate test result and photos)

  • Do any Radial circuits for socket-outlets R1+R2 sample tests match those recorded on the certification submitted? (note which circuits checked, certificate test result and photos)

  • Do the Insulation resistance sample tests match those recorded on the certification submitted? (note either individual circuits or whole installation/group of circuits as applicable and photos)

  • Do the Zs sample tests match those recorded on the certification submitted? (note which circuits were checked, certificate test result and photos)

  • Does any RCD (incl RCBO) sample tests match those recorded on the certification submitted? (x1 instrument trip test and test button operation, certificate test result and photos)

  • Has any Surge Protection Device fitted been recorded correctly on the certification submitted?

  • Has any AFDD manual test button operation been noted and matching what is recorded on the certification submitted? (if applicable)

  • Do any other circuit/s sample tests match those recorded on the certification submitted? (state circuit/s and tests performed, certificate test result and photos

  • If occupant is present, did the engineer wear PPE and use dust sheets/clean up after work completed? (if debris still evident, please supply photo)

Audit conclusion

  • Is any further action required? (to re-attend site for any reason due to outstanding works from remedial works/EICR or issues that have arisen since)

Additional comments

  • undefined

Signatures

  • Auditor

This audit has been completed by Gas-Elec Safety (UK) Ltd. The report is standard industry procedure as part of the company's NAPIT Competant Persons Scheme membership (EAS Scheme). This audit is not intended to be an investigation or diagnosis of any faults or defects that may have developed since the EICR/works were completed. This Audit is not in any way a part or full reproduction of any original certification previously issued by the attending contractor. Gas-Elec Safety (UK) Ltd or it's employees accept no liability for any omissions on this report.

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.