Inspection

Exterior

Is there Knox Box?

Are the keys in the Knox Box the current keys to the business?

Square Footage:

Is the street address posted with a minimum 4" numbers with contrasting background, and visible from the street?

IFC 2009 Fire Code Violation # 505.1

Are the fire apparatus access roads, fire hydrants, FDCs, etc are clear of all obstructions?

Add media

Roads: IFC 2009 Fire Code Violation # 503 FDCs & Hydrants 3' clearance around: IFC Fire Code Violation # 507.5.5

Building Services
Utilities

Are utilities in good working order?

Location of gas shut off:

Are there elevators?

Does the elevator have fire service recall?

Does the elevator/s have fire service control?

Have the elevator/s been inspected by elevator inspector?

What is the location of the fire service keys?

Fire Protection Systems

Is there a fire suppression system?

Date of annual inspection:

Coverage:

Type of system:

Is there a fire pump?

Is it in the automatic position?

Date of last fire pump test:

Is there clearance of at least 18" on all sprinkler heads?

IFC 2009 Fire Code Violation # 315.2.1

Notes

Is there a Fire Alarm?

Location of Panel:

Type of Monitoring System:

Date of last system inspection:

Type of initiation devices:

Fire Extinguishers Present

Has the extinguisher been inspected in the last 12 months?

NFPA Fire Code Violation #: 13.6.9.3.1.1.1

Are the fire extinguishers mounted properly?

NFPA Fire Code Violation # 13.6.8.1.3.8

Date of annual inspection:

Adequate Number?

NFPA Fire Code Violation # 13.6.8.1

Fire Code Violation #: 906.1

Means of Egress

Are there exit signs? (Required where more than one exit is required/occupant load greater than 50)

Are the exit signs illuminated?

IFC 2009 Fire Code Violation # 1011.2

Readily Visibile?

Clear and Unobstructed?

Two remote exits available in loads greater than 50?

Doors swing in direction of egress when required?

Panic/Fire exit hardware operable?

Doors open easily?

IFC 2009 Fire Code Violation # 1008.1.9.3

Self closure operable and closes completely and latches?

Doors closed or held open with automatic closers?

Corridors and aisles of sufficient size? 44" load greater than 50; 36" load less than 50

IFC 2009 Fire Code Violation # 1017.2

Stairwell re-entry?

IFC 2009 Fire Code Violation # 1008.1.9.10

Housekeeping

Are all areas free of excessive combustibles/clutter?

Electrical

30" width/36" depth clearance maintained around electrical panels?

IFC 2009 Fire Code Violation # 605.3

Are extension cords being use as permanent wiring?

Add media

IFC 2009 Fire Code Violation # 605.5

Automatic External Defibrillators

Do they have an A.E.D.?

Location:

Summary

Notes

Representative of business
Inspector

Was a copy of the report emailed to business?

Kansas City Kansas Fire Department Checklist

Created by: Anonymous | Industry: Emergency Services | Downloads: 40

General Fire Safety Inspection

Signup for a free iAuditor account to download and edit this checklist. It will be added to your free account and you will be able to conduct inspections from your mobile device.

Download and edit this free checklist

Browse for other checklists


iauditor logo

The World's #1 Cloud-Based Inspection Software and App

chevron logo
coles logo
emirates logo
overground logo
tesla logo
toyota logo

Audit

Add location
Property Name
Exterior Image (Not Required)

Business Name

Address

Owner/Manager

Name:

Email Address:

Business Phone Number

Emergency Contact (Primary)

Name:

Phone Number

Emergency Contact (Secondary)

Name:

Phone Number

Inspection

Exterior

Is there Knox Box?

Are the keys in the Knox Box the current keys to the business?

Square Footage:

Is the street address posted with a minimum 4" numbers with contrasting background, and visible from the street?

IFC 2009 Fire Code Violation # 505.1

Are the fire apparatus access roads, fire hydrants, FDCs, etc are clear of all obstructions?

Add media

Roads: IFC 2009 Fire Code Violation # 503 FDCs & Hydrants 3' clearance around: IFC Fire Code Violation # 507.5.5

Building Services
Utilities

Are utilities in good working order?

Location of gas shut off:

Are there elevators?

Does the elevator have fire service recall?

Does the elevator/s have fire service control?

Have the elevator/s been inspected by elevator inspector?

What is the location of the fire service keys?

Fire Protection Systems

Is there a fire suppression system?

Date of annual inspection:

Coverage:

Type of system:

Is there a fire pump?

Is it in the automatic position?

Date of last fire pump test:

Is there clearance of at least 18" on all sprinkler heads?

IFC 2009 Fire Code Violation # 315.2.1

Notes

Is there a Fire Alarm?

Location of Panel:

Type of Monitoring System:

Date of last system inspection:

Type of initiation devices:

Fire Extinguishers Present

Has the extinguisher been inspected in the last 12 months?

NFPA Fire Code Violation #: 13.6.9.3.1.1.1

Are the fire extinguishers mounted properly?

NFPA Fire Code Violation # 13.6.8.1.3.8

Date of annual inspection:

Adequate Number?

NFPA Fire Code Violation # 13.6.8.1

Fire Code Violation #: 906.1

Means of Egress

Are there exit signs? (Required where more than one exit is required/occupant load greater than 50)

Are the exit signs illuminated?

IFC 2009 Fire Code Violation # 1011.2

Readily Visibile?

Clear and Unobstructed?

Two remote exits available in loads greater than 50?

Doors swing in direction of egress when required?

Panic/Fire exit hardware operable?

Doors open easily?

IFC 2009 Fire Code Violation # 1008.1.9.3

Self closure operable and closes completely and latches?

Doors closed or held open with automatic closers?

Corridors and aisles of sufficient size? 44" load greater than 50; 36" load less than 50

IFC 2009 Fire Code Violation # 1017.2

Stairwell re-entry?

IFC 2009 Fire Code Violation # 1008.1.9.10

Housekeeping

Are all areas free of excessive combustibles/clutter?

Electrical

30" width/36" depth clearance maintained around electrical panels?

IFC 2009 Fire Code Violation # 605.3

Are extension cords being use as permanent wiring?

Add media

IFC 2009 Fire Code Violation # 605.5

Automatic External Defibrillators

Do they have an A.E.D.?

Location:

Summary

Notes

Representative of business
Inspector

Was a copy of the report emailed to business?