Station Inspection

Monthly Inspection

  • O&M Buildings cleaned & bins emptied

  • Fire maintenance complete and master fire panel free of alarms

  • Oil water separator functional and clean

220kV Transmission Line Inspection

  • Structures free of defects

  • Corridor free of vegetation

  • Any defects noticed during maintenance

  • Complete 6 Monthly Inspection

6 Monthly Inspection

General Facility

  • Perimeter fence, roads, doors, locks, hazard signs all in good order

  • Eye wash station functional

  • Internal lights functional

  • External lights functional

  • Security and CCTV functional

  • Buildings free of damage, rodents

  • Interior roads in good condition

  • Drainage working

  • Trench covers present and undamaged

220/33kV Yard

  • Yard fence in good condition

  • Gantries and other metallic structure free of rust

  • 220kV VT free of oil leaks, damage, rust

220kV DS/ES

  • Clean, undamaged, free of build up on insulators

  • LV cables in good condition

  • Gaskets in good condition

  • Any other defects

220kV CB

  • Bushings ok

  • SF6 level ok

  • Operation counter

  • Door seal ok

  • Heater working

  • Any other defects

  • 220kV Bus free of defects, debris

220/33kV Transformer

  • Liquid levels ok

  • Oil temp max

  • HV winding temp max

  • LV winding temp max

  • Silica gel breathers ok

  • Control cubicle seals ok, heaters working

  • Fans and pumps functional

  • Any other defects

33kV NET/Aux TX

  • Winding temp max

  • Any other defects

  • 33kV GIS Block
  • Indicating lights operating correctly

  • External condition of switchgear ok

  • SF6 indication green

  • CB operation counter

  • CB operation counter over 10000

  • Heaters working

  • Free of moisture

  • Any other defects

  • 33kV RMU
  • Relays operational

  • External condition of switchgear ok

  • SF6 indication green

  • Any other defects

  • Core TX
  • Current Temperature (C)

  • Maximum Temperature (C)

  • External condition

  • Complete 12 Monthly Inspection

12 Monthly Inspection

  • Thermal images of 415V Switchboards (Control room, Block 1, Block 2, and Block 3)

General Facility

  • Air conditioning units working

  • Air conditioning filters cleaned

  • Battery impedance check - X Battery

  • Battery impedance check - Y Battery

220/33kV Yard

  • Oil sample of T1.TX1 and OLTC

  • Thermal images of all 220/33kV assets

  • Lighting mast inspection

  • Block
  • Thermal Images of Block Switchboard

  • Battery impedance check complete

  • Oil samples taken - 30x Core transformer, 1x main transformer, 1x tap changer

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.