  • Location
  • Check & Confirm with Airmaster Water Treatment (WT) maintenance staff (Nicole or Lynne on watertreatment@airmaster.com.au or 03 9837 8333) to see if they have been able to obtain a copy of the regular reports from the incumbent provider for this site. FYI - There are 2 treatment systems typically installed at each site. Firstly a LU-VE wetting agent applied by a simple dosing pump, which feeds into the spray header tank. Secondly a water softening plant, which includes cylinders of polymer resin granules and a brine backwashing system

  • Airmaster to Attend site and review the condition of the installed plant and equipment, log all available parameters

  • Log the available information at the WT controller

  • pH

  • Conductivity

  • Are there any water leaks or visual faults evident at water softening station?

  • Are there any leaks or visual faults evident at LU-WET wetting agent station?

  • LU-WET canister is what percentage full?

  • Take good quality images of the coils, especially showing any surface build-up and foreign matter. Take special consideration to bottom of the unit.

  • Photograph any items flagged for follow up. Include these images within the quarterly report;

  • Are fans and spray system operational at time of inspection, note any concerns?

  • Record high pressure spray pump discharge pressure (as displayed on controller) in KPA

  • Check if pressure Pump and spray solenoids are installed as per IP weatherproof rating, or whether a cover is needed;

  • Check if activation of spray temperature setting (wet) is in line with design data sheet. Log setting

  • Design Temp (C)

  • Actual Temp (C)

  • Please record cooler leaving water set point Temp (C)

  • Please record ACTUAL cooler leaving water Temp (C)

  • Carry out visual inspection of the coil headers, looking for leaks or areas of concern. Take quality images.

  • Log the number of hours of operation of the spray system. (Maximum hours p.a. aprox. 900);

  • Inspect spray tank for cleanliness and also that vermin proof lid and mesh on overflow point installed).

  • Run LU-Wet Dosing Pump and ensure correct supply of chemical is delivered into Tank.

  • Are there any obvious local environmental concerns at the time of the inspection i.e. leaves building up from local trees, chemical drift noted from local pipe vent, etc.

  • Review fault diagnostics on main controller. Record comments on recent faults where applicable.

  • Customer Sign off

  • Airmaster check sheet is complete and has been signed off by Customer representative on site.

  • Airmaster Sign off

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.