Heat and Smoke Venting Systems Checklist

  • 1. Has a quantified risk assessment highlighting the effects heat and smoke could have on your premises, contents, stock, occupants and business operations been completed?

  • 2. Has a quantified assessment been made on how long it would take to decontaminate the ventilation systems/site following a fire?

  • 3. Is there knowledge or a formal relationship in place with a third-party decontamination specialist to assist in post-event recovery?

  • 4. If you do not have heat and smoke vents and/or means of extracting the effects of heat and smoke, would the fitting of such devices provide benefits to your business?

Heat and Smoke Vents – Where Already Provided

  • 5. Are there accurate drawings and detailed specifications showing the location and layouts of the heat and smoke venting system?

  • 6. Are all aspects of the heat and smoke venting systems, including any wiring, supports, ducting, etc., constructed to withstand the:<br>• Maximum expected temperatures?<br>• Direct exposure to flame?

  • 7. Are the actuation mechanisms of all heat and smoke venting systems formally documented and understood?

  • 8. Is the heat and smoke venting system dedicated or is it part of a combined air conditioning/ventilation system?

  • 9. Are the exit points from the vents located in positions to ensure that vented smoke is not entrained into the building or nearby buildings?

  • 10. Do the vents actuate individually or are there multiple devices within zones or groups?<br><br>Is this appropriate for the risk and the protection measures in place?

  • 11. Have compartmented zones been created at ceiling/roof level to segregate the heat and smoke venting?<br><br>Is this with at least 1m deep non-combustible draft curtains?

  • 12. Are any interlocks between the heat and smoke vents and other systems formally documented and understood?

  • 13. Is heat and smoke venting provided in a building protected with automatic sprinklers?<br><br> If yes, is the heat and smoke venting in the building only manually actuated?<br><br>If yes, if Regulatory requirements formally state heat and smoke venting in a sprinkler protected building should be automatic; for property protection purposes it should be designed to:<br>• Operate vents singularly<br>• Be actuated by a fusible link/frangible bulb rated at Standard response >181ᵒC

  • 14. Is heat and smoke venting manually actuated?<br><br>If yes, Are these actuation devices:<br>• In readily accessible and safe location(s)?<br>• Clearly and logically labelled to avoid confusion?<br>• Next to a schematic drawing to support expected response?

  • 15. For vents that rely on motorised controls or mechanical extraction, are there means to allow for actuation and operation in the event of loss of power?

  • 16. Are the public fire service and any on-site trained emergency response teams aware of the heat and smoke venting arrangements, including?<br>• When to utilise it?<br>• How to actuate it?<br>• How to isolate it?

  • 17. Is there a formal regular inspection and maintenance programme that covers?<br>• Damage?<br>• Deterioration?<br>• Debris accumulation or obstruction?<br>• Water, snow or ice?<br><br>Is formal and tracked action taken to address any deficiencies?

  • 18. Is there a formal annual physical release and test of all vents, to ensure correct operation? <br>(Excludes Drop Out/Melt Out vents)<br><br>Does this include the cause and effect/interlocks associated with the heat and smoke venting?

Sign Off

  • Additional Comments:

  • Completed by (Name and Signature)

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.