Title Page
-
Date
-
Technician Name
-
Job Number
-
Customer
-
Genset model Number - Description
-
Genset Serial Number
-
Asset Number
-
License Plate Number
INSPECTION
-
Is there a Marechal fitted
-
Engine Model Number
-
Engine Serial Number :
-
Alternator Model Number :
-
Alternator Serial Number :
-
Standby kVA Rating :
-
Standby kW Rating :
-
Power Factor :
-
Full Load Amp :
-
Frequency :
-
Voltage :
-
Phase :
-
Insulation resistance from outlet to the main earth while MEN Disconnected<br>and MCB ON must be > 1Mohms.<br>Record Result :
-
Earth continuity from main earth to the panels must be < 0.5ohms. Record Result :
-
Earth continuity from main earth to the outlet must be < 0.5ohms.<br>Record Result :
-
MEN Connection - MEN is installed at load connection compartment and<br>labeled
-
Polarity check between outlet and MCB
-
Phase rotation check
LOAD TEST
-
Test Criteria Duration
-
Engine and Generator output - 0%
-
0% Engine - Speed RPM
-
0% Power kW
-
0% Voltage - P+N Red - P+N White - P+N Blue
-
0% Frequency Hz
-
0% Amperes - Red - White - Blue
-
0% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 25%
-
25% Engine - Speed RPM
-
25% Power kW
-
25% Voltage - P+N Red - P+N White - P+N Blue
-
25% Frequency Hz
-
25% Amperes - Red - White - Blue
-
25% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 50%
-
50% Engine - Speed RPM
-
50% Power kW
-
50% Voltage - P+N Red - P+N White - P+N Blue
-
50% Frequency Hz
-
50% Amperes - Red - White - Blue
-
50% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 75%
-
75% Engine - Speed RPM
-
75% Power kW
-
75% Voltage - P+N Red - P+N White - P+N Blue
-
75% Frequency Hz
-
75% Amperes - Red - White - Blue
-
75% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 100%
-
100% Engine - Speed RPM
-
100% Power kW
-
100% Voltage - P+N Red - P+N White - P+N Blue
-
100% Frequency Hz
-
100% Amperes - Red - White - Blue
-
100% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 110%
-
110% Engine - Speed RPM
-
110% Power kW
-
110% Voltage - P+N Red - P+N White - P+N Blue
-
110% Frequency Hz
-
110% Amperes - Red - White - Blue
-
110% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 100%
-
100% Engine - Speed RPM
-
100% Power kW
-
100% Voltage - P+N Red - P+N White - P+N Blue
-
100% Frequency Hz
-
100% Amperes - Red - White - Blue
-
100% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 75%
-
75% Engine - Speed RPM
-
75% Power kW
-
75% Voltage - P+N Red - P+N White - P+N Blue
-
75% Frequency Hz
-
75% Amperes - Red - White - Blue
-
75% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 50%
-
50% Engine - Speed
-
50% Power kW
-
50% Voltage - P+N Red - P+N White - P+N Blue
-
50% Frequency Hz
-
50% Amperes - Red - White - Blue
-
50% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 25%
-
25% Engine - Speed RP
-
25% Power kW
-
25% Voltage - P+N Red - P+N White - P+N Blue
-
25% Frequency Hz
-
25% Amperes - Red - White - Blue
-
25% Engine - Water Temp C - Oil Press Bar - Battery VDC
-
Engine and Generator output - 0%
-
0% Engine - Speed RPM
-
0% Power kW
-
0% Voltage - P+N Red - P+N White - P+N Blue
-
0% Frequency Hz
-
0% Amperes - Red - White - Blue
-
0% Engine - Water Temp C - Oil Press Bar - Battery VDC
ELECTRICAL
-
Electrical Test and Tag
-
All cables numbered both ends
-
All cable ends terminated with bootlace ferrules/lugs
-
All relays, circuit breakers and contactors correctly labeled
-
Check control panel door wiring
-
Check cable duct lids in place
-
Check conduit fittings , glands and plugs are secure
-
Check all cable connections
-
Ensure no risk of abrasion or damage from sharp objects/edges
ENGINE HARNESS
-
Ensure all conduits are secure and neat
-
Ensure conduit connections and plugs are secure and neat
-
Ensure no risk of abrasion or damage from sharp edges /objects
-
Ensure cable boots installed and secure where ap
-
Ensure earth straps on all doors installed
-
Ensure appropriate fasteners used on earth straps
-
Ensure earth strap between alternator and chassis installed
-
Ensure all cabling for connections are secure and neat
-
Ensure all cabling is secured to prevent fatigue due to bending
GENSET INTERNAL PHOTOS
-
Internal Photos
-
Control Panel External Photos, including electrical tag
-
Checked by:
-
Signature
-
Date
OTHER
-
OTHER