Information
-
Document No.
-
Inspection Title
-
Client / Site
-
Conducted on
-
Prepared by
-
Location
-
Fire Protection Contractor
Kitchen Suppression Acceptance Report
-
Approved drawing on site.
-
Received system certification from installer.
-
Manual pull station easily accessible in the path of egress.
-
Manual pull station is 42" to 48" above floor level.
-
Manual pull station activates system.
-
Building fire alarm, if system is available, sounds upon system activation.
-
Fuel or power shut down device operates on system activation and all equipment under the hood shall shut down when the system activates.
-
Fuel or power shutdown device,must be manually reset.
-
Operation of detection device activates system, perform a nitrogen blow off test.
-
Pipe size and configuration complies with the approved plans.
-
Piping and nozzles are secured.
-
Nozzle types match appliance hazard and type of use as shown on approved plans.
-
Nozzle placement complies with the approved plans,
-
Nozzle blow off caps are in place.
-
Plenum and duct areas are protected in accordance with the approved plans.
-
Chemical container is accessible and installed in accordance with NFPA 17A 5.4.1.
-
Pressure gauges are in the operable range.
-
Listed grease filter are in place.
-
All penetrations of the hood are properly sealed.
-
The class K extinguisher shall be located within 30 ft of cooking equipment.
-
The system is tagged and certified.
Signatures
-
Fire Protection Contractor
-
Foley Fire Inspector
-
Acceptance Test Approved.