Information

  • WO Number:

  • Item Number:

  • Customer:

  • Project:

  • Conducted on

  • Prepared by

  • Location
  • Personnel

Mechanical Check

  • Visual inspection to ensure overall quality of paint finish and general appearance

  • Physical dimensions and number of sections

  • Panel hardware and constructional bolts and fixings

  • Correct devices and components fitted including trip ratings correct to drawings

  • Electrical Connections, torque and clearances

  • Manual operation of all devices including correct function of mechanical interlocks

  • Cable termination sizes and customer access for incoming/outgoing cables

  • Correct identification and warning labels fitted

Electrical Test

  • Dielectric test at 2.5KV AC for 2 seconds between phases, phases to neutral and phases to earth

  • L1-L2

  • L1-L3

  • L2-L3

  • L1-N

  • L2-N

  • L3-N

  • L1-E

  • L2-E

  • L3-E

  • Insulation test at 1000V D.C. Resistance value greater than 999 Megohms

  • L1-L2

  • L1-L3

  • L2-L3

  • L1-N

  • L2-N

  • L3-N

  • L1-E

  • L2-E

  • L3-E

  • N-E

  • Continuity test on busbar joints

  • Operation of control equipment under simulated conditions

  • Set devices to specification or information supplied

  • Instrumentation verified

  • Earth continuity check

  • Other checks or observations:

Photographs

  • Overall view

  • Incoming device

  • Incoming connections

  • Cable Ways

  • Controls if relevant

  • Any other photos

Close out

  • Tested by:

The templates available in our Public Library have been created by our customers and employees to help get you started using SafetyCulture's solutions. The templates are intended to be used as hypothetical examples only and should not be used as a substitute for professional advice. You should seek your own professional advice to determine if the use of a template is permissible in your workplace or jurisdiction. You should independently determine whether the template is suitable for your circumstances.